Novus TxBlock-USB User manual

NOVUS AUTOMATION 1/5
TxBlock
-USB Transmitter
TEMPERATURE TRANSMIT
TER - OPERATING MANUAL – V1.0x I
INTRODUCTION
The TxBlock-USB is a 4-20 mA 2-wire temperature transmitter for
head mount, powered by the current loop. The output current is
linearized and adjusted in fuction of the input sensor type and range
configured.
Its configuration is accomplished by connecting the transmitter to a
PC USB port without the need of any dedicated interface. The
configuration does not require that the transmitter be powered.
MECHANICAL INSTALLATION
The TxBlock-USB transmitter is suitable to be installed in heads.
Vibrations, moisture and extreme temperatures, electro-magnetic
interference, high voltage and other interferences can permanently
damage the unit, and could cause error in the measured value.
DIMENSIONS:
Fig. 1– Transmitter dimensions
ELECTRICAL INSTALLATION
•Section of the cable used: 0.14 to 1.5 mm ².
•Recommended torque in the terminal: 0.8 Nm.
RECOMMENDATIONS FOR INSTALLATION
•Sensor signals conductors must go through the plant system
separate from power leads (loop), if possible in grounded
conduits.
•The instruments must be powered from the instrumentation power
supply circuit.
•In control and monitoring applications is essential to consider
what can happen when any part of the system fails.
•It is recommended the use of suppressors in contact coils,
solenoids and any inductive load.
ELECTRICAL CONNECTIONS
The figures below show the electrical connections required. The
terminals 3, 4, 5 and 6 are dedicated to the sensor connection.
LOAD represents the 4-20 mA current measuring device (indicator,
controller, recorder, etc.).
PT100 2-WIRE
Note: When the Pt100 2-wire is selected, the terminals 3 and 4 must
be interconnected, according to the figure below.
The Pt100 wire length should be less than 30 cm to maintain the
measurement error within specifications (electrical resistance).
Fig. 2– Transmitter electrical connections (Pt100 2-wire)
PT100 3-WIRE
Fig. 3– Transmitter electrical connections (Pt100 3-wire)
PT100 4-WIRE
Fig. 4– Transmitter electrical connections (Pt100 4-wire)

TxBlock-USB
NOVUS AUTOMATION 2/5
Pt1000 3-wire / Pt100 3-wire and 4-wire: For appropriate cable
resistance compensation they should be equal for all legs. Maximum
wire resistance is 25 Ωper wire leg. Usage of a 3 or 4 wire with
conductors of equal length and gauge is recommended.
NTC 2-WIRE
Fig. 5– Transmitter electrical connections (NTC 2-wire)
THERMOCOUPLES
Fig. 6– Transmitter electrical connections (Thermocouple)
VOLTAGE (0-50 mV)
Fig. 7– Transmitter electrical connections (0-50 mV)
CONFIGURATION
When the trasmitter is used with the factory setting, no further action
is required and the transmitter is ready to be installed.
Changes to the configuration are possible through the TxConfig II
software or the TxConfig application, provided free of charge.
The TxBlock-USB Setup Kit consisting of the TxConfig II software and
USB cable can be purchased from the manufacturer or any authorized
distributor.
The software is continuously updated and new versions can be
downloaded at no charge from the manufacturer’s website. To install,
execute the TxConfigIISetup.exe file and follow the instructions.
The setup application is only available for Android smartphones and
also can be downloaded for free in the Google Play Store. To configure
the device through the application, an On The Go (OTG) adapter is
required. The procedure for using this adapter will be explained
throughout this manual.
Fig. 8– USB cable connection
During the setup, the transmitter is powered by the USB, not
requiring an external power supply.
The transmitter setup can also be made by connecting it to the loop,
using the loop power supply. There is no electrical insulation between
the transmitter and the communication port (interface), therefore it is
not recommended to configure it with the sensor inlet connected to the
process. See Fig. 9.
Fig. 9– USB cable connections – Loop powered
After these connections, the user must run the TxConfig II software
and, if necessary, consult the Help topic to help using the software.
For more information on how to connect the TxBlock-USB to the
smartphone itself and to configure the device, see chapter
SMARTPHONE CONNECTIONS.
The USB communication port (interface) of the
TxBlock-USB is not electrically insulated from the
transmitter’s input.

