S&P MDX-ES24VK User manual

MDX-ES24VK-IOM_02.03.2020
6393 Powers Ave
Jacksonville, FL 32217
P: 800.961.7370
F:800.961.7379
MDX-ES24VK
READ AND SAVE THESE INSTRUCTIONS
The purpose of this manual is to aid in the proper installation and operation of fans manufactured
by S&P. These instructions are intended to supplement good general practices and are not
intended to cover detailed instruction procedures, because of the wide variety and types of fans
manufactured by S&P.
Installation, Operation and Maintenance Manual


1
WARNINGS
READ AND SAVE THESE INSTRUCTIONS. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN
PERSONAL INJURY AND/OR PROPERTY DAMAGE!
CAUTION:
1. For General Ventilating Use Only. Do Not Use To Exhaust Hazardous Or Explosive Materials And Vapors
2. The MDX-ES24VK is suitable for operation within indoor environments only.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety
standards such as those published by the National Fire Protection Association (NFPA), and the American
Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
PREINSTALLATION INSPECTION
The MDX-ES24VK has been manufactured in accordance with rigorous standards of production. All the components
have been checked and tested at the end of the manufacturing process. We recommend that you check the following
after receiving this product:
1. The correct size has been received.
2. The correct model has been received.
3. The details on the rating label correspond to the electrical supply: voltage, frequency etc.
Remove the unit from packaging and inspect for shipping damage within 5 days of receipt. If the product is found to be
damaged, immediately contact your local authorized supplier. DO NOT OPERATE THE UNIT IF DAMAGED. These
instructions should be considered as a supplement to EPA standard practices, as well as all state and local building
code regulations.
Before installing the product check the following points:
1. The damper blade opens and closes freely.
2. There are no obstructions to the airflow.
ENVIRONMENT
The MDX-ES24VK is suitable for operation within indoor environments only. The MDX-ES24VK is suitable for the
supply of both conditioned and un-conditioned airstreams within the temperature ranges (inclusive of duct airstream’s
temperature) of -40°C up to +60°C.
MOUNTING
Choose a mounting location which allows convenient wiring and maintenance accessibility. The MDX-ES24VK can
be mounted in any orientation, horizontal or vertical, and is suitable for supply/fresh air applications. The motorized
damper will be installed between the fresh air wall cap/roof cap/soffit vent (with insect screen) and the HVAC unit
return duct. The ES24V fresh air control can be mounted:
• On the insulated ductwork between the wall cap and the motorized damper, or
(Note, the 24V power wires (R & C) will need to be extended from the HVAC unit power supply or a
separate 120V-24V transformer)
• On the HVAC unit (Note, the temperature (26AWG cable) and humidity (6P6C phone cable) sensor wires
will need to be extended.)

2
Make sure the temperature and humidity sensors are installed into the insulated fresh air duct between the wall cap
and motorized damper if necessary.

