manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Novus
  6. •
  7. Transmitter
  8. •
  9. Novus TxRail User manual

Novus TxRail User manual

- -
INSTALLATION
The TxRail transmitter is intended for DIN rail mounting. Its drawing is presented in
figure 4.
19 mm
69 mm
7 mm
77 mm
78 mm
7 mm
7
7
m
m
Figure
4 – TxRail dimensions
ELECTRICAL CONNECTIONS
Connector specification:
♦
Insulating material: Polyamide, self-extinguishing to UL 94, V-0
♦
Connection wire cross section: 0,14 – 4,0 mm²
♦
Screw tightening torque: 0,8 Nm / 7.0 lb-in
♦
Terminal block: CuZn
It is important to follow the recommendations below:
♦
Signal wires should be installed in grounded conduits and away from power or
contactor wires.
♦
The instrument should have its own power supply wires, which should not be
shared with electrical motors, coils, contactors, etc.
♦
Installing RC filters is strongly recommended at contactor coils or any other inductors.
♦
System failure should always be taken into account when designing a control
panel to avoid irreversible damage to equipment or people.
Figure 5 below shows the TxRail connections to the sensor and power supply.
Terminals 1, e 3 are used for sensor input. For -wire Pt100, terminals and 3
shall be connected together.
ZERO
TRANSMISOR
ZERO
1
6
5
3
4
LOAD
POWER SUPPLY
Pt100 3 WIRE SENSOR
Figure 5 – TxRail wiring (Pt100)
Figure 6 below shows the thermocouple wiring.
TRANSMISOR
1
6
5
3
4
THERMOCOUPLE
ZERO
ZERO
LOAD
POWER SUPPLY
Figure 6 – TxRail wiring (Thermocouple)
The LOAD represents the input shunt of an instrument measuring the 4- 0 current
loop.
OPERATION
All input types and the 4- 0 mA output current are factory calibrated. However, a
manual offset trim is implemented to provide fine adjustments to the signal in the
field. This is accomplished by the front keys ZERO+ and ZERO-. Using a small tool,
press and hold the desired key for at least seconds to increase or decrease the
output current. The offset adjustment is capable of varying the output current by an
amount equal to ±0.80 mA relative to the original calibration..
The offset correction can also be accomplished by the TxConfig software. See in
Figure 3 the ero Correction field for this purpose. The serial adaptor can be
connected to the transmitter while it is operating in the process.
Note: when using a Pt100 simulator, make sure the TxRail Pt100 excitation current
(0.18 mA) s compatible with the simulator specification.
The input types are listed in Table 1, along with the maximum and minimum ranges
accepted by each one. The TxConfig software will allow only configurations that are
consistent with the data in this table.
Please note that the specified accuracy is referenced to the maximum span of each
input type. For instance, for the Pt100 input, the 0. % accuracy results in 1.7 ºC
total accuracy [(650 – (- 00)) x 0. ].
M I C R O P R O C E S S O R
B A S E D T E M P E R A T U R E T R A N S M I T T E R
T x R a i l 4 - 2 0 m A
I N S T A L L A T I O N A N D O P E R A T I N G M A N U A L
WARRANTY
NOVUS Electronics provides the original purchaser of this instrument a one (1) year
warranty against defects in material and workmanship under the following terms:
•
The one year warranty begins on the day of shipment as stated on the sales bill.
•
During the warranty period all costs of material and labor will be free of charge
provided that the instrument does not show any evidence of misuse.
•
For maintenance, return the instrument with a copy of the sales bill to our
factory. All transportation and insurance costs should be covered by the owner
of the equipment.
•
Should any sign of electrical or mechanical shock, abuse, bad handling or
misuse be evident the warranty voids and maintenance costs will be charged.
MAN 500149 A V1. x
- -
PRESENTATION
The TxRail is a -wire DIN rail mount temperature transmitter. Microprocessor
based, it was designed for flexibility, accepting mV, Pt100 and a variety of
thermocouples as the input sensor. The TxRail delivers a scalable linear 4- 0mA
output current proportional to the sensor temperature. A user-friendly configuration
software is provided for parameter setup, including sensor type, temperature range,
filter, etc.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in table 01, along
with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N and E, to IEC 60584 (ITS-90).
Impedance >> 1 M
Ω
Pt100: Excitation: 0.18 mA., or 3-wire connection (for -wire
sensors, tie terminals and 3 together).
α= 0.00385, according to IEC 60751(ITS-90).
Voltage: 0 a 50 mVdc.
Impedance >> 1 M
Ω
Sensor Type Range Minimum measurement span
Thermocouple K 0 to 1370 °C 100 °C