TxBlock-USB
NOVUS AUTOMATION 3/5
SOFTWARE AND APPLICATION CONFIGURATION:
Fig. 10 – TxConfig II software main screen
Fig. 11 – TxConfig application main screen
The fields in the screen mean:
1. General Information: This field shows information that identifying
the transmitter. This information should be sent to the
manufacturer in an eventual request for technical assistance.
2. Sensor: Select the type of sensor to be used. See Table 1.
3. Measuring Range: Sets de measurement range of the
transmitter.
Lower Range Limit: equivalent temperature for a current of 4 mA.
Upper Range Limit: equivalent temperature for a current of 20 mA.
Sensor Range
The values chosen cannot exceed the range of sensor shown in
this field. See Table 1 of this manual.
Minimum Range
Do not set a lower band (span) that the Minimum Range
indicated below in this same field. See Table 1 of this manual.
4. Sensor Failure: It establishes the output behavior, when the
transmitter indicates a failure:
Minimum:Output current goes to < 3.6 mA (down-scale),
typically used for refrigeration.
Maximum: Output current goes to > 22.0 mA (up-scale), typically
used for heating.
5. Zero Correction: It corrects small deviations presented in the
transmitter output, for example, when the sensor is replaced.
6. Send Configuration: It applies the new setup. Once sent, the
setup will be immediately adopted by the transmitter.
7. Read Configuration: Reads the current setup in the transmitter
connected. The screen now presents the current setup that may
be changed by the user.
FACTORY SETTING:
•Sensor: Pt100 3-wire, range 0 to 100 °C
•Sensor failure: upscale (maximum).
•0 °C zero correction.
•Unit: °C;
•Output: 4-20 mA.
Upon purchase order, the user can define a specific setup.
SMARTPHONE CONNECTIONS
With the help of a specific cable, which allows smartphones to
recognize and configure TxBlock-USB when running the TxConfig
application, Android smartphones with On the Go (OTG) technology
can be directly connected to the device via the Micro-USB.
To do this, it is necessary to observe the connection mode of the
cable On the Go in the device, as can be seen in Fig. 12:
Fig. 12 – On the Go connection cable
Incorrectly positioning the cable end may cause
the device to be unrecognized by the application.