3
DUCTING
All ducting and fresh air intake construction/location must comply with local and national building codes. Do not
locate fresh air intakes near contaminant sources (ex: dryer exhaust vent, garbage, etc). Connect the ductwork to
the wall cap and HVAC return duct with screws, cable ties, worm clamps, and rated tape as necessary. Ensure that
the ductwork is properly connected to a properly sized, low restriction fresh air intake with weather hood and insect
screen.
S&P recommends round insulated rigid ductwork for best air and sound performance. Round
flexible ductwork is acceptable, but ensure that it is pulled tight to reduce losses. Keep the length of
duct and number of elbows to a minimum for best air and sound performance. Insulated ductwork
will minimize building heat loss/gain and reduce the potential for condensation.
The ducting from the HVAC unit fan to the outside of the building has a strong effect on the air flow, noise and energy
use of the fan. Use the shortest, straightest duct routing possible for best performance, and avoid installing smaller ducts
than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth.
Ductwork connections and penetrations should be sealed with duct tape, duct fast-clamps, or caulk (available through
your local distributor) to create an air-tight path from the building exterior to the ventilated space.
WIRING
CAUTION: Ensure that power is turned off and locked out before making any wiring connections.
The MDX-ES24VK operates from a standard 24V 60Hz AC electrical supply. There are multiple
wiring scenarios available depending on the installer preferences. The diagrams below show 3 common scenarios
where the ES24V is connected either directly to the HVAC unit transformer or an auxiliary transformer and the
MD is connected either directly to the ES24V damper terminals or to the ES24V damper
terminals through a SPST, N.O. 24V relay and transformer. This will depend on the VA
available from the HVAC unit transformer. S&P recommends 20VA be available to operate
the motorized damper. If 20VA is not available from the HVAC unit transformer, then an
auxiliary transformer to power the ES24V and motorized damper is recommended (transformers and relays provided
by others).
All wiring must be carried out by a qualified electrician in accordance with National Electrical Code and all applicable
state and local buildings codes. Electrical connections should be made in accordance with the following Figures: 1-3
FIGURE 1
ES24V (20VA REQUIRED TO OPERATE MD6 MOTORIZED DAMPER. CLASS II POWER
SUPPLY CAN COME FROM HVAC TRANSFORMER,
IF ADEQUATE, OR AUXILIARY TRANSFORMER IF NECESSARY)
SENSOR
SENSOR
C
TSTS
R
G
R
C
GG
C
R
FIGURE 2
ES24V (20VA NOT AVAILABLE FOR DIRECT CONNECTION OF
MOTORIZED DAMPER)
COMMON
TRANSFORMER
R
C
G
G
C
R
SENSOR
G
R
TS TS
C
SENSOR

4
AIRFLOW SETTING
CAUTION: Refer to local and national Ventilation and Indoor Air Quality standards to ensure the proper airflow rate.
Ensure the HVAC unit air filter is clean and installed. Turn the ES24V to the “ON” position and wait approximately 10
seconds for the HVAC unit fan to turn on and the motorized damper to open. (Note, ensure that the Motorized Damper
is enabled on the ES24V; refer to ES24V IOM on page 6-7). Using a manometer or anemometer, measure and record
the airflow through the fresh air duct (refer to the measuring device instructions and the airflow/air velocity table on
page 5. Keep in mind, lower velocities are preferred to decrease noise and increase filter effectivity). Once complete,
turn the ES24V to the “OFF” position and calculate the required continuous CFM based on the ventilation code.
ASHRAE 62.2-2010
Required Continuous CFM = ((0.01 * Floor Area in ft²) + 7.5(# of bedrooms + 1))
Example:
2,000 sqaure foot dwelling
3 bedrooms
= 50 CFM continuous
ASHRAE 62.2-2013 & 2016
Required Continuous CFM = ((0.03 * Floor Area in ft²) + 7.5(# of bedrooms + 1))
Example:
2,000 sqaure foot dwelling
3 bedrooms
= 90 CFM continuous
Now that the required continuous CFM is known, calculate the required run time / hour.
Run Time / Hour = 60 * (Required Continuous CFM / Actual Measured CFM)
Example (based on ASHRAE 62.2-2010 example above):
50 Required Continuous CFM
150 Actual Measured CFM
= 20 minutes / hour
Set the ES24V to the correct Run Time / Hour and High / Low Temperature & Humidity limits per the ES24V IOM on
pages 6-7.
FIGURE 3
ES24V (20VA NOT AVAILABLE FOR DIRECT
CONNECTION OF MOTORIZED DAMPER)
SENSOR
C
TSTS
R
G
SENSOR
R
C
GG
C
R
TRANSFORMER
COMMON
Refer to the ES24V – Envirosense Ventilation Control IOM on pages 8-9 for ES24V wiring connections and operation.

