manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens KNX RL 524D23 User manual

Siemens KNX RL 524D23 User manual

GAMMA instabus
Solar protection actuator 2 x 6 A DC
RL 524D23
The solar protection actuator is used to control shutters, awnings, sunblinds or
ventilation flaps with DC 24 V.
● End position detection by current detection for automatic move time determination.
● Built-in device for installation in an automation module box AP 118 or in a M590
DIN rail housing, which has to be ordered separately
● Maintenance-free terminals for connecting and looping through solid, stranded and
fine-stranded conductors.
Functions for configuration with ETS:
● Extensive control and override functions and status messages for each channel
● On-site control of the drives
● Direct moving to element or slat positions.
● Automatic control of the drives with configurable behavior when the sun is shining
(sun tracking control)
● Scene control for calling up and storing defined element positions
● Safety functions through overrides in case of wind, rain, frost, moving blocks etc.
A6V12883339_en--_b Smart Infrastructure
2023-10-27 Building Products
2
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Characteristics
The solar protection actuators are used to control blinds, roller shutters, sliding shutters, ex-
ternal blinds, awnings or ventilation flap drives with DC 24 V. They are used in building auto-
mation. Device control is conducted via KNX.
Through the selection of various operating modes such as manual and automatic mode,
solar protection is controlled both locally and centrally. Automatic commands from a weather
station enable sun tracking control with shade edge tracking.
The device is designed for installation in an automation module box AP 118 or a M590 DIN
rail housing, which has to be ordered separately
The bus connection of the device uses a bus terminal block. The electronics of the device
are supplied via the bus voltage (no additional supply voltage required).
The maintenance-free terminals are for connecting solid, fine-stranded and stranded con-
ductors with conductor cross-sections from 0.5 to 2.5 mm² to the relay output channels.
Stranded and fine-stranded conductors can be plugged into the terminals without ferrules.
DC 24 V FELV is supplied centrally via separate connection terminals to control the motor
drives.
Solar protection actuator RL 524D23 consists of the device (hardware) and the application
program (software). Depending on its use, each relay output channel can be assigned differ-
ent functions.
Functions
Factory settings
In the factory settings, the functions “manual operation solar protection“ up/down and
“manual operation stop, slats” open/close are assigned to the building site function for all
channels (outputs).
Building site function
In the factory settings, the building site function enables moving up and down as well as
stopping and changing the slat position of an element via a corresponding bus button, even if
these devices are yet to be commissioned via the Engineering Tool Software (ETS).
Programming mode
Fig.1: Programming button and programming LED (exemplary illustration)
After bus voltage recovery, wait several seconds before pushing the programming (1) but-
ton (not before booting is complete).
Activating programming mode
◈Briefly press the programming button (1) (< 2 seconds).
aProgramming mode is activated.
aThe programming LED (2) illuminates continuously.
Deactivating programming mode
üProgramming mode is activated. The programming LED (1) lights up continuously.
3
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
◈Briefly press the programming button (1) (< 2 seconds).
aProgramming mode is deactivated.
aThe programming LED (2) is not illuminated.
Resetting the device to factory settings
A very long push of the programming button of more than 20 seconds resets the device to its
factory settings. This is indicated by the programming LED flashing steadily for 8 seconds.
All configuration settings are deleted. The building site function of the delivery state is re-ac-
tivated.
Behavior on unloading the application program
After unloading the application program with the ETS, the unloaded device has no functions.
Behavior on voltage failure/recovery
The electronics of the device are bus powered. Therefore, a grid voltage failure only leads to
a functional failure of the device if the bus voltage also fails as a result of the grid voltage fail-
ure.
In case of bus voltage failure, the current status and other values for each channel are saved
permanently so that they can be restored when the bus voltage is recovered.
When bus voltage is recovered, the configured actions for each channel are executed and,
depending on the parameters set, new statuses are reported.
Each channel can be independently configured with parameters to define what status it is to
assume in case of bus voltage failure (up, down, no change or stop). In addition, a starting
behavior when bus voltage is recovered can be configured for each active override (e.g.
alarms, moving blocks).
When bus voltage is recovered, one of the following functions can be selected as the starting
value: Up, down, no change, as per parameter and stop. A delay can be configured for the
starting value.
End position detection and automatic move time determination
The move time to defined element positions between the end positions can be analyzed
automatically.
To this end, current detection is used to detect if the upper or lower end position is reached
in the context of the respective Up/Down command.
Direct control commands: Move Up / Down, Stop, Slat Adjustment
1-bit objects can be used to control the moving direction of the solar protection via Up and
Down commands.
In the “Shutter” operating mode, an ongoing blind move for the respective channel can be
stopped or, if the blind is stationary and a logical “0” is received, the slats can be opened by
