manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. RAB
  6. •
  7. Lighting Equipment
  8. •
  9. RAB EM-2H2RNY User manual

RAB EM-2H2RNY User manual

EM-2H2RNY NY EMERGENCY LIGHT
EM-2H2RNY
MI PORTANT
CAREFULLY BEFORE INSTALLING FIXTURE. R TAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.READ E
IMPORTANT SAFEGUARDS:
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
• Do not use outdoors.
• Do not let power supply cords touch hot surfaces.
• Do not mount near gas or electric heaters.
• Equipment should be mounted securely in locations and at heights where it will not be readily subjected to tampering by
unauthorized personnel.
• The use of accessory equipment and replacement parts not recommended by the manufacturer may cause an unsafe condition.
• Do not use this equipment for other than its intended purpose.
• The AC voltage rating of this equipment is specified on the product label. Do not connect equipment to any other voltage.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
INSTALLATION
1. Remove the front cover.
2. Mount the equipment securely in place on the wall. Two additional
Key Hole mounting holes are located at the top of the unit housing
in addition to the J-Box mounting holes. These 2 additional
mounting slot holes must be used when the unit is mounted to the
wall. Additional chain suppor t may be required by local codes.
Chain hook holes are provided at each end of the enclosure.
3. Extend 24 hr AC supply of rated voltage to the equipment, which is
furnished with a dual voltage (120/277V) field selectable input.
Connect unit to utility power using an approved connector. For 120V
supply connect the line wire to the Black lead and for 277V supply
connect the line wire to the Red lead. Connect neutral wire to the
White lead. The Ground wire (green lead) needs to be connected in
accordance with the local codes. DO NOT energize the circuit at this
time. CAUTION: Insulate the unused Black or Red wire. Failure to do so
may cause an unsafe condition.
4. If remote fixtures are to be connected to the equipment extend the
remote circuit in accordance with Ar ticle 700 and 720 of the National
Electric Code (NEC) and connect to the yellow and violet leads coming
out of the unit. CAUTION: The minimum wire size required by the NEC
is 12 gauge Copper or equivalent. Your installation may require larger
sized wire to ensure that the voltage drop DOES NOT exceed 5%. Do
not exceed the total output rating of the equipment including any
additional mounted heads.
5. Install and connect the battery.
6. Energize the unit with AC supply. The charge indicator will illuminate.
7. Replace the unit cover.
8. Adjust and focus the lighting heads as required.
OPERATION
1. To test the equipment, depress the TEST switch. The charge (LED)
indicator will turn OFF and the emergency lights will illuminate.
2. Once you release the TEST switch the emergency lights will turn OFF
and the charge (LED) indicator will illuminate.
3. The automatic charger will retur n into action, charging the battery
and trying to maintain it in a fully charged state.
NOTE: Allow the battery to charge for a minimum of 24 hrs after
installation or after a power failure before conducting a 90-minute test
(see TESTING section).
CAUTION: This equipment is furnished with a sophisticated solid state
transfer switch which will automatically disconnect the emergency
lights from the batter y if the batter y has been discharged to the end
of its useful output.
WARNING: Unused wires must be capped using enclosed wire nuts.
EM-2H2RNY NY EMERGENCY LIGHT
TESTING
Easy Answers
EM-2H2RNY-IN-0123
Cranbury, New Jersey 08512 USA
TROUBLESHOOTING
2023
1. The emergency lights DO NOT operate and
a. If the charge indicator light if OFF
- Check that the circuit breaker for AC supply is ON.
B. If the charge indicator light is ON
- Check that the batter y is proper ly connected.
- If remote lamps are connected to the equipment, then turn OFF
the AC supply and disconnect the remote circuit wires from the
equipment. Turn ON the AC supply and depress the test switch.
If the local lamps (mounted on the equipment itself) come ON,
then check the remote circuit for short or over load condition
and correct as required. Reconnect the circuit wires and restore
AC power.
- If the local lamps don’t turn ON after disconnecting the remote
circuit wires, then replace battery.
2. Emergency lights are dim- Implies battery might not be fully charged.
Allow batter y to recharge for 24 hours and then re-test.
3. Remote lights are dim -Remote wire size is too small causing
excessive voltage drop (more than the permitted 5%) and thus causing
the lamps to illuminate with less intensity. Refer to STEP 4 of
INSTALLATION section for more information.
Paragraph 31-1.3.7 of NFPA 101-1985, Life Safety Code requires that all
emergency lighting equipment be functionally tested every 30 days
for a minimum of 30 seconds and tested annually for full 90-minute
duration. Written records of the testing are to be kept for examination
by the authority having jurisdiction.
NOTE: Please contact factory for help with other types of issues.
WARNING:
UNUSED WIRES MUST BE CAPPED USING ENCLOSED WIRE NUTS.
NOTE: 4 TOTAL LED LAMP HEADS MAX. (INCLUDING REMOTE HEADS)
VIOLET(-)
YELLOW(+)
VIOLET(-)
YELLOW(+)
VIOLET(-)
YELLOW(+)
To Remote
CHARGER
BOARD
TRANSFORMER
RED
BLACK
WHITE
277 VAC
120 VAC
COMM
RED(+)
BLACK(-)
9.6V
AA900mAh
BATTERY
AC ON TEST
SWITCH
LED
LAMP
HEAD
LED
LAMP
HEAD
LED
LAMP
HEAD
LED
LAMP
HEAD
KCALB
KCALB
MAINTENANCE
CAUTION: Always turn OFF AC power to the equipment before
servicing. Ser vicing should be performed only by a qualified service
technician. Only manufacturer SUPPLIED or APPROVED replacement
parts must be used.
1. BATTERY: The battery supplied with this unit requires ZERO
maintenance. However it should be tested periodically (see TESTING
section) and replaced when it no longer operates the connected
fixtures for the complete duration of a 30-second or 90-minute test.
It has a life expectancy of 5-7 yrs when used in a normal ambient
temperature of 72°F.
2. OTHER: Clean lenses and replace lamps as and when required.
WIRING DIAGRAMS

Other RAB Lighting Equipment manuals

RAB STEALTH 360 User manual

RAB

RAB STEALTH 360 User manual

RAB GUS- 2FT User manual

RAB

RAB GUS- 2FT User manual

RAB EXIT34-RG User manual

RAB

RAB EXIT34-RG User manual

RAB T8 User manual

RAB

RAB T8 User manual

RAB FXLED User manual

RAB

RAB FXLED User manual

RAB HAZL34-40 User manual

RAB

RAB HAZL34-40 User manual

RAB STRINGER34 User manual

RAB

RAB STRINGER34 User manual

RAB Lightcloud Controller Mini User manual

RAB

RAB Lightcloud Controller Mini User manual

RAB GOTCHA PLUS GT500 User manual

RAB

RAB GOTCHA PLUS GT500 User manual

RAB PLC-9-V-8XX-BYP User manual

RAB

RAB PLC-9-V-8XX-BYP User manual

RAB PLL-14-8 DIR Series User manual

RAB

RAB PLL-14-8 DIR Series User manual

RAB SWISHFA -2X2 User manual

RAB

RAB SWISHFA -2X2 User manual

RAB STRING-50 User manual

RAB

RAB STRING-50 User manual

RAB ECOMBO34 User manual

RAB

RAB ECOMBO34 User manual

RAB STL200H/L User manual

RAB

RAB STL200H/L User manual

RAB TOMO- 2FT User manual

RAB

RAB TOMO- 2FT User manual

RAB X17 XFU 60W User manual

RAB

RAB X17 XFU 60W User manual

RAB STL360HB/L User manual

RAB

RAB STL360HB/L User manual

RAB SHARK - 8FT User manual

RAB

RAB SHARK - 8FT User manual

RAB LESLIE User manual

RAB

RAB LESLIE User manual

RAB FIELD-ADJUSTABLE TOMO-2 User manual

RAB

RAB FIELD-ADJUSTABLE TOMO-2 User manual

RAB EZPAN HE 1X4 User manual

RAB

RAB EZPAN HE 1X4 User manual

RAB GT500R/L User manual

RAB

RAB GT500R/L User manual

RAB STL110H/L User manual

RAB

RAB STL110H/L User manual

Popular Lighting Equipment manuals by other brands

SPI LIGHTING Lightruss LED Installation

SPI LIGHTING

SPI LIGHTING Lightruss LED Installation

VISICO VISICO2 user manual

VISICO

VISICO VISICO2 user manual

SWIT CL-M100C Mini user manual

SWIT

SWIT CL-M100C Mini user manual

Glamox A51-R G2 user manual

Glamox

Glamox A51-R G2 user manual

Beghelli SR instructions

Beghelli

Beghelli SR instructions

Ibiza MHSPOT30-FX manual

Ibiza

Ibiza MHSPOT30-FX manual

BEARWARE 304751 manual

BEARWARE

BEARWARE 304751 manual

Equinox Systems Nimbus user manual

Equinox Systems

Equinox Systems Nimbus user manual

Lightolier MBS2GHP1FT Specification sheet

Lightolier

Lightolier MBS2GHP1FT Specification sheet

Whitegoods P150L-LED installation instructions

Whitegoods

Whitegoods P150L-LED installation instructions

LIGMAN LIGHTALK 19 installation manual

LIGMAN

LIGMAN LIGHTALK 19 installation manual

Kuryakyn 8621 instructions

Kuryakyn

Kuryakyn 8621 instructions

Lampo Fari Solar LED Series instruction sheet

Lampo

Lampo Fari Solar LED Series instruction sheet

Champlain ACM-122 quick start guide

Champlain

Champlain ACM-122 quick start guide

Prilux Niza quick start guide

Prilux

Prilux Niza quick start guide

Hedler MaxiSoft 50x50 max. 2000 W quick start guide

Hedler

Hedler MaxiSoft 50x50 max. 2000 W quick start guide

Outwell LEONIS LUX instruction manual

Outwell

Outwell LEONIS LUX instruction manual

Ledj STRATOS SPOT user manual

Ledj

Ledj STRATOS SPOT user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.