5
Airflow / Air Velocity Reference Table
Airflow
(CFM)
Duct Size (in)
4 5 6 8
Air Velocity (FPM)
30 344 220 15 3 86
40 458 293 204 115
50 573 367 255 14 3
60 688 440 306 172
70 802 513 357 201
80 917 587 407 229
90 10 31 660 458 258
100 114 6 733 509 286
11 0 1261 807 560 315
12 0 1375 880 6 11 344
13 0 14 9 0 953 662 372
14 0 1604 1027 713 4 01
15 0 1719 11 0 0 764 430
160 18 33 117 3 815 458
170 194 8 12 4 7 866 487
18 0 2063 132 0 917 516
190 217 7 1393 968 544
200 2292 14 6 7 1019 573
Note, if the Actual Measured CFM is not enough, the installer may need to increase the duct size or add a booster fan if necessary. Ensure there is no blockage
in the ductwork first.
MAINTENANCE
CAUTION: BEFORE CARRYING OUT ANY MAINTENANCE OR SERVICING, ENSURE THE UNIT IS
DISCONNECTED FROM THE MAIN ELECTRICAL SUPPLY.
S&P recommends inspection of the Motorized Damper and ES24V at least once every twelve (12) months. To inspect
the unit disconnect from electrical supply. Remove the motorized damper from the fresh air ductwork and inspect the
damper blade for damage and proper function. If any debris is evident on the damper blade clean with a damp (not
wet) cloth. DO NOT USE any detergents or abrasive materials for cleaning. Reinstall motorized damper to the fresh
air ductwork and reseal joints.
WARRANTY
S&P USA - S&P Canada warrant that the MDX-ES24VK will be free from defective materials and workmanship for
the period of (5) years from the date of original purchase. In the event that we find any part is defective the product
will be repaired or, in the Company’s discretion, replaced without charge provided that the product has been installed
in accordance with the enclosed instructions and all applicable EPA Standards and state and local building codes.
an such as: Improper Maintenance; Misuse; Negligence; Alteration; Abuse; Abnormal Use; or Accident or Incorrect
Electrical Voltage and Current.
Please visit SolerPalau-USA.com/sp-form/claims.html for additional details about warranty procedures.

