INSTALLATION
The transmitter is intended for DIN rail mounting. Its drawing is presented in Figure 04.
Figure 04 –Transmitter dimensions
ELECTRICAL CONNECTIONS
Figure 05 below shows the transmitter connections to the sensor and power supply.
Terminals 1, 2 and 3 are used for sensor input. For 2-wire Pt100, terminals 2 and 3
shall be connected together.
Figure 05 –Transmitter connections –Pt100
Figure 06 –Transmitter connections –Thermocouple
It is important to follow the recommendations below:
Signal wires should be installed in grounded conduits and away from power or
contactor wires.
The instrument should have its own power supply wires, which should not be
shared with electrical motors, coils, contactors, etc.
Installing RC filters is strongly recommended at contactor coils or any other
inductors.
System failure should always be taken into account when designing a control
panel to avoid irreversible damage to equipment or people.
SPECIFICATIONS
Sensor input:User defined. The supported sensors are lited in Table 01, along
with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N and E, according IEC 60584-1 (ITS-90.
Impedance >> 1 M
Pt100: Excitation: 0.18 mA, 2 or 3-wire connection (for 2-wire
sensors, tie terminals 2 and 3 together).
= 0.00385, according to IEC 60751 (ITS-90)
Voltage: 0 to 50 mVdc. Impedance >> 1 M
Sensor Type Range Minimum measurement span
Thermocouple K 0 to 1370 °C 100 °C
Thermocouple J 0 to 760 °C 100 °C
Thermocouple R 0 to 1760 °C 400 °C
Thermocouple S 0 to 1760 °C 400 °C
Thermocouple T
0 to 400 °C
100 °C
Thermocouple N
0 to 1300 °C
100 °C
Thermocouple E
0 to 720 °C
100 °C
Pt100
-200 to 650 °C
40 °C
Voltage
0 to 50 mV
5 mV
Table 01 –Transmitter input sensors
Output: 0 to 10 Vdc, linear with respect to the measured temperature.
Total Accuracy: better than 0.3 % of the maximum range for thermocouples and
0.2 % for Pt100 and voltage (for voltage output above 100 mV).
Resolution: 0.025 V (12 bits)
Maximum Current (Load): 2 mA
Response Time: < 100 ms
Power supply: 18 to 35 Vdc
Operation Temperature: -40 to 85 °C
Humidity: 0 to 90 % RH
Protection: IP40
Electromagnetic compatibility: EN 50081-2, EN 50082-2
No isolation between input, voltage output and power supply.
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Housing: ABS plastic. Dimensions: Refer to Figure 04.
T E M P E R A T U R E T R A N S M I T T E R
T X R A I L 0 - 1 0 V D C
O P E R A T I N G M A N U A L
Man 5001496
CONFIGURATION
If the transmitter is already configured as required by the application (sensor type,
range, etc), it may be installed and used right away. However, if a distinct
configuration is required, this can be done through the TxConfig software and the
TxConfig Interface.
The TxConfig interface and software can be purchased from the manufacturer or at its
authorized distributors and representatives. Updates for the software are available at
our website. To install the TxConfig software, run the Tx_setup.exe file and follow the
instructions.
Serial port configuration errors may occur when other devices are sharing the
same port (ex.: Palm Hot Synch). Close all serial port applications prior to
using the TxConfig software.
The TxConfig interface connects the transmitter to the PC, as shown in Figures 01
and 02. There are two types of interface: TxConfig-RS232 and TxConfig-USB.
Figure 01 –TxConfig Interface connections model RS232
Figure 02 –TxConfig Interface USB connections
The TxConfig interfaces contain dedicated circuitry for proper
communication between transmitters and computer. Always make use of
the TxConfig interfaces for configuration purposes, otherwise the
transmitters may get damaged, voiding the warranty.
Once the connection is accomplished, the software shows the configuration options
of the transmitter model attached. Access the Help for usage instructions.
The TxConfig screen in shown in Figure 03.
Figure 03 –TxConfig main screen
The fields in the screen mean:
1. Input Sensor: Choose the desired temperature sensor among the available
options. See Table 01.
2. Measuring Range: Defines the beginning and the end of the range.
Lower Range Value: Sets the value of the input signal (temperature or mV)
associated to the 0 V output.
Upper Range Value: Sets the value of the input signal thal Will correspond to
the 10 V output.
When the Lower Range Value is configured with a value higher than the Upper
Range Value, the voltage output will have a decrescent behavior (10-0 Vdc).
The values configured in these fields can not be beyond the sensor measuring
range. The minimum span value has to be observed as well. See Table 01.
3. Line Noise Rejection: The transmitter incorporates a digital filter to cancel the
induced noise from the 50 or 60 Hz systems. For better performance, select the
line frequency used in your country.
4. Sensor Failure Detection: Establishes the transmitter output behavior (Upscale or
Downscale) in the presence of a sensor fail.
5. Zero Correction: Allows for small sensor corrections. See item Operating.
6. Device Information: The Device Information box contains relevant data
concerning a particular transmitter. Please pass along this information when
contacting the technical assistance department.
7. Read Device: Brings to the screen the current transmitter parameters
configuration.
8. Apply: Sends a new configuration to the transmitter.
Note: The factory default configuration is (unless otherwise specified or ordered):
Pt100 input, 0 to 100 ºC;
60 Hz filtering and up scale (10 Vdc) output for sensor fail.
OPERATION
All input types and the 4-20 mA output current are factory calibrated and have no
need for user adjustment.
However, if desired by the user, a manual offset trim is implemented to provide fine
adjustments to the signal in the field. This is accomplished by the front keys ZERO+
and ZERO-, located under the frontal label in order to avoid accidental adjustments.
Using a small tool (2 mm diameter), press and hold the desired key for at least 2
seconds to increase or decrease the output current. When the output current is
reached, the key must be released.
The offset correction can also be accomplished by the TxConfig software. See in
Figure 03 the Zero Correction field for this purpose. The serial adaptor can be
connected to the transmitter while it is operating in the process.
The user must choose the sensor and configure the sensor span which best suit the
application. The sensor span must not exceed the maximum range supported by the
transmitter for a particular sensor, neither be lower than the minimum span.
It is important to note that the transmitter accuracy is related to the total sensor span
of a sensor, regardless of the output scale (span) configured. Example:
Pt100; maximum input span of –200 to +650 °C, 0.2 % accuracy.
Maximum error: 1.7 °C (0.2 % of 850 °C)
This error is the same no matter if total span is used (-200 to 650 °C) or a
narrower user-defined span is used, like 0 to 100 °C.
Note: When using a Pt100 simulator, make sure the transmitter Pt100 excitation
current (0.18 mA) is compatible with the simulator specification.
The transmitter must be powered in order to be configured. The TxConfig-USB
interface provides the necessary power. The TxConfig-RS232 interface, however,
requires an auxiliary supply to guarantee a reliable communication with the
computer. A recommended solution is to power the transmitter by an external power
supply (18-35 Vdc), as shown in Figure 01.

