manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens LME39 Series User manual

Siemens LME39 Series User manual

2/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
Do not to open, interfere with or modify the unit!
•All activities (mounting, installation and service work, etc.) must be performed by quali-
fied staff
•Before making any wiring changes in the connection area of the LME39…, completely
isolate the plant from mains supply (all-polar disconnection). Ensure that the plant
cannot be inadvertently switched on again and that it is indeed dead. If not discon-
nected, there is a risk of electric shock hazard
•Ensure protection against electric shock hazard by providing adequate protection for
the burner control’s connection terminals
•Check the connecting lines of the air pressure switch for short-circuits («LP» between
terminals 2 and 6)
•Press the lockout reset button / operation button only manually (applying a force of no
more than 10 N) without using any tools or pointed objects
•Fall or shock can adversely affect the safety functions. Such units must not be put into
operation, even if they do not exhibit any damage
•Each time work has been carried out (mounting, installation, service work, etc.), check
to ensure that wiring is in an orderly state and make the safety checks as described in
«Commissioning notes»
•The data line for the AZL2… display and operating unit or other accessories, such as
the OCI410… (plugs into the BCI interface), must be connected or disconnected only
when the burner control is dead (all-polar disconnection), since the BCI interface does
not ensure safe separation from mains voltage
Engineering notes
•When used in connection with actuators, there is no position feedback signal from the
actuator to the burner control
•The running times of the actuators must match the burner control’s program. An addi-
tional safety check of the burner control together with the actuators is required
•If the communication interface (jack RJ11) is not used, protection against electric
shock hazard must be provided (jack must be covered up)
Mounting notes Ensure that the relevant national safety regulations are complied with.
3/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Parameterization Siemens supplies the LME39… burner controls with the factory settings as specified in
«Type summary».
The OEM can change the Siemens default settings to meet its own requirements.
With the LME39…, the burner control’s characteristics are determined primarily through
parameterization. Every time the unit is recommissioned, the parameter settings must be
checked. The LME39… must never be transferred from one plant to another without
matching the parameters to the new plant.
Caution Parameters and settings may only be changed by qualified staff.
If parameters are changed, responsibility for the new parameter settings is assumed by
the person who – in accordance with the access rights – has made parameter changes
on the respective access level.
After parameterization, the OEM must check to ensure that safe burner operation will
be warranted.
The OEM which made the settings is always responsible for the parameters, their set-
tings and compliance of the respective application with the relevant national and inter-
national standards and safety regulations, such as EN 676, EN 267, EN 1643, etc.
Siemens, its suppliers and other Group Companies of Siemens Ltd. do not assume
responsibility for special or indirect damage, consequential damage, other damage, or
damage resulting from wrong parameterization.
Warning If the factory settings are changed, all changes made must be documented and
checked by the OEM.
The OEM is obliged to mark the unit accordingly and to include at least the list of device
parameters and settings in the burner’s documentation.
Siemens also recommends attaching an additional mark on the LME39… in the form of
an adhesive label. As specified in EN 298, the label should be easy to read and wipe
proof.
The label with a maximum size of 70 x 45 mm can be attached to the upper part of the
housing.
Example of label: OEM logo
Product no. / part no.: 1234567890ABCD
Caution! OEM settings:
Parameter no.
225 = 30 s (t1) 226 = 2 s (t3)
230 = 10 s (t4) 234 = 0 s (t8)
240 = 1 (repetition)
257 = 2 s (t3n) TSA = t3n + 0.,7 s
259 = 30 s (t11)
260 = 30 s (t12)
4/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Installation notes
•Always run the ignition cables separate from the unit and other cables while observing
the greatest possible distance
•Do not mix up live and neutral conductors
•Install switches, fuses, earthing, etc., in compliance with local regulations
•The connection diagrams show the burner controls with earthed neutral conductor.
In networks with nonearthed neutral conductor and ionization current supervision, ter-
minal 2 must be connected to the earth conductor via an RC unit (product no.
