manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Rielta
  6. •
  7. Security Sensor
  8. •
  9. Rielta FOTON-16B User manual

Rielta FOTON-16B User manual

1 General Information
1.1 Passive infrared infrared vertical curtain detector «Foton-16B»
(hereinafter, the Detector) is designed for detecting intrusion into a
protected space and generating an alarm message.
1.2 Ambient class: Boreal climate.
1.3 The Detector is designed to operate continuously around the
clock.
1.4 The Detector does not produce any interferences to other
detectors of the same or other type and designation, as well as to any
domestic radio equipment.
2 Features
- Active infrared channel with antimasking function.
- Possibility of saving of the Detection channel masking parameters
into nonvolatile memory.
- Two-color LED indication with a possibility of it’s disabling.
- Self-testing mode.
- Immunity to insect’s intrusion to the pyrodetector.
- Swivel bracket (supplied) providing ease of the Detector installation
and detection zone repositioning.
3 Specifications
Parameter Value
Detection range, maximum 15 m
Maximum antimasking detection range, not less than 0.1 m
Power supply 9 …15 V DC
Consumption current, not more than 35 mA
Alarm message duration, not less than 4 sec
Operation temperature minus 30 ... +55 °С
Relative humidity under +25 °С without moisture
condensation, up to 98 %
IP rating IP41
Dimensions, maximum 126 х 70 х 55 mm
Mass, maximum 150 g
Average service life, not less than 8 years
Detection zone pattern is shown in Figure 1.
Figure 3 – Terminals for hookup wire connection
Connection of the Detector to the control panel (CP) should be
fulfilled in accordance with CH Installation Guide.
7 The Detector Adjustment
The Detector adjustment should be realized by changing position
of «1», «2», «3», «4» and «5» DIP-switches, located at the top of
PCB. DIP-switch «1» changes sensitivity value, «5» – manages
anti-masking channel operation tactics, «2», «3», «4» supervise only
the LED indication modes.
a) Detector base
b) Swivel Bracket
6
3
5
1
23
4
78910 11
12
Figure 1 – Detection Zone Pattern
4 Scope of delivery
Name QNT
Passive infrared vertical curtain detector «Foton-16B»
Swivel bracket
Screw 3-3х30.016
Passive infrared vertical curtain detector «Foton-16B».
Installation Guide
1 pc.
1 pc.
2 pcs.
1 copy
5 Installing the Detector
Recommended mounting height of the Detector is 2.3 m above the
floor. The shape of the Detector base allows to mount the Detector
on the wall, as well as in the corner of the room. In case of the swivel
bracket usage (supplied), the Detector can be installed on the wall or
ceiling at a hight 2.3 ... 3 m above the floor. Swivel bracket construction
provides detection zone repositioning.
When choosing the Detector installation place, take note of the fact
that the detection zone may be limited by non-transparent objects
(curtains, houseplants, cabinets, bookcases, etc.), as well as glass and
mesh partitions. There must be no windows, air conditioners, space
heaters or heating radiators in the Detector visibility range.
The Detector installation:
5.1 Unfasten the latch through the opening (5), which is situated
downside the detector case by means of screwdriver and put off the
detector cover.
5.2 Put off the PCB by means of pushing up it’s fixing arm (4) on
the base.
5.3 Drill the holes (1) for wiring and fastening the Detector:
- for wall mounting – holes (6);
- for corner mounting – holes (3).
5.4 Pass the wire through the mounting holes (1) and fasten the
base on the wall (corner) by screws.
5.5 If swivel braket is used for installation:
- open hole (2);
- insert a nut (8) to the sphere bulge (9);
- insert a sphere (9) and then a bush (7) to the base of the swivel
bracket (11).
Fasten an assembled swivel bracket on the wall (ceiling) by screws.
Pass the wires and tighten the base on the swivel bracket by the screw
(12). Fix position of the sphere when tightening the screw (12).
5.6 Put PCB on it’s place.
Figure 2 – Detectoir Base and Swivel Bracket
Note – Places for mounting holes on the installation surface can
be marked using a detector base with opened holes as a pattern.
6 The Detector Hooking up
Marked terminals for the Detector hooking up are located at the top
of the PCB (See Figure 3).
DIP-switch Position
ON OFF
«1» Sensitivity Norm High
«2» TEST Alarm LED
Indication
Indication of
detection
«3» LED indication ON OFF
«4» Alarm memory ON OFF
«5» MASK See Cl. 8.7
MASK
MEM
IND
TEST
SENS
+12V-
ALFAILURE TAMPER
Table 2
PASSIVE INFRARED
VERTICAL CURTAIN
DETECTOR
«FOTON-16B»
WITH ANTIMASKING
FUNCTION
Installation Guide
b) Top
View
a) Side
View
15 m
15 m
1 m 2.3 m
5 m
8.7 Masking Detection
The Detector provides anti-masking function. «Masking» message is
displayed by the LED indicator intermittent blinking green. If masking
attributes remain constant, «Masking» message is generated by «AL»
and «FAILURE» contacts opening. Masking message is generated
not earlier than after three minutes upon the expiry of warmup time.
Depending on switch «5» position, anti-masking function is realised
by two modes:
a) upon setting DIP-switch «5» to «OFF» position after every switching
on the Detector stores current circumstances as an basic reference
