Novus TxIsoBlock-HRT User manual

NOVUS AUTOMATION 1/4
TxIsoBlock
-HRT
TEMPERATURE TRANSMIT
TER - OPERATING MANUAL – V1.1x
INTRODUCTION
The TxIsoBlock-HRT is a configurable head mount temperature
transmitter widely required in various industrial processes. Its
universal input can be configured to read RTDs, thermocouples and
mV signals.
It converts the input signal into a 4-20 mA linear output proportional
to the configured range. The TxIsoBlock-HRT uses the HART®
communication protocol over the 4-20 mA output current loop.
The input and output are electrically isolated, enhancing their
performance and user and system safety.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in
Table 1, along with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E and B, according to
IEC 60584 (ITS-90).
Impedance >> 1 MΩ
Pt100: Excitation 0.15 mA, α= 0.00385, according IEC 60751
(ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
Pt1000: Excitation 0.20 mA, α= 0.00385, according IEC 60751
(ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
NTC R25°C: 10 kΩ±1 %, B25/85 = 3435.
Voltage: 0 to 50 mVdc. Impedance >> 1 MΩ.
Sensor Type
Maximum Measurement
Range
Minimum
Retransmission Range
Thermocouple K
-150 to 1370 °C
(-238 to 2498 °F)
50 °C
(90 °F)
Thermocouple J
-100 to 760 °C
(-148 to 1400 °F)
50 °C
(90 °F)
Thermocouple R
-50 to 1760 °C
(-58 to 3200 °F)
200 °C
(360 °F)
Thermocouple S -50 to 1760 °C
(-58 to 3200 °F)
200 °C
(360 °F)
Thermocouple T -160 to 400 °C
(-256 to 752 °F)
50 °C
(90 °F)
Thermocouple N -270 to 1300 °C
(-454 to 2372 °F)
50 °C
(90 °F)
Thermocouple E
-90 to 720 °C
(-130 to 1328 °F)
50 °C
(90 °F)
Thermocouple B
500 to 1820 °C
(932 to 3308 °F)
200 °C
(360 °F)
Pt100
-200 to 650 °C
(-328 to 1202 °F)
30 °C
(54 °F)
Pt1000
-200 to 650 °C
(-328 to 1202 °F)
30 °C
(54 °F)
NTC -30 to 120 °C
(-22 to 248 °F)
10 °C
(18 °F)
Voltage 0 to 50 mV 3 mV
Table 1 – Sensors accepted by the transmitter
Switch-on delay: < 10 s with damping filter set to factory setting.
The accuracy is only guaranteed after 15 min.
Terms of reference for accuracy: Ambient: 25 °C (77 °F); voltage:
24 Vdc, load: 250 Ω. Stabilization time of 15 minutes after any
setting is required.
Temperature effect:
NTC: < 0.11 % FS / 25 °C (45 °F)
Other sensors: < 0.05 % FS / 25 °C (45 °F)
(FS = Full Scale).
Response time: Typical 6 s with factory damping filter. This is the
maximum time between a temperature step being applied in the input
and the output reaching 90 % of the corresponding value.
HART protocol version:7.
RTD cable resistance effect: 0.005 °C (0.009 °F) / Ω.
Maximum allowable cable resistance for RTD: 25 Ω.
Accuracy: Calibration error in relation to sensor measuring range
(Full Scale).
Sensor Type
CURRENT LOOP HART
Typical
Accuracy
Minimum
Accuracy
Typical
Accuracy
Minimum
Accuracy
Pt100
(-200 to 650 °C)
(-328 to 1202 °F)
0.08 % 0.15 % 0.05 % 0.15 %
Pt1000
(-200 to 650 °C)
(-328 to 1202 °F)
0.07 % 0.15 % 0.04 % 0.15 %
K, J, R, S, T, N,
E, B 0.07 % (*) 0.15 % (*) 0.04 % (*) 0.15 % (*)
mV 0.07 % 0.15 % 0.04 % 0.15 %
NTC
0.20 °C
(0.36 °F)
0.45 °C
(0.81 °F)
0.15 °C
(0.27 °F)
0.45 °C
(0.81 °F)
Table 2 – Accuracy of input types
(*) Add Cold Junction compensation: < ± 1 °C (1.8°F).
Power supply influence: < 0.005 % / V (percentage of the full
measure range).
Output (4-20 mA):4-20 mA current, 2-wired; linear and proportional
to the configured range.
Output resolution (4-20 mA): 0.25 µA.
Power supply: 8.5 to 36 Vdc (output 4-20 mA).
Maximum load (RL): RL (max.) = (Vdc – 8.5) / 0.0215 [Ω]
Where: Vdc = Power supply voltage
(8.5 to 36 Vdc)
Operating temperature: -40 to 85 °C (-40 to 185 °F).
Humidity: 0 to 90% RH.
It presents electrical isolation between input and output of 1.5
kVrms.
Internal protection against reverse polarity of the supply voltage.
Cold Junction compensation for thermocouples.
Connection wire cross section: 0.14 to 1.5 mm².
Screw Tightening: 0.8 Nm.
Housing: Polyamide.
Certification: CE and HART®.

TxIsoBlock-HRT
NOVUS AUTOMATION 2/4
CONFIGURATION
When the transmitter is used with the factory setting, no further
action is required and the transmitter is ready to be installed.
Changes to the configuration are possible through the TxConfig II
software, provided free of charge.
The TxConfig II configuration software allows the device configuration.
A TxConfig-HRT interface is required to allow the communication
between a computer and the device. The Txconfig II configuration
software is continuously updated and new versions can be downloaded
at no charge from the manufacturer’s website. To install, execute the
TxConfigIISetup.exe file and follow the instructions.
The interface connects the transmitter to the computer, as shown in
Fig. 1:
Fig. 1 – TxConfig-HRT Interface connection to the TxIsoBlock-HRT
SOFTWARE CONFIGURATION
Fig. 2– TxConfig II software main screen
The fields in the screen mean:
1. General Information: This field shows information that identifying
the transmitter. This information should be sent to the
manufacturer in an eventual request for technical assistance.
2. Sensor: Select the type of sensor to be used. See Table 1.
3. Unit: Select the temperature unit to °C (Celsius) or °F
(Fahrenheit).
4. Range: Sets de measurement range of the transmitter.
Lowest Limit: Equivalent temperature for a current of 4 mA.
Highest Limit: Equivalent temperature for a current of 20 mA.
Sensor Range: The values chosen cannot exceed the Range of
Sensor shown in this field. See Table 1 of this manual.
Minimum Range:It is not possible to establish a range with a
span less than the Minimum Range value indicated below in this
field. See Table 1 of this manual.
5. HART Information:
Tag: Field with a brief identification of the device (up to 8
characters).
Descriptor: Descriptor used by the master for registering (up to
16 characters).
Message: Message used by the master for registering (up to 32
characters).
6. Sensor Failure: It establishes the output behavior, when the
transmitter indicates a failure, as recommended NAMUR NE 43:
Minimum: Output current goes to <= 3.6 mA (down-scale),
typically used for refrigeration.
Maximum: Output current goes to >= 21.5 mA (up-scale),
typically used for heating.
7. Zero Offset: It corrects small deviations presented in the
transmitter output, for example, when the sensor is replaced.
8. Filter: Damping filter.
The damping filter changes the response time of the transmitter in
order to smooth the variations in the output. The value set in the
filter indicates the time interval at which the PV will reach 63% of
its final value.
The factory setting is 1.0 s and can be changed from 0 s to 32 s.
In a case with variation from 0 ° C to 100 ° C, considering the
factory configuration and after 1.0 s, the PV value will be 63 °C.
With zero value in the filter, the function is disabled.
9. Enable write protection: When activated, the configuration
setting is not allowed.
10. Send Configuration: It applies the new setup. Once sent, the
setup will be immediately adopted by the transmitter.
11. Read Configuration: Reads the current setup in the transmitter
connected. The screen now presents the current setup that may
be changed by the user.
FACTORY SETTING
•Sensor: Pt100 3-wire, range 0 to 100 °C;
•Maximum output for sensor failure;
•0 °C zero correction;
•Unit: °C;
•Filter: 1.0 s.
It is possible to configure the device via third-party
software and with the help of an FSK modem to perform
HART® communication.
An EDD (Electronic Device Descriptor) file is available,
which can be used with compatible systems and allows
access to the settings and supervise the transmitter.

TxIsoBlock-HRT
NOVUS AUTOMATION 3/4
Fig. 3– Connections with handheld terminal
MECHANICAL INSTALLATION
The TxIsoBlock-HRT transmitter is suitable to be installed in heads.
Vibrations, moisture and extreme temperatures, electro-magnetic
interference, high voltage and other interferences can permanently
damage the unit and could cause error in the measured value.
DIMENSIONS
Fig. 4– Transmitter dimensions
ELECTRICAL INSTALLATION
•Polyamide housing to the terminals.
•Section of the cable used: 0.14 to 1.5 mm².
•Recommended torque in the terminal: 0.8 Nm.
RECOMMENDATIONS FOR INSTALLATION
•Conductors of small electrical signals must be distant from
activation or high-tension/current conductors, preferably passing
through grounded conduits.
•A specific electrical power supply network should be provided for
instruments use only.
•In controlling and monitoring applications, possible consequences
of any system failure must be considered in advance.
•RC filters (47 Ωand 100nF, serial) in inductor charges
(contactors, solenoids, etc.) are recommended.
ELECTRICAL CONNECTIONS
The figures next show the electrical connections required. The
terminals 3, 4, 5 and 6 are dedicated to the sensor connection.
LOAD represents the 4-20 mA current measuring device (indicator,
controller, recorder, etc.).
Pt100/ Pt1000 2-WIRE
Note: When used the Pt100/ Pt1000 2-wire, the terminals 3 and 4
must be interconnected, according to the figure below.
To use the Pt100/ Pt1000 2-wire, you must configure the Pt100/
Pt1000 3-wire option in TxConfig II.
The Pt100/ Pt1000 wire length should be less than 30 cm to
maintain the measurement error within specifications (electrical
resistance).
Fig. 5– Transmitter electrical connections (Pt100/ Pt1000 2-wire)
Pt100/ Pt1000 3-WIRE
Fig. 6– Transmitter electrical connections (Pt100/ Pt1000 3-wire)
Pt100/ Pt1000 4-WIRE
Fig. 7– Transmitter electrical connections (Pt100/ Pt1000 4-wire)
Pt100/ Pt1000 3 and 4-wire: The use of wires with same length and
gauge is recommended for a better resistance compensation. The
transmitter compensates up to 25 Ωper wire.
THERMOCOUPLE
Fig. 8– Transmitter electrical connections (Thermocouple)

TxIsoBlock-HRT
NOVUS AUTOMATION 4/4
VOLTAGE (0-50 mV)
Fig. 9– Transmitter electrical connections (0-50 mV)
NTC
Fig. 10 – Transmitter electrical connections (NTC)
OUTPUT (4-20 mA)
Fig. 11 – Transmitter electrical connections ( 4-20 mA)
OPERATION
The transmitter is factory calibrated with standardized sensors, not
requiring any adjustment by the user.
Small corrections can be accomplished through the TxConfig II
software (in units of temperature).
The user may choose the sensor and the range that best fits its
application. The range chosen must not exceed the maximum
measuring range defined for the sensor and must not be less than
the minimum range for the sensor.
It is important to note that the accuracy of the transmitter refers to the
maximum range of the sensor used, regardless of the actual range.
Example:
•The sensor Pt100 has a max. range of -200 to 650 °C and total
accuracy de 0.08 %.
•Thus, we can have an absolute error up to 0.68 °C (0.08% of
850 °C).
•This error is possible in a wide range as the maximum (-200 to
650 ° C) or in a narrower range, set by the user as (example) 0
to 100 ° C.
SAFETY INFORMATION
Control system projects must take into account that any part of the
system has the potential to fail. This product is not a safety or
protection device and its internal alarms do not provide protection in
case of failure. External safety devices should be provided whenever
there is a risk to persons or property.
The performance and specifications of this product may be affected
by your operating environment and installation. It is the responsibility
of the user to ensure adequate grounding, shielding, cable routing
and noise filtering, following local regulations and good installation
practices and electromagnetic compatibility.
SUPPORT AND MAINTENANCE
This product does not contain any serviceable parts. Contact our
local distributor for an authorized service.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
Table of contents
Other Novus Transmitter manuals

Novus
Novus NP600 User manual

Novus
Novus RHT-WM User manual

Novus
Novus RHT-WM-485-LCD User manual

Novus
Novus NP785 User manual

Novus
Novus TEMP-WM User manual

Novus
Novus RHT-P10 User manual

Novus
Novus TL400-I User manual

Novus
Novus RHT Climate-WM Series User manual

Novus
Novus TxMiniBlock User manual

Novus
Novus TxIsoRail User manual

Novus
Novus TxRail User manual

Novus
Novus TxRail-USB User manual

Novus
Novus TXMINI-M12 User manual

Novus
Novus NP785-50 User manual

Novus
Novus TxBlock-USB User manual

Novus
Novus RHT-XS User manual

Novus
Novus TXMINI-DIN43650 User manual

Novus
Novus TxBlock-USB User manual

Novus
Novus NP785 User manual

Novus
Novus TXRAIL Series User manual