ARC 4 668 9066 0). It must be made certain that local regulations are complied with
(e.g. protection against electric shock hazard) since AC 120 V / 50 Hz or
AC 230 V / 60 Hz mains voltage produces peak leakage currents of 2.7 mA
•Make certain that the maximum permissible current rating of the connection terminals
will not be exceeded
•Do not feed external mains voltage to the control outputs of the unit. When testing the
devices controlled by the burner control (fuel valves, etc.), the LME39… must not be
connected
•In the case of burners with no fan motor, an AGK25 must be connected to terminal 3
of the unit, or else the burner cannot reliably be started up
•To prevent mixup of different types of burner controls, the LME39… must always be
used in connection with grey plug-in bases AGK11.6. Make absolutely certain that the
live conductor for the control thermostat or pressurestat «R / W» is tapped after the
gas pressure switch «GP» and the safety limit thermostat «STB» and connected to
terminal 11 (refer to «Connection diagram»)
•Connecting cable from LME39… to AZL2…or from LME39… to OCI400 / OCI410…:
Since the BCI interface has no safe separation from mains voltage, the connecting ca-
ble between LME39… and AZL2…, or LME39… and OCI400 / OCI410…, must con-
form to certain specifications. Siemens has specified the cable for use under the
burner hood (cable supplied by Hütter; refer to «Technical data»). When using cables
of other manufacture, Siemens’ requirement will not necessarily be met
•Do not lay the connecting cable from the LME39… to the AZL2… together with other
cables. Use a separate cable
•Service operation with a longer connecting cable from LME39… to AZL2…, or from
LME39… to OCI410…:
If a longer cable is required for service work for example (short-time, <24 hours), note
that above usage under the burner hood no longer applies and, for this reason, the
cable can be subjected to increased mechanical stress. In that case, extra cable
sheathing is required (e.g. heat shrink tubing)
•Both the cable and the AZL2… display and operating unit must be shipped and stored so
that no damage due to dust and water can occur when used in the plant later on
•To ensure protection against electric shock hazard, make certain that, prior to switch-
ing on power, the cable is correctly connected to the AZL2…
•The AZL2… must be used in a dry and clean environment
•For safety reasons, feed the neutral conductor to terminal 2. Connect the burner com-
ponents (fan, ignition transformer and gas valves) to the neutral distributor as shown
below in the illustration. The connection between neutral conductor and terminal 2 is
prewired in the base
Example
23
745
BV2
BV1
Z
M
N7106a01/0405
Correct wiring of neutral conductors!
Legend
BV... Fuel valve
M Fan motor
Z Ignition transformer
5/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Electrical connection of flame detectors
It is important to achieve practically disturbance- and loss-free signal transmission:
•Never run detector cables together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate cable
•Observe the permissible length of the detector cables (refer to «Technical data»)
•The ionization probe is not protected against electric shock hazard
•Locate the high-voltage ignition electrode and the ionization probe such that the igni-
tion spark cannot arc over to the ionization probe (risk of electrical overloads) and that
it cannot adversely affect the supervision of ionization
•Insulation resistance
– Must be a minimum of 50 MΩbetween ionization probe and ground
– Soiled detector holders reduce the insulation resistance, thus supporting cree-
page currents
•Earth the burner in compliance with the relevant regulations; earthing the boiler alone
does not suffice
Commissioning notes When commissioning the plant for the first time or when doing maintenance work, make
the following safety checks:
Safety check to be carried
out Expected response
Supply state (factory setting):
a) Burner startup with previously
interrupted line to the flame
detector
Lockout at the end of «TSA»
→Max. 3 repetitions
b) Burner operation with simulated
loss of flame. For that purpose,
cut off the gas supply
•Establishment of flame at the end of
«TSA»
→Max. 3 repetitions
(can be parameterized)
→Factory setting: Lockout
•No establishment of flame at the end
of «TSA»
→Lockout
c) Burner operation with simulated
air pressure failure (not with
atmospheric burners)
Immediate lockout
After installation and commissioning, the parameterized values and settings must be
documented by the person / heating engineer responsible for the plant. These data can
be printed out with the help of the ACS410 PC software, for example, or must be written
down. The documentation must be checked by the expert and then kept in a safe place.
On the OEM access level of the LME39…, it is possible to make parameter settings
that differ from application standards. When setting the parameters, it must be made
certain that the application will run safely in accordance with legal requirements.
Prior to commissioning, the following points must be checked:
•The correct time parameter settings, especially the settings of the safety and pre-
purge times
•The correct functioning of the flame detector in the event of loss of flame during
operation (including the response time); with extraneous light, during the prepurge
time and, when there is no establishment of flame, at the end of the safety time
•Air pressure
•Safety loop (e.g. STB)
•Minimum gas pressure (GP)
6/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Standards and certificates
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Directive for gas-fired appliances
2004/108/EC
90/396/EEC
ISO 9001: 2000
Cert. 00739 ISO 14001: 2004
Cert. 38233
Identification code to EN 298
LME39.100… F T C L B N
LME39.400… A B C L B N
Disposal notes The unit contains electrical and electronic components and must not be disposed of to-
gether with domestic waste.