one step; if a logical “1” is received, they can be closed by one step.
Direct control commands: Move to positions 0…100 %
1-byte objects can be used to move the sunblind of the corresponding channel to any posi-
tion between 0 and 100% in manual operation and automatic operation.
In “Shutter” operating mode, the slats of the corresponding channel can also be moved into
any position between 0 and 100%.
Scene control
8-bit scene control
Using 8-bit scene control, current solar protection or slat positions can be assigned to a
scene and retrieved.
Move to position 1/2, 3/4 (1-bit scene control)
The function “move to position 1/2, 3/4” is particularly suitable to repeatedly move to pre-
ferred element positions in combination with the 1-bit scene control.
The function can be used to specify 4 different solar protection positions for each channel. 2
of these preset positions (1/ 2 or 3/4) are addressed via one group address with the values
“0” and “1.”
4
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
The stored default settings of the positions can also be changed without programming the
device via KNX. To do this, the blinds must be moved to the desired element height. This
new position with the value “0” and “1” is copied to the memory of the device via the commu-
nication objects “position 1/2” (store) and “position 3/4” (store).
A preferred blind position can be called and stored at the push of a button. To do this, a key
is pressed briefly to call up a position and a long key press is used to store it as a desired
position.
Manual operation/automatic operation
The “manual operation” and “automatic operation” functions can be released separately for
each channel via the ETS.
Manual operation is used for on-site control of the drives either individually or as a central
command. Direct moving to element or slat positions is also possible here.
Automatic operation is configured for automated control of drives via a weather station. Auto-
matic control via central commands is also possible.
When the sun is shining, sun tracking control of slats or shadow line tracking is implemented.
Central control
Each solar protection channel can be controlled centrally in manual operation and in auto-
matic operation (manual operation solar protection central, automatic operation solar protec-
tion central). In addition, an individual delay time can be configured for time-delayed opera-
tion of the solar protection to avoid load peaks and noise pollution when starting up several
drives.
Overrides
Up to seven different override function blocks can be activated via ETS to override the solar
protection functions. The overrides can be configured per channel and individually.
For each of the override function blocks, one of the following functions can be selected: Wind
Alarm, Rain Alarm, Frost Alarm, Lock, Forced position, Forced Control, Range limitation,
User defined.
This enables flexible configuration of an individual priority-specific override for each channel.
For the override functions a control value input can be selected instead of a switching control
input.
Different priorities can be assigned to the override functions.
Range limitation
In order to not disturb the movement of the solar protection when windows, doors or sky-
lights are open, the movement range can be restricted with an upper and lower limit.
Element settings
For exact positioning and adjustment of the elements, the move times between the respect-
ive end positions can be determined automatically. For this purpose, there are calibration
runs, which can be configured.
An end position dead time can also be set for this.
Alternatively, the move times of the elements or the slat move times and step sizes for slats
(shutters) can be set manually.
Advanced configuration
Specific settings for controlling the drives are offered. This includes, e.g. the swapping of the
UP and DOWN connections. A reverse pause time is set to protect the motor.
A slip compensation time can be projected as slip compensation for a change in direction.
The drives can be controlled with start-up delays or run on for a configured time.
Status messages
Responses on element positions, such as dynamic element position, slat position, moves,
moving directions, reaching the upper or lower end position are reported. In addition, re-
sponses to the different overrides and the current operating mode, such as automatic opera-
tion, can be displayed. In automatic end position detection, a status on the calibration of the
move time is communicated.
Diagnostic functions
Contact faults can be reported.
5
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Schematic design of a solar protection actuator channel
The following scheme shows the function of a channel of the solar protection actuator using
the “blind” function in a logical context.
Position
Manual operation
Override Automatic operation
Calibration
Stop, slats
Solar protection
via dimming
8-bit scene
Position
% control
Central
solar protection
Automatic operation
Send status values
% control
Sunshine
Central solar protection
Override 1 – 7
External value
solar protection position
Start calibration of
moving time
8-bit
1-bit
Manual operation
Delay
t
Off
Automatic operation
Delay
t
Status
automatic operation
Override 1 – 7
Control
Recall/store
positions
≥ 1 active
Overrides
status
Overrides
1 – 7 status
Status upper end position
Status lower end position
Status moving direction
Status
solar protection position
Status
slat position
Status calibration
moving time
Automatic operation
Override
Status solar protection
Cali-
bration Manual operation Position
Solar protection
Up/Down
Status drive moving
6
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Technical design
Position and function of the operating and display elements and connections
4
5
6
8
123
7
Fig.2: Position and function of the connections and labeling, operating and display elements Solar pro-
tection actuator RL 524D23, 2 x 6 A DC