6
The ES24V controls a ventilator to meet fresh air supply requirements
while limiting operation during periods of extreme temperature and/or
humidity.
INSTALLATION & OPERATION MANUAL
CAUTION:
1. READ AND SAVE THESE INSTRUCTIONS.
2. Before installation or maintenance, disconnect the power supply.
3. This control is for 24 VAC applications only.
4. All wiring must be done by qualified person(s) in accordance with
all applicable codes & standards.
5. Indoor Use Only
WIRING
Use Copper Conductors Only
Terminal Type Description
R
24Vac
Input: 24Vac input (50/60 Hz)
C
24Vac
Input: 24Vac common
G
24Vac
Input: Furnace Blower (Optional)
B
24Vac
Output: Furnace Blower (2A max) (Optional)
F+
24Vac
Output: Fresh Air Fan output + (2A max)
F-
24Vac
Output: Fresh Air Fan output - (2A max)
D+
24Vac
Output: Motorized Damper + (2A max) (Optional)
D-
24Vac
Output: Motorized Damper - (2A max) (Optional)
H+
24Vac
Output: Duct Heater output + (2A max) (Optional)
H-
24Vac
Output: Duct Heater output - (2A max) (Optional)
MOUNTING
Front Cover Removal
Insert a flathead screwdriver into the slot
on the right side of the controller and
apply gentle pressure inward and up so
that the front cover disengages from the
back cover. Pull the front cover up and to
the left.
Back Cover Mounting
Locate the control on the mounting surface being sure to allow clearance
for the necessary wiring connections. Mark the mounting hole locations and
remove the back cover from the work space. Make the stripped/labelled
wiring connections now. CAUTION: Be sure that no exposed portions of
wires are touching.
If installing onto wood, mount the back cover with the provided screws. If
installing onto drywall, drill pilot holes using a 7/32”drill bit (not provided)
and tap the provided drywall anchors into place. Mount with provided
screws. NOTE: Velcro can be used to mount the control instead of screws
if necessary.
Verify that wiring connections are correct and secure.
Align the front cover with the
back cover starting on the left
side. Push the front cover
towards the back cover in a
“hinging” motion from the left to
the right. CAUTION: Make sure
the front cover is aligned properly
with the back cover to avoid
damaging the control. Press
down until the front cover snaps
securely into place.
Sensor Mounting
The ES24V comes with a temperature sensor (26AWG, 2 wire) and
humidity sensor (6P6C, telephone wire), both 10” long. Install the sensors
at a location so that they will be exposed to the fresh air intake (ex: the
fresh air ductwork). Drill 2, 3/4" diameter holes, spaced appropriately and
install the sensors with the provided hardware. NOTE: the sensor wires can
be extended up to 300 feet without deviation. Use appropriate duct tape to
seal joints/openings as necessary.
DIMENSIONS (in)
SCREEN DIAGRAM
OPERATING MODES
OFF Mode: All outputs are off.
ON Mode: The Fresh Air Fan, Motorized Damper (if enabled), and
Furnace Blower (if enabled) are on continuously. The Duct Heater
will follow the user settings (see FUNCTION SETTINGS below).
Eco Mode: Eco Mode limits the Fresh Air Fan operation during
periods of extreme temperature and/or humidity. The Fresh Air
Fan, Motorized Damper (when enabled), Furnace Blower (when
enabled), and Duct Heater (when enabled) will follow the user
settings when the outside air temperature/humidity is within the
user set limits (see FUNCTION SETTINGS below).
The Fresh Air Fan will run for the user set amount of time/hour
while the temperature/humidity limits are within range. The
temperature/humidity sensors evaluate the fresh air conditions
every 10 seconds. While the fresh air temperature/humidity is
within the user set limits, the Fresh Air Fan/accessories will run
per the user settings. When the fresh air temperature/humidity
exceeds the user set limits, the Fresh Air Fan/accessories will turn
off and engage a timer. The timer will run the fan for 5 minutes
every 15 minutes in order to meet code requirements. NOTE: the
Furnace Blower (if enabled) will not run during this check
procedure to prevent cycling. The fan will continue this check
procedure until the temperature/humidity limits are within the user
set limits.
If Enabled (in SETUP):
The Furnace Blower will be on: any time there is a call from “G”
Input or any time the Fresh Air Fan is on (excluding the check
procedure above).
The Motorized Damper will be on anytime the Fresh Air Fan is on.
The Duct Heater will be on any time the Fresh Air Fan is on and
the set point > room temperature +2°F.
(Motorized Damper, Furnace Blower, and Duct Heater are
required to be enabled in SETUP)
BUTTONS
Keys Description
Mode Select the operating mode
Set Confirm settings
▲Increase settings
▼Decrease settings
S&P USA Ventilation Systems, LLC
6393 Powers Ave
Jacksonville, FL 32217
ES24V
Envirosense Ventilation Controller
Operating Modes: OFF, ON, or Eco
Motorized Damper indicator
Relative Humidity %
Temperature (F or C)
Thermostat integration indicator
Fresh Air Fan indicator
Duct Heater indicator