Local and currently valid legislation must be observed.
Mechanical design
•The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It is of
plug-in design and engages audibly in the base
•Burner controls LME39… and plug-in base AGK11.6 are silver-grey (RAL7001)
•The housing accommodates the
- microcontroller for the control sequence and the control relays for load control
- electronic flame signal amplifier (ionization)
- lockout reset button with its integrated 3-color signal lamp (LED) for operational
status and fault status messages and the socket for connecting the OCI400 inter-
face adapter
•The AZL2… display and operating unit is for direct connection to the burner control. All
safety-related digital inputs and outputs of the system are monitored by the contact
feedback network. Operation and parameterization of the LME39… is accomplished
with the AZL2… or via the OCI410… / ACS410
•Unlimited burner capacity (thermal output on startup ≤120 kW)
•3 repetitions in the event of loss of flame during operation (can be parameterized)
•Multicolor indication of operational status and fault status messages
•Forwarding of operational status messages, fault status messages and full service
information via additional OCI400 / OCI410… interface adapter and Windows ACS410
PC software
RJ11 jack for connection of the AZL2… display and operating unit or the OCI410… inter-
face adapter for communication and parameterization via Windows ACS410 PC tool.
The most important time parameters for the program:
−Prepurge time (t1)
−Preignition time (t3)
−Postignition time (t3n)
−Interval (t4)
−Postpurge time 1 (t8-1)
−Opening time for actuators (t11)
−Closing time for actuators (t12)
Both the prepurge time and the safety times are safety-related and can be changed by the
OEM with the help of the display and operating unit.
LME39...
Indication and
diagnostics
Display and
communication
Time parameters
7/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Type summary (other types of burner controls on request)
The product nos. given below apply to the LME39… burner control without plug-in base
and without flame detector. For ordering information on plug-in bases and other accesso-
ries, refer to «Ordering».
Flame detector Product no. Main
voltage
tw
max.
s
TSA
max.
s
t1
(P225)
min.
s
t1´
(P256)
min.
s
t3
(P226)
approx.
s
t3n
(P257)
ap-
prox.
s
t4
(P230)
approx.
s
t8
(P234)
min.
s
t10
(P224)
max.
s
t11
(P259)
min.
s 1)
t12
(P260)
min.
s 1)
t22
ap-
prox.
s
2)
Burner controls for 2-stage burners with actuator control and communication
LME39.100A1 AC 120 V 2.5 (3)
t3n + 0.7 30 --- 3 2.3 10 0 65 30 30 --- 1
Ionization probe (ION)
or flame detector
QRA… 3) with
AGQ3…A27 LME39.100A2 AC 230 V 2.5 (3)
t3n + 0.7 30 --- 3 2.3 10 0 65 30 30 --- 1
min. --- --- 0.7 0 --- 1 0 1 0 --- 0 0 --- 1
Setting range Max. --- --- 4.7 75 --- 37.5 4 75 240 --- 75 75 --- 4
Increment (s) --- --- 0.147 0.294 --- 0.147 0.147 0.294 5 --- 0.294 0.294 --- 1
Burner controls for atmospheric, 2-stage burners without actuator control with communication
LME39.400A1 AC 120 V 2.5 (5)
t3n + 0.7 --- 14.5 1.7 4 9 0 --- --- --- 5 1
Ionization probe (ION)
or flame detector
QRA… 3) with
AGQ3…A27 LME39.400A2 AC 230 V 2.5 (5)
t3n + 0.7 --- 14.5 1.7 4 9 0 --- --- --- 5 1
min. --- --- 0.7 --- 0 1 0 1 0 --- --- --- 0 0
Setting range Max. --- --- 4.7 --- 75 37.5 4.2 75 1237 --- --- --- 8 4
Increment (s) --- --- 0.147 --- 0.294 0.147 0.147 0.294 5 --- --- --- 0.147 1
Note on parameterization:
Use the AZL2… or ACS410 to always set the exact value of the required time (multiples of increments of 0.147
seconds or 0.294 seconds).
When parameterizing minimum or maximum times, the possibility of a ±7% tolerance must be taken into con-
sideration.
For minimum values: The value to be parameterized must be at least 7% greater.
For maximum values: The value to be parameterized must be at least 7% smaller.