Other Novus Transmitter manuals

Novus TxIsoRail User manual

Novus

Novus TxIsoRail User manual

Novus NP600 User manual

Novus

Novus NP600 User manual

Novus RHT-WM User manual

Novus

Novus RHT-WM User manual

Novus TxBlock-USB User manual

Novus

Novus TxBlock-USB User manual

Novus NP400 User manual

Novus

Novus NP400 User manual

Novus RHT Climate-WM Series User manual

Novus

Novus RHT Climate-WM Series User manual

Novus RHT-P10 User manual

Novus

Novus RHT-P10 User manual

Novus TL400-V User manual

Novus

Novus TL400-V User manual

Novus TxIsoBlock-HRT User manual

Novus

Novus TxIsoBlock-HRT User manual

Novus TL400-I User manual

Novus

Novus TL400-I User manual

Novus TxIsoBlock-HRT User manual

Novus

Novus TxIsoBlock-HRT User manual

Novus TxBlock-USB User manual

Novus

Novus TxBlock-USB User manual

Novus TxIsoPack-HART User manual

Novus

Novus TxIsoPack-HART User manual

Novus NP-430D User manual

Novus

Novus NP-430D User manual

Novus TxMiniBlock User manual

Novus

Novus TxMiniBlock User manual

Novus NP620 User manual

Novus

Novus NP620 User manual

Novus TxIsoRail User manual

Novus

Novus TxIsoRail User manual

Novus TxRail User manual

Novus

Novus TxRail User manual

Novus RHT-Air User manual

Novus

Novus RHT-Air User manual

Novus TEMP-WM User manual

Novus

Novus TEMP-WM User manual

Novus RHT-WM-485-LCD User manual

Novus

Novus RHT-WM-485-LCD User manual

Novus TxIsoRail-HRT User manual

Novus

Novus TxIsoRail-HRT User manual

Novus TXMINI-DIN43650 User manual

Novus

Novus TXMINI-DIN43650 User manual

Novus TxIsoRail-HRT User manual

Novus

Novus TxIsoRail-HRT User manual

Popular Transmitter manuals by other brands

Ados T060E User and installation manual

Ados

Ados T060E User and installation manual

evertz 7700 Series manual

evertz

evertz 7700 Series manual

Teleco TVSLC868A01 manual

Teleco

Teleco TVSLC868A01 manual

Riken Keiki SD-1DOX operating manual

Riken Keiki

Riken Keiki SD-1DOX operating manual

NIVELCO EchoTREK S-300 Installation and programming manual

NIVELCO

NIVELCO EchoTREK S-300 Installation and programming manual

EnOcean PTM 215ZE user manual

EnOcean

EnOcean PTM 215ZE user manual

Absolute Process Instruments API 6380 G HV Series quick start guide

Absolute Process Instruments

Absolute Process Instruments API 6380 G HV Series quick start guide

rojaflex WSR-1 Original assembly and operating instructions

rojaflex

rojaflex WSR-1 Original assembly and operating instructions

HumanTechnik A-2450-0 operating instructions

HumanTechnik

HumanTechnik A-2450-0 operating instructions

Conrad 20 51 55 operating instructions

Conrad

Conrad 20 51 55 operating instructions

M-system 10VS4 instruction manual

M-system

M-system 10VS4 instruction manual

Bosch CRS-SB-423FI operating instructions

Bosch

Bosch CRS-SB-423FI operating instructions

Webasto Telestart T80 operating instructions

Webasto

Webasto Telestart T80 operating instructions

Matsushima MWLM-FM79 instruction manual

Matsushima

Matsushima MWLM-FM79 instruction manual

Vaisala HUMICAP HMT310 user guide

Vaisala

Vaisala HUMICAP HMT310 user guide

ALGE-Timing RLS1n manual

ALGE-Timing

ALGE-Timing RLS1n manual

Evikon PluraSens E2658-PID user manual

Evikon

Evikon PluraSens E2658-PID user manual

GRASS VALLEY Python 3G Series user guide

GRASS VALLEY

GRASS VALLEY Python 3G Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.