Pos. Connection, operating or display
element
Function
1 Connection pins for KNX bus terminal
block
Connect KNX bus
2 Programming button Short push of button (<2s):
● Activate programming mode, display status (programming
LEDon = active)
Very long push of button (>20s):
● Reset to factory settings (programming LED starts flashing
after 20s)
3 Programming LED (red)
4 Label with barcode of the device Two copies of the barcode are printed on it. The second
barcode can be separated to facilitate commissioning and, for
example, be kept with the documents for the project.
5 Labeling of switching contacts for the channels and input terminals
6 Connection terminals of the channels Connect motors
7 Feed in 24 V DC for all channels (motors)
8 Label field Enter physical address
7
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Type overview
Type Designation Item number KNX PL-Link
RL 524D23
Solar protection
actuator,
2 x 6 A, DC 24 V
5WG1524-4DB23 yes
Scope of delivery
Module for installation in AP118 automation module box or M590 DIN rail housing.
Accessories
Type Order number Designation
5WG1118-4AB01 Automation module box AP 118
5WG1590-8AB01 DIN rail housing M590
Table1: Automation module box AP 118 and DIN rail housing M590
Version of the Engineering Tool Software
Application Version
Engineering Tool Software (ETS) ETS 5 or above
Product documentation and support
Product documentation
Documents related the product, such as operating and installation instructions, application
program description, product database, additional software and CE declarations can be
downloaded from the following website:
http://www.siemens.com/gamma-td
Frequently asked questions
For frequently asked questions about the product and their solutions, see:
https://support.industry.siemens.com/cs/products?dtp=Faq&mfn=ps&lc=en-WW
FAQ
Support
Contact details for additional questions relating to the product:
Tel.: +49 89 9221-8000
8
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
http://www.siemens.com/supportrequest
Notes
Security
The device is designed to be installed in an AP118 automation module box or a M590 DIN
rail housing.
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.
● The device should only be installed and put into operation by a certified electrician.
● When connecting the device, ensure that the device can be enabled.
● Do not open the casing of the device.
● Only use conventional transformers that comply with the relevant standards and con-
tain a thermal fuse.
● For planning and setup of electric systems, the relevant guidelines, observe the regula-
tions and standards of the respective country.
● Secure the phases with a B10 line protection switch.
Commissioning
Areas of use
The device is installed in an automation module box AP 118 in dry interior spaces.
Connecting motors to the relay contacts
Fig.3: Solar protection actuator RL 524D23, 2 x 6 A DC
Cu
9
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
0.5...2.5 mm²
2.5 mm²
Connecting KNX
Fig.4: Solar protection actuator RL 524D23, 2 x 6 A DC
Cu
0.6…0.8mm
Testing KNX 24 V DC type. SELV
This test can be used to check whether the bus connection cable is connected with the cor-
rect polarity and whether device is supplied with bus voltage.
Fig.5: Solar protection actuator RL 524D23, 2 x 6 A DC
If the programming button is pushed for more than 20seconds, the device is reset to its fact-
ory settings.
10
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Disposal
The device is considered an electronic device for disposal in accordance
with European Directive and may not be disposed of as domestic waste.
● Use only designated channels for disposing the devices.
● Comply with all local and currently applicable laws and regulations.
If a device is defective, contact the local sales office.
11
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Technical data
Power supply
KNX bus voltage DC 24 V (DC 21...30 V)
KNX power consumption 15 mA
KNX power loss (power consumption) 0.15 W
Outputs
Number of drive channels 2
Switching voltage DC 24 V
Output current
Rated current per channel 6 A
Rated current per device 10 A
Current sensing for move time determination > 150 mA
Service life
Mechanical lifespan 10,000,000 switching cycles
Electrical lifespan 50,000 switching cycles
Power loss
Maximum power loss of the device at rated
output
3 W
Maximum power loss per output at rated
output and maximum resistive load
1.8 W
Switching capacities/load types, loads
Resistive load 144 W
Minimum switching capacity 5 V
100 mA
DC1 switching capacity 24 V
6 A
Mechanical data
Housing material Plastic
Dimensions See Dimension drawing [}13]
Product weight 82 g
Fire load 2 MJ
Environmental conditions
Ambient temperature in operation -5 °C...+45 °C (23 °F...113 °F)
Storage temperature -20 °C...+70 °C (-4 °F...158 °F)
Transport temperature -25 °C...+70 °C (-13 °F...158 °F)
Relative humidity
(non-condensing)
5 %...95 %
Environmental rating EN 60721-3-3 class 3k5
Protection settings
Degree of pollution (according to IEC
60664-1)
2
Over-voltage category
(according to IEC 60664-1)
III
12
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Protection settings
Housing protection class (according to EN
60529)
IP20 (when installed AP 118)
Electrical safety, bus (SELV) yes
Electrical safety, device fulfills EN 50428
EMC requirements, device complies with EN 50428
Test mark KNX, EAC, RCM, WEEE, China-RoHS
CE mark yes
Reliability
Failure rate (at 40°C) 1024 fit
Connection example
The following connection example shows the connection of 2 DC motors for control (up/down
or open/close) e.g. of solar protection, door, window or ventilation flaps via channels A and
B.
.
13
Smart Infrastructure A6V12883339_en--_b
GAMMA instabus 2023-10-27
Dimension drawing
Compliance information
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens 2023
Technical specifications and availability subject to change without notice.
Document ID A6V12883339_en--_b
Edition 2023-10-27

Other Siemens Controllers manuals

Siemens Simatic S7-1500/ET 200MP User guide

Siemens

Siemens Simatic S7-1500/ET 200MP User guide

Siemens scalance WLC711 Operating manual

Siemens

Siemens scalance WLC711 Operating manual

Siemens PXC00-U User manual

Siemens

Siemens PXC00-U User manual

Siemens SIMOTION C User manual

Siemens

Siemens SIMOTION C User manual

Siemens RMU7 Sereis User manual

Siemens

Siemens RMU7 Sereis User manual

Siemens Simatic S7-1500 Parts list manual

Siemens

Siemens Simatic S7-1500 Parts list manual

Siemens RLU2 Series User manual

Siemens

Siemens RLU2 Series User manual

Siemens Synco 200 User manual

Siemens

Siemens Synco 200 User manual

Siemens FLN User manual

Siemens

Siemens FLN User manual

Siemens GLB111.9E/MO User manual

Siemens

Siemens GLB111.9E/MO User manual

Siemens SIMODRIVE 611U User manual

Siemens

Siemens SIMODRIVE 611U User manual

Siemens ACVATIX SQV..P Series User manual

Siemens

Siemens ACVATIX SQV..P Series User manual

Siemens RXB39.1 User manual

Siemens

Siemens RXB39.1 User manual

Siemens IP Controller N350E User manual

Siemens

Siemens IP Controller N350E User manual

Siemens Stratos Outstation User manual

Siemens

Siemens Stratos Outstation User manual

Siemens OpenAir GDE Series Owner's manual

Siemens

Siemens OpenAir GDE Series Owner's manual

Siemens SQK34.00S User manual

Siemens

Siemens SQK34.00S User manual

Siemens 3RK1304-5 S70 Series User manual

Siemens

Siemens 3RK1304-5 S70 Series User manual

Siemens SIMATIC S7 User manual

Siemens

Siemens SIMATIC S7 User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens RWD44U User guide

Siemens

Siemens RWD44U User guide

Siemens ECOFAST User manual

Siemens

Siemens ECOFAST User manual

Siemens SINAMICS S120 Technical Document

Siemens

Siemens SINAMICS S120 Technical Document

Siemens SIMATIC S7-200 User guide

Siemens

Siemens SIMATIC S7-200 User guide

Popular Controllers manuals by other brands

YASKAWA MOTOMAN DX100 Operator's manual

YASKAWA

YASKAWA MOTOMAN DX100 Operator's manual

Signet 8860 user manual

Signet

Signet 8860 user manual

Bartlett 3K Operation manual

Bartlett

Bartlett 3K Operation manual

Emerson Aventics SENTRONIC HD 616 Series installation manual

Emerson

Emerson Aventics SENTRONIC HD 616 Series installation manual

Evco Vcolor 318 M Installer manual

Evco

Evco Vcolor 318 M Installer manual

Flowserve FlowAct IG 253 Assembly instructions

Flowserve

Flowserve FlowAct IG 253 Assembly instructions

ROBBE 8400 operating instructions

ROBBE

ROBBE 8400 operating instructions

Dynasty ProAudio PMC-2 owner's manual

Dynasty ProAudio

Dynasty ProAudio PMC-2 owner's manual

D-Link PowerLine DHP-W611AV user manual

D-Link

D-Link PowerLine DHP-W611AV user manual

Mitsubishi Electric RJ71PB91V-U-IN-E user manual

Mitsubishi Electric

Mitsubishi Electric RJ71PB91V-U-IN-E user manual

KB Genesis KBAC-24D Installation & operation manual

KB Genesis

KB Genesis KBAC-24D Installation & operation manual

junger C8702 manual

junger

junger C8702 manual

Xilinx XC4000 Series manual

Xilinx

Xilinx XC4000 Series manual

Mateksys H743-WING quick start guide

Mateksys

Mateksys H743-WING quick start guide

SoundForce SFC-OB user manual

SoundForce

SoundForce SFC-OB user manual

Kohler Curtis F Series manual

Kohler

Kohler Curtis F Series manual

PS Automation PSQ-AMS Series operating instructions

PS Automation

PS Automation PSQ-AMS Series operating instructions

Rain Bird ESP-LX manual

Rain Bird

Rain Bird ESP-LX manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.