standard;
b) upon setting DIP-switch «5» to «ON» position the Detector refers
to once-stored current circumstances as an basic reference standard.
Reference environment storage is fulfilled immediately after setting
switch «5» to ON position. If the switch «5» is set to ON position while
the Detector is in »Warm-up time» state with power off, then storage of
reference environment is executed upon the expiry of »warm-up time».
8.8 Detection of repositioning
The Detector controls changing of its tilt relatively to initial position
for more than (5.5 ± 0.5)°. Storage of initial position is executed upon
the expiry of «warm-up time».
9 Storage and Transportation
9.1 The Detector in original package without power supply batteries
is resistant to:
а) transport jolting with the acceleration of 30 m/sec2with impact
frequency rate from 10 to 120 impacts/sec or 15000 impacts with the
same acceleration;
b) the ambient temperature from minus 50 … +50 °С;
c) relative air humidity (95 ± 3) % at the ambient temperature +35 °С.
9.2 The Detectors in original package may be transported by any
transport facility in closed vehicles over any distances in compliance with
the existing shipping rules concerning the respective means of transport.
9.3 After transportation under the conditions different to exploitation
conditions, the Detector shall be ready to operate after a maximum of
six hours.
10 Manufacturer’s Guarantees
The Manufacturer guarantees conformity of the Detector to it’s
Technical Specifications if conditions of transportation, storage,
assembling and operation are observed. The guaranteed storage
period is 63 months since the date of manufacturing the Detector.
The guaranteed period of operation is 60 months since the date of
commissioning within the storage period guaranteed.
The Detectors that are found to non-conforming to it’s Technical
Requirements shall be repaired by the Manufacturer, provided the
installation and operation rules have been complied with.
11 Packing Certificate
Passive infrared vertical curtain detector «Foton-16B» has been
manufactured in compliance with the active technical documentation
and classified as fit for operation and packed by «RIELTA» JSC.
Packing date _______________________________
month, year
The Detector generates the following messages:
Table 3
Message Contacts state LED
Indication
Indication
Duration
AL TAMPER FAILURE
«Warm-Up
Time» Opened Opened Opened Red 1 Hz Up to 60
sec
«Norm» Closed Closed Closed OFF
«Alarm» Opened Closed Closed Red
Not less
than 2s
«Case
tampering» Closed Opened Closed
OFF
Up to cause
removal
«Masking» Closed Opened Closed Blinking
green
Up to cause
removal
«Repositioning
or wall
tampering»
Closed Opened Closed
Blinking
green
Up to cause
removal
«Total lack of
power supply» Opened Opened Opened OFF Up to cause
removal
«Voltage drop» Closed Closed Opened Green/
Red
15
minutes1)
«Rise of
ambient
temperature»
Closed Closed Opened Green/
Red
15
minutes1)
«Self-testing
procedure fail» Closed Closed Opened Green/
Red
15
minutes1)
1) «Alarm memory»indication is switched ON with 5 minutes delay and is
lighting during 15 minutes.
8 Switching ON and Testing
8.1 During one minute after energizing the Detector with closed
cover or after closing cover of already energized detector, the Detector
operates in «Warm-up time» mode, after what it changes to standby
mode and is ready to generate «Alarm» message.
8.2 «Alarm» message is generated by opening «AL» contacts for
4 sec after intrusion into detection zone.
8.3 During first seven minutes operation in standby mode the
Detector displays crossing of every sensitivity zone by shot-term blink
(0.25 sec) of red LED indicator. This indication mode allows to check
and adjust detection zone position. If «2» DIP-switch is set to «ON»
position, LED indicator displays an «Alarm» message generation by
lighting red during 4 sec.
8.4 After seven minutes operation in standby mode LED indicator
displays an «Alarm» message generation by lighting red during 4 sec.
To provide masking of the Detector operation, «Alarm» LED indication
can be disabled by setting «3» switch to «OFF» position.
8.5 DIP-switch «1» changes the Detector sensitivity from normal
(«ON» position) to high («OFF» position). Detection range data in
Cl. 3 are reported for the Detector normal sensitivity state.
8.6 Self-Testing
During process of its operation the Detector is monitoring power
supply and ambient temperature values. Also it performs periodical
procedure of detection channel self-testing. In case when ambient
temperature reaches the value close to 36 °С, the Detector sensitivity
level increases automatically.
If power supply reaches the value (62.5 ± 2.5) °С or if self-testing
procedure fails, the Detector generates relevant message by opening
FAILURE contacts. This message is in progress during 15 minutes
after removal of its cause, it is followed by LED indicator alternate
lighting green and red.
«RIELTA» JSC, www.rielta.com,
Chapaeva Str. 17, Saint Petersburg, Russia, 197101, [email protected],
Tel./fax. +7 (812) 233-0302, 703-1360,
Technical support, tel. +7 (812) 233-29-53, 703-13-57, [email protected].
Rev. 3 оf 03.09.19
v.6.1