TxBlock-USB
NOVUS AUTOMATION 4/5
CONFIGURING TXBLOCK-USB WITH TXCONFIG APPLICATION
FOR ANDROID:
Once the connection between the smartphone and the TxBlock-
USB is made, the device will send the following message:
Fig. 13 – USB device connected
For the correct operation of the application, the option "Open
TxConfig when this USB device is connected?" must be checked and
then click the OK button.
After that, it will automatically run the TxConfig application, which
has already been previously installed on the smartphone, and will
display the following message:
Fig. 14 – Reading device
The application will automatically switch to the configuration screen
(see Fig. 11), where it will be possible to configure the TxBlock-USB.
OPERATION
The sensor offset can be changed through the TxConfig II software
or the TxConfig app.
The USB cable may be connected to the transmitter without causing
any measurement errors. See item Zero Correction in the chapter
CONFIGURATION of this manual.
The uer must choose the most suitable sensor and range to the
process. The chosen range must not exceed the maximum range of
measurement defined for the sensor and should not be smaller than
the minimum range for the same sensor.
It is important to note that the transmitter accuracy is based on the
maximum range of the sensor used, even when a narrower range is
programmed.
Example:
•The Pt100 sensor in the range 0 to 100 °C and accuracy of
0.12 %, the maximum error will be 1.02 °C (0.12 % de 850 °C).
•The Pt100 sensor in the range 500 to 600 °C and accuracy of 0.19 %,
the maximum error will be 1.61 °C (0.19 % of the 850 °C).
Note: When measurements are made at the transmitter, see if the
Pt100 excitation current required by the calibrator is compatible with
the Pt100 excitation current used in the transmitter: 0.8 mA.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in
Table 1, along with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E and B accoding to
IEC 60584 (ITS-90). Impedance >> 1 MΩ
Pt100: Type 3-wire, Excitation 0.8 mA, α= 0.00385,
according IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4
together.
Pt1000: Type 3-wire, Excitation 0.65 mA, α= 0.00385,
according IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4
together.
NTC R25°C: 10 kΩ±1 %, B25/85 = 3435
Voltage: 0 to 50 mVdc. Impedance >> 1 MΩ
Sensor Type
Maximum Measurement
Range
Minimum Measurement
Range
Voltage
0 to 50 mV
5 mV
Thermocouple K
-150 to 1370 °C
100 °C
Thermocouple J
-100 to 760 °C
100 °C
Thermocouple R
-50 to 1760 °C
400 °C
Thermocouple S
-50 to 1760 °C
400 °C
Thermocouple T
-160 to 400 °C
100 °C
Thermocouple N
-270 to 1300 °C
100 °C
Thermocouple E
-90 to 720 °C
100 °C
Thermocouple B
500 to 1820 °C
400 °C
Pt100
-200 to 650 °C
40 °C
Pt1000
-200 to 650 °C
40 °C
NTC
-30 to 120°C
40 °C
Table 1 – Sensors accepted by the transmitter
Switch-on delay: < 2.5 s. The accuracy is only guaranteed after 15
min.
Terms of reference: Ambient: 25 ° C; voltage: 24 Vdc, load: 250 Ω;
settling time: 10 minutes.
Temperature Effect: < ±0.16 % / 25 °C
Response time: Typical 1.6 s.
Maximum voltage allowed at input terminals no sensor: 3 V.
RTD current: 800 µA.
RTD cable resistance effect: 0.005 °C / Ω
Maximum allowable cable resistance for RTD: 25 Ω.
Sensor Type
Typical
Accuracy
Minimun
Accuracy
Pt100 / Pt1000
(-150 to 400 °C)
0.10 % 0.12 %
Pt100 / Pt1000
(-200 to 650 °C)
0.13 % 0.19 %
mV, K, J, T, E, N, R, S, B
0.1 % (*)
0.15 % (*)
NTC
0.3 °C
0.7 °C
Table 2 – Calibration error, percentage of the full measurement range
(*) Add cold junction compensation: < ± 1 °C.
Power supply influence: 0.006 % / V typical (percentage of the full
measure range).
Output:4-20 mA or 20-4 mA current, 2-wired; linear in relation to the
temperature measurement by the selected sensor.
Output Resolution: 2 µA.
Power supply: 10 to 35 Vdc, across the transmitter;
Maximum load (RL): RL (max.) = (Vdc – 10) / 0.02 [Ω]
Where: Vdc= Power supply voltage (10-35 Vdc)
Operating Temperature: -40 to 85 °C
Humidity: 0 to 90 % RH
Electromagnetic Compatibility: EN 61326-1:2006

TxBlock-USB
NOVUS AUTOMATION 5/5
No electrical isolation between input and output.
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Dimensions: 43.5 mm (diameter) x 20.5 mm (height)
Connection Wire Cross Section: 0.14 a 1.5 mm²
Screw Tightening: 0.8 Nm
Housing: ABS UL94-HB
SAFETY INFORMATION
Any control system design should take into account that any part of
the system has the potential to fail. This device is not a protection or
safety device and its alarms are not intended to protect against
device failures. Independent safety devices should be always
provided if personnel or property are at risk.
Device performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.
SUPPORT AND MAINTENANCE
This device contains no serviceable parts inside. Contact our local
distributor in case you need authorized service.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
Table of contents
Other Novus Transmitter manuals

Novus
Novus TXMINI-M12-485 User manual

Novus
Novus TEMP-WM User manual

Novus
Novus TxIsoPack User manual

Novus
Novus TxIsoRail0-10Vdc User manual

Novus
Novus RHT Climate WM User manual

Novus
Novus TXMINI-DIN43650 User manual

Novus
Novus TxRail User manual

Novus
Novus TxIsoRail User manual

Novus
Novus RHT-WM-485-LCD User manual

Novus
Novus NP785 User manual

Novus
Novus RHT Climate-WM Series User manual

Novus
Novus TxRail-USB User manual

Novus
Novus TxIsoRail 0-10 Vdc User manual

Novus
Novus RHT-WM User manual

Novus
Novus DigiRail-VA User manual

Novus
Novus TxIsoRail User manual

Novus
Novus TxMiniBlock User manual

Novus
Novus RHT-WM-485-LCD User manual

Novus
Novus TL400-V User manual

Novus
Novus TxRail-USB User manual