Example: t1min shall be set to 30 s
Calculation: 30 s + 7% = 32.1 s
Value to be parameterized: Must be equal to or greater than the calculated value
(e.g. 32.34 s)
Example: TSAmax. shall be set to 5 s
Special case here: TSA is set directly via the change of t3n using the following formula:
t3n = TSA – 0.7 s
Calculation: 5 s – 7% = 4.65 s
t3n = 4.65 s – 0.7 s = 3.95 s
Value t3n to be
parameterized: Must be equal to or smaller than the calculated value (e.g. 3.822 s)
tw Waiting time t4 Interval between ignition «Off» and «BV2»
TSA Safety time t8 Postpurge time
t1 Prepurge time t10 Specified time for air pressure signal
t1´ Purge time t11 Programmed opening time for actuator «SA»
t3 Preignition time t12 Programmed closing time for actuator «SA»
t3n Postignition time t22 2nd safety time
1) Maximum running time available for actuator «SA». The actuator’s running time must be shorter
2) Repetition (maximum number of startups per controlled start)
3) Only AC 230 V
Legend
8/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Technical data Mains voltage AC 120 V +10% / -15%
AC 230 V +10% / -15%
Mains frequency 50...60 Hz ±6%
Power consumption 12 VA
External primary fuse (Si) Max. 10 A (slow)
Mounting position Optional
Input current at terminal 12 Max. 5 A
Weight Approx. 160 g
Safety class I
Degree of protection IP40 (to be ensured through mounting)
(if RJ11 jack is not covered, only IP10)
Perm. cable length terminal 1 Max. 1 m at a line capacitance of 100 pF/m
(max. 3 m at 15 pF / m)
Perm. cable length from QRA… to
AGQ3…A27 (lay separate cable) Max. 20 m at 100 pF / m
Remote reset laid separately Max. 20 m at 100 pF / m
Perm. cable length terminals 8 and 10 Max. 20 m at 100 pF / m
(lay separate cable)
Perm. input voltage terminals 6 and 11 AC 120 V +10% / -15%
AC 230 V +10% / -15%
Perm. cable lengths other terminals Max. 3 m at 100 pF / m
Possible input current terminals 6 and 11 0.5 mA
Current rating At cosϕ≥0.6 At cosϕ= 1
- Terminal 3 Max. 2.7 A
(15 A for max. 0.5 s →only LME2…) Max. 3 A
- Terminals 4, 5, 7 and 9 Max. 1.7 A Max. 2 A
- Terminal 10 Max. 1 A Max. 1 A
Signal cable Color white
Unshielded
Conductor 4 x 0.141 mm²
Supplier Reference:
Hütter
http://www.huetter.co.at/telefonkabel.htm
Order number: on request
Location Under the burner hood (extra measures
required for compliance with SKII EN
60730-1)
Storage DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Transport DIN EN 60 721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Operation DIN EN 60 721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...+60 °C
Humidity <95% r.h.
Condensation, formation of ice and ingress of water are not permitted!
General unit data
Connecting cable
Display →BCI
Environmental
conditions
9/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Technical data (cont´d)
LME… burner controls have a designed lifetime* of 250,000 burner startup cycles which,
under normal operating conditions in heating mode, correspond to approx. 10 years of
usage (starting from the production date given on the type field). This lifetime is based on
the endurance tests specified in standard EN 298 and the table containing the relevant test
documentation as published by the European Association of Component Manufacturers
(Afecor) (www.afecor.org).
The designed lifetime is based on use of the burner controls according to the manufac-
turer’s Data Sheet and Basic Documentation. After reaching the designed lifetime in terms
of the number of burner startup cycles, or the respective time of usage, the burner control
is to be replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
At mains voltage
UN = AC 120 V ¹) UN = AC 230 V ¹)
Detector voltage between ionization probe and ground
(AC voltmeter Ri ≥10 MΩ) AC 50...120 V AC 115...230 V
Switching threshold (limit values):
Switching on (flame on) (DC ammeter Ri ≤5 kΩ)
Switching off (flame off) (DC ammeter Ri ≤5 kΩ)
≥DC 1.5 µA
≤DC 0.5 µA
≥DC 1.5 µA
≤DC 0.5 µA
Detector current required for reliable operation ≥DC 3 µA ≥DC 3 µA
Switching threshold in the event of poor flame during operation
(LED flashes green) Approx. DC 5 µA Approx. DC 5 µA
Short-circuit current between ionization probe and ground
(AC ammeter Ri ≤5 kΩ) Max. AC50...150 µA Max. AC 100...300 µA
¹) For applications outside the European Community, operