2.
Technical Data (1):
K Factor
Thread
Size
Temperature
Rating Maximum
Ambient
Temperature
Sprinkler
Identifica-
tion
Number
(SIN)
US Met-
ric Sprinkler SWC
Cover
56 80
1/2”
NPT
R1/2
155°F
(68°C)
135°F
(57°C)
100°F
(38°C)
RA1564
175°F
(79°C)
165°F
(74°C)
150°F
(66°C)
200°F
(93°C)
165°F
(74°C)
150°F
(66°C)
(1) Minimum spacing of 14 feet (4,3m).
Coverage Area
Maximum Coverage
Area Width x Length
ft x ft (m x m)
Flow Rate
gpm (L/min)
Pressure
psi (bar)
28 x 8 (8,5 x 2,4) 23 (87,1) 16.9 (1,2)
28 x 10 (8,5 x 3) 28 (106) 25 (1,7)
Approval Type:
• Quick Response, Extended Coverage.
• Approved for installation in accordance with NFPA 13
for light hazard occupancies.
Maintenance
Model DH56 should be inspected and the sprinkler main-
tained in accordance with NFPA 25. Do not clean sprinklers
with soap and water, ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming. Re-
move any sprinkler/cover assembly, which has been painted
(other than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to instal-
lation, sprinklers should be maintained in their original cartons
and packaging until used to minimize the potential for dam-
age to sprinklers that would cause improper operation or non-
operation.
Installation
DH56 Recessed, FP Escutcheon
To install the DH56 with the FP Escutcheon as a re-
cessed sprinkler cut a 2 5/8” diameter hole in the wall as
shown in Figure1. Remove temporarily the plastic protec-
tive cap, then use the GFR2 wrench to tighten the sprin-
kler until secured in the sprinkler fitting. NOTE: The GFR2
wrench has a notch in it to accommodate the deflector
top. This wrench can only be inserted one way. Care must
be taken not to damage the deflector during tightening.
Apply a PTFE based sealant to the sprinkler threads be-
fore installing in the fitting. When inserting or removing the
wrench from the sprinkler cup, care must be taken to pre-
vent damage to the sprinkler. Wrench only on the square
boss. DO NOT WRENCH ON ANY OTHER PART OF THE
SPRINKLER. It is recommended that the sprinkler be pro-
tected during plastering and painting operations by rein-
stalling the protective cap P/N 6802710003. Installation is
completed by removing the protective cap and inserting
the push-on escutcheon. Turn clockwise to adjust the es-
cutcheon against the wall.
DH56 Recessed, F2 Escutcheon
To install the DH56 with the F2 Escutcheon as a re-
cessed sprinkler cut a 2 ¼” diameter hole in the wall as
shown in Figure 2. Thread the DH80 into the collar hand
tight. Apply a PTFE based sealant to the sprinkler threads
and install in the fitting. Wrench only on the square boss.
NOTE: The GFR2 wrench has a notch in it to accommo-
date the deflector top. This wrench can only be inserted
one way. When inserting or removing the wrench from the
sprinkler cup care must be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER. It is recommended that the sprinkler
be protected during plastering and painting operations by
using the protective cap P/N 6999991009. These must be
ordered separately. Installation is completed by removing
the protective cap and inserting the F2 Escutcheon over
the collar.
DH56 with SWC Cover Plate Concealed
To install the sprinkler, cut a 2 5/8” diameter hole into the
wall as shown in Figure1. A PTFE based thread sealant
should be applied to the sprinkler threads only. Remove
the protective cap (P/N 6802710003) and then position
the GFR2 wrench into the sprinkler/cup assembly until
the wrench engages the flats of the square boss. Then
tighten the sprinkler into the pipe fitting. When inserting
or removing the wrench from the sprinkler/cup assembly,
care should be taken to prevent damage to the sprin-
kler. DO NOT WRENCH ON ANY OTHER PART OF THE
SPRINKLER. The protective caps should be reinstalled for
protection during plastering and painting. Remove caps
only when covers are being installed. The cover assembly
is then pushed onto the cup. Cover assemblies provide
½” (13mm) of adjustment. Final adjustment is made by
turning the cover clockwise until the skirt flange makes
full contact with the wall surface. Cover removal requires
turning in the counter- clockwise direction.
Concealed cover/cup assemblies are listed only for use
with specific sprinklers. The use of any other concealed
cover/cup assembly with the Model DH56 Horizontal Side-
wall Sprinkler or the use of the concealed cover assembly
on any sprinkler with which it is not specifically listed will
void all guarantees, warranties, listings and approvals.
Note: DH56 and DH56 Recessed Sprinklers have orange
bulb protectors to minimize bulb damage during shipping,
handling, and installation. REMOVE THIS PROTECTION
AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN
SERVICE FOR FIRE PROTECTION. Removal of the protec-
tors before this time may leave the bulb vulnerable to dam-
age. RASCO wrenches are designed to install sprinklers
when covers are in place. REMOVE PROTECTORS BY
UNDOING THE CLASP BY HAND. DO NOT USE TOOLS