Thermocouple J 0 to 760 °C 100 °C
Thermocouple R 0 to 1760 °C 400 °C
Thermocouple S 0 to 1760 °C 400 °C
Thermocouple T 0 to 400 °C 100 °C
Thermocouple N 0 to 1300 °C 100 °C
Thermocouple E 0 to 7 0 °C 100 °C
Pt100 - 00 to 530 °C 40 °C
Voltage 0 to 50 mV 5 mV
Table 1 – TxRail input sensors
Output: -wire 4- 0 mA, linear with respect to the measured temperature.
Total accuracy: better than 0,3 % of the maximum range for thermocouples and
0, % for Pt100 and voltage;
Resolution: 0,004 mA (1 bits).
Response Time: < 100 ms;
Power supply: 18 to 30 Vdc, across the transmitter;
Maximum load (RL): RL (max.)= (Vcc – 1 ) / 0,0 [
Ω
]
where: Vcc= Power supply voltage
Operating Temperature: -40 to 85 °C
Humidity: 0 a 90 % RH
Electromagnetic compatibility: EN 50081- , EN 5008 -
No isolation between the sensor and the 4-20 mA loop.
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Housing: ABS plastic. Dimensions: Refer to figure 4.
CONFIGURATION
Please check the configuration parameters programmed in theTxRail, using the
TxConfig software. A communication path needs to be established between the
TxRail and the serial port of a PC. The 1.5 m long TxConfig Interface is provided
for this purpose. Connect its DB9 end to the PC COMM port and the other end to
the transmitter as shown in Figure 1.
TxConfig interface has a buit-in electronic circuit to convert
voltage levels of the PC RS232 to acceptable levels. Never use
a different interface or cable to connect the product to the
RS232 port, or the device will be damaged. This damage is not
covered by product warranty.
Once configured, the transmitter is ready to be installed in the process.
Note: The TxConfig Interface and Software can be purchased separately from
Novus or one of its distributors. The latest release of this software can be
downloaded from our website www.novusautomation.com. Do not save the
TxConfig software into a file which contains accent marks. To install, run the
Tx_setup.exe and follow the instructions. To install de configurator, run the
Tx_setup.exe file.
Serial port configuration errors may occur when other devices are sharing the same
port (ex.: Palm Hot Synch). Close all serial port applications prior to using the
TxConfig software.
Transmitter
6
5
4
TxConfig Adaptor
Battery 9V
to PC serial port
1
6
5
3
4
Figure 1 – Adaptor connections to the TxRail
The transmitter requires to be powered during the configuration. Depending on the
PC used, the power can be supplied by the serial port. To assure proper
communication, it is recommended to apply external power to the TxRail. The
TxConfig interface provides a 9 Vdc battery socket for powering the transmitter
during the configuration.
Do not use the battery if the transmitter is being powered by another supply or
connected to the process, as in Figure .
powered current loop
Transmitter
6
5
4
TxConfig Interface
1 3
4
to PC serial port
Figure – TxRail-TxConfig Adaptor wiring (loop powered). Terminal 5 is left opened.
The TxConfig screen in shown in Figure 3. All user parameters can the seen and/or
modified by either typing a value or selecting among the available options. The help
menu provides further information about the software and the transmitter.
Figure 3 –TxConfig main screen
The fields in the screen mean:
1. Input Sensor: Choose the desired temperature sensor among the available
options.
. Measuring range: Defines the beginning and the end of the range.
Lower Range Value: sets the value of the input signal (temperature or mV)
associated to the 4 mA output.
Upper Range Value: sets the value of the input signal that will correspond to the
0 mA output
The values configured in these fields can not be beyond the sensor measuring
range. The minimum span value has to be observed as well (see Table 1).
3. Line Noise Rejection: The TxRail incorporates a digital filter to cancel the
induced noise from the 50 or 60 Hz systems. For better performance, select the
line frequency used in your country.
4. Sensor Failure Detection: establishes the transmitter output behavior (upscale
or down-scale) in the presence of a sensor fail.
5. ero Correction: Allows for small sensor corrections.
6. Read Configuration: Brings to the screen the current TxRail parameters
configuration.
7. Apply: Sends a new configuration to the transmitter.
8. Device Information:
The Device Information box contains relevant data concerning a particular TxRail
transmitter. Please pass along this information when contacting the technical
assistance department.
Note:
The factory default configuration is (unless otherwise specified or ordered):
Pt100 input, 0 to 100 °C
60 Hz filtering and upscale ( 0 mA) output for sensor fail.

Other Novus Transmitter manuals

Novus TxIsoPack User manual

Novus

Novus TxIsoPack User manual

Novus TxRail-USB User manual

Novus

Novus TxRail-USB User manual

Novus TXMINI-M12-485 User manual

Novus

Novus TXMINI-M12-485 User manual

Novus NP785 User manual

Novus

Novus NP785 User manual

Novus TXRAIL Series User manual

Novus

Novus TXRAIL Series User manual

Novus NVPT-131VTP-HD User manual

Novus

Novus NVPT-131VTP-HD User manual

Novus TXMINI-M12 User manual

Novus

Novus TXMINI-M12 User manual

Novus TxMiniBlock User manual

Novus

Novus TxMiniBlock User manual

Novus TxRail User manual

Novus

Novus TxRail User manual

Novus RHT-Air User manual

Novus

Novus RHT-Air User manual

Novus TxIsoRail-HRT User manual

Novus

Novus TxIsoRail-HRT User manual

Novus RHT-XS User manual

Novus

Novus RHT-XS User manual

Novus NP785 User manual

Novus

Novus NP785 User manual

Novus NP620 User manual

Novus

Novus NP620 User manual

Novus NP-430D User manual

Novus

Novus NP-430D User manual

Novus RHT-WM User manual

Novus

Novus RHT-WM User manual

Novus NP400 User manual

Novus

Novus NP400 User manual

Novus TxIsoBlock-HRT User manual

Novus

Novus TxIsoBlock-HRT User manual

Novus TL400-V User manual

Novus

Novus TL400-V User manual

Novus RHT-WM-485-LCD User manual

Novus

Novus RHT-WM-485-LCD User manual

Novus TxBlock-USB User manual

Novus

Novus TxBlock-USB User manual

Novus NP600 User manual

Novus

Novus NP600 User manual

Novus TxIsoRail-HRT User manual

Novus

Novus TxIsoRail-HRT User manual

Novus TXMINI-M12 User manual

Novus

Novus TXMINI-M12 User manual

Popular Transmitter manuals by other brands

Samson AirLine SYNTH owner's manual

Samson

Samson AirLine SYNTH owner's manual

HumanTechnik Mini Lisa operating instructions

HumanTechnik

HumanTechnik Mini Lisa operating instructions

BriarTek ORCA TX-104 user guide

BriarTek

BriarTek ORCA TX-104 user guide

Woxcon TPHD463 user manual

Woxcon

Woxcon TPHD463 user manual

Technaxx FMT1350BT user manual

Technaxx

Technaxx FMT1350BT user manual

Cardin Elettronica TXQPRO486 quick start guide

Cardin Elettronica

Cardin Elettronica TXQPRO486 quick start guide

DMP Electronics 1102 installation guide

DMP Electronics

DMP Electronics 1102 installation guide

Emerson Rosemount 2051 Wireless Series Reference manual

Emerson

Emerson Rosemount 2051 Wireless Series Reference manual

FAAC TM XT1 MINI operating instructions

FAAC

FAAC TM XT1 MINI operating instructions

MG M6NWVS instruction manual

MG

MG M6NWVS instruction manual

Abus FUAT50000 manual

Abus

Abus FUAT50000 manual

Absolute Process Instruments DuoPak APD 2015 instructions

Absolute Process Instruments

Absolute Process Instruments DuoPak APD 2015 instructions

Magnetrol Jupiter JM4 Installation and operating manual

Magnetrol

Magnetrol Jupiter JM4 Installation and operating manual

SICK PHT operating instructions

SICK

SICK PHT operating instructions

Sennheiser SZI 1015-T Instructions for use

Sennheiser

Sennheiser SZI 1015-T Instructions for use

Lectronics UH400TM instruction manual

Lectronics

Lectronics UH400TM instruction manual

R.V.R. Electronica AUD2MP1 user manual

R.V.R. Electronica

R.V.R. Electronica AUD2MP1 user manual

Hampshire Controls TT Series operating instructions

Hampshire Controls

Hampshire Controls TT Series operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.