Other Rielta Security Sensor manuals

Rielta PYRONE-SH2-RK User manual

Rielta

Rielta PYRONE-SH2-RK User manual

Rielta STZ-RK User manual

Rielta

Rielta STZ-RK User manual

Rielta PYRONE-SH User manual

Rielta

Rielta PYRONE-SH User manual

Rielta FOTON-21 User manual

Rielta

Rielta FOTON-21 User manual

Rielta PYRONE-4i User manual

Rielta

Rielta PYRONE-4i User manual

Rielta CELSIUS-RK User manual

Rielta

Rielta CELSIUS-RK User manual

Rielta Ladoga MK-RK User manual

Rielta

Rielta Ladoga MK-RK User manual

Rielta PYRONE-8-RK User manual

Rielta

Rielta PYRONE-8-RK User manual

Rielta PYRONE-5 User manual

Rielta

Rielta PYRONE-5 User manual

Rielta Ladoga MK-RK User manual

Rielta

Rielta Ladoga MK-RK User manual

Rielta ORLAN-2 User manual

Rielta

Rielta ORLAN-2 User manual

Rielta FOTON-SH2-RK User manual

Rielta

Rielta FOTON-SH2-RK User manual

Rielta FOTON-10M User manual

Rielta

Rielta FOTON-10M User manual

Rielta Pyrone-4D User manual

Rielta

Rielta Pyrone-4D User manual

Rielta GRAN-RK User manual

Rielta

Rielta GRAN-RK User manual

Rielta UDAR User manual

Rielta

Rielta UDAR User manual

Rielta Pyrone-7 User manual

Rielta

Rielta Pyrone-7 User manual

Rielta ZVON-1 User manual

Rielta

Rielta ZVON-1 User manual

Rielta Pyrone-7i User manual

Rielta

Rielta Pyrone-7i User manual

Rielta FOTON-SH2 User manual

Rielta

Rielta FOTON-SH2 User manual

Rielta CELSIUS-RK User manual

Rielta

Rielta CELSIUS-RK User manual

Rielta PYRONE-SH2-RK User manual

Rielta

Rielta PYRONE-SH2-RK User manual

Rielta FOTON-12-RK User manual

Rielta

Rielta FOTON-12-RK User manual

Rielta Ladoga IPR-RK User manual

Rielta

Rielta Ladoga IPR-RK User manual

Popular Security Sensor manuals by other brands

ZKTeco LD01 user manual

ZKTeco

ZKTeco LD01 user manual

PCB Piezotronics 8120G-400A Installation and operating manual

PCB Piezotronics

PCB Piezotronics 8120G-400A Installation and operating manual

Heitronic 42207 Installation and operating instruction manual

Heitronic

Heitronic 42207 Installation and operating instruction manual

OHD QuantiCheck quick start guide

OHD

OHD QuantiCheck quick start guide

Bresser 7009994 instruction manual

Bresser

Bresser 7009994 instruction manual

SEA FLIPS PLUS quick start guide

SEA

SEA FLIPS PLUS quick start guide

ensto AVR66 Series Installation and operating instructions

ensto

ensto AVR66 Series Installation and operating instructions

Me MERCURY D-47 user manual

Me

Me MERCURY D-47 user manual

DMP Electronics 1126R installation guide

DMP Electronics

DMP Electronics 1126R installation guide

Balluff BTL7-A/C/E/G5 M HB/WB-KA K Series user guide

Balluff

Balluff BTL7-A/C/E/G5 M HB/WB-KA K Series user guide

AJAX Systems StreetSiren user manual

AJAX Systems

AJAX Systems StreetSiren user manual

ELTEX UPG 16720 instructions

ELTEX

ELTEX UPG 16720 instructions

Cura1 iBeam 2721 quick start guide

Cura1

Cura1 iBeam 2721 quick start guide

GEV LBD 1251 manual

GEV

GEV LBD 1251 manual

Velleman PIR415U user manual

Velleman

Velleman PIR415U user manual

Renkforce 1362919 operating instructions

Renkforce

Renkforce 1362919 operating instructions

SICK KTX-WB9214125A Series manual

SICK

SICK KTX-WB9214125A Series manual

Preiffer adixen ASM 380 operating instructions

Preiffer

Preiffer adixen ASM 380 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.