7
SETUP
Press and hold [MODE] for 3 seconds to enter setup mode.
OR
01 Optional Duct Heater (Default: heater disabled)
Press [▲]/[▼] to enable or disable duct heater.
Press [SET] to confirm settings.
OR
02 Temperature Unit (Default: degrees F)
Press [▲]/[▼] to select degrees C or degrees F.
Press [SET] to confirm settings.
OR OR
03 Humidity/Temperature (Default: temperature and humidity)
Press [▲]/[▼] to evaluate temperature only, humidity only or both
temperature and humidity.
Press [SET] to confirm settings.
OR
04 Optional Motorized Damper (Default: motorized damper disabled)
Press [▲]/[▼] to enable or disable motorized damper.
Press [SET] to confirm settings.
OR
05 Optional Thermostat Integration (Default: standalone system)
Press [▲]/[▼] to enable or disable thermostat integration.
Press [SET] to confirm settings.
06 Fan Run Time per Hour (Default: 15 minutes)
Press [▲]/[▼] to adjust 5-60 Minutes/Hour (Increments of 5).
Press [SET] to confirm settings and return to normal mode.
All setting screens will return to the normal mode screen automatically after
20 seconds.
FUNCTION SETTINGS
Press <Set> key to set the temperature/humidity limits and duct heater set
point.
FACTORY RESET
Press and hold [▲]&[▼] buttons in OFF mode for ~5 seconds to
reset the control to factory settings. will be displayed on the
screen when complete.
FEATURES
◆Voltage supply: 24VAC +/- 15% 50/60Hz
◆System mode: Off / On / Eco
◆Temperature unit mode: F or C
◆Temperature measurement range: 15F - 130F (-10C to
55C)
◆High Limit Temperature settings range: 65 -105°F (18C to
40C)
◆Low Limit Temperature settings range: 20 - 60°F ( -6C to
16C)
◆Heater Temperature settings range: 32°F - 62°F (0°C -
16°C)
◆Temperature resolution: 1 °F or 0.5C
◆Temperature Accuracy: +/-1 °F or 0.5C
◆Humidity measurement range: 10-95%
◆High Limit Humidity settings range: 55-90%
◆Low Limit Humidity settings range: 10-50%
◆Humidity resolution: 1 %
◆Humidity Accuracy: +/- 5 %
◆10 inch RJ11 (6 wires) phone cable for humidity sensor
◆10 inch 26AWG (2 wires) cable for temperature sensor
◆Max Sensor Wire Length: 300 feet (100m)
◆Motorized Damper relay output (Maximum 2A)
◆Fan relay output (Maximum 2A)
◆Duct Heater relay output (Maximum 2A)
◆Furnace Blower Output (Maximum 2A)
◆Non-volatile memory to store settings, configuration
parameters
◆Operating temperature: 15F to 130F (-10 C to 55C)
◆Storage temperature: -20F to 158F (-29 C to 70C)
◆Temperature limit of mounting surface: 130F (55C)
◆Terminals: 2.5mm2cable
◆Pollution Degree: 2
◆Degree of protection: IP20
◆Electronic control: Type 2.B
◆Class II Control
◆cULus listed: UL60730-1
◆Housing Material: Lexan 943(f1), 1.6mm thick, V-0 (UL94
Rating)
◆Time Setting Rage: 5-60 Minutes
◆Power: 1.5W (Max)
200103
Press [▲]/[▼] to change the high limit
temperature setting.
Press [SET] to confirm settings.
Press [▲]/[▼] to change the high limit
humidity setting.
Press [SET] to confirm settings.
Press [▲]/[▼] to change the low limit
temperature setting.
Press [SET] to confirm settings.
Press [▲]/[▼] to change the duct heater
activation temperature setting.
Press [SET] to confirm settings and return to
normal mode.
Press [▲]/[▼] to change the low limit
humidity setting.
Press [SET] to confirm settings.

S&P USA Ventilation Systems, LLC
6393 Powers Avenue
Jacksonville, Florida 32217
T. 904-731-4711 F. 904.737.8322
www.solerpalau-usa.com
S&P Canada Ventilation Products, Inc
6710 Maritz Drive Unit #7
Mississauga, ON L5W 0A1- Canada
T. 416-744-1217 F. 416-744-0887
www.solerpalaucanada.com
Table of contents
Other S&P Fan manuals

S&P
S&P KCTR Series User manual

S&P
S&P DECOR-100 VISUAL User manual

S&P
S&P decor-100 DC User manual

S&P
S&P CAB Series User manual

S&P
S&P SILENT-100 DESIGN User manual

S&P
S&P PCD110 User manual

S&P
S&P SILENT-100 DESIGN User manual

S&P
S&P SILENTUB-100 Manual

S&P
S&P TPSB ECOWATT Series User manual

S&P
S&P TH-MIXVENT Series User manual

S&P
S&P VENT-355 Manual

S&P
S&P DUOVENT COMPACT DV User manual

S&P
S&P HTB-150 N IP55 User manual

S&P
S&P HTB-140 Technical Document

S&P
S&P HTB-2500 Quick guide

S&P
S&P PV-DEDPV User manual

S&P
S&P CADB-HE ECOWATT Series User manual

S&P
S&P HVE User manual

S&P
S&P VENT-160 N N8 User manual

S&P
S&P ARTIC TOWER N User manual