TxMini-M12 Transmitter
NOVUS AUTOMATION 2/3
The fields in the screen mean:
1. General Information: This field shows information that identifying
the transmitter. This information should be sent to the
manufacturer in an eventual request for technical assistance.
2. Sensor: Select the type of sensor to be used. See Table 1.
3. Measuring Range: Sets de measurement range of the
transmitter.
Lower Range Limit: equivalent temperature for a current of 4
mA.
Upper Range Limit: equivalent temperature for a current of 20
mA.
Sensor Range
The values chosen cannot exceed the range of sensor shown in
this field. See Table 1 of this manual.
Minimum Range
Do not set a lower band (span) that the Minimum Range
indicated below in this same field. See Table 1 of this manual.
4. Sensor Failure: It establishes the output behavior, when the
transmitter indicates a failure:
Minimum: output current goes to < 3.8 mA (down-scale), typically
used for refrigeration.
Maximum: output current goes to > 20.5 mA (up-scale), typically
used for heating.
5. Zero Correction: It corrects small deviations presented in the
transmitter output, for example, when the sensor is replaced.
6. Send Configuration: It applies the new setup. Once sent, the
setup will be immediately adopted by the transmitter.
7. Read Configuration: Reads the current setup in the transmitter
connected. The screen now presents the current setup that may
be changed by the user.
FACTORY SETTING:
•Sensor: Pt100 3-wire, range 0 to 100 °C
•Sensor failure: upscale (maximum).
•0 °C zero correction.
•Unit: °C;
•Output: 4 to 20 mA.
Upon purchase order, the user can define a specific setup.
MECHANICAL INSTALLATION
TxMini-M12 Transmitter was designed to be installed in tubes and
other small places. Vibrations, moisture and extreme temperatures,
electro-magnetic interference, high voltage and other interferences
can permanently damage the unit, and could cause error in the
measured value.
Fig. 2– Dimensions of the transmitter
ELECTRICAL INSTALLATION
•Polyamide enclosure.
•Section of the cable used: 0.14 to 1.5 mm ²
RECOMMENDATIONS FOR INSTALLATION
•Sensor signals conductors must go through the plant system
separate from power leads (loop), if possible in grounded
conduits.
•The instruments must be powered from the instrumentation power
supply circuit.
•In control and monitoring applications is essential to consider
what can happen when any part of the system fails.
•It is recommended the use of suppressors in contact coils,
solenoids and any inductive load.
POWER AND COMMUNICATION CONNECTION
Terminal 2 is used to communicate with the transmitter (TxConfig-
M12 interface must be used).
Terminal 4 can be connected to cable shield, if needed.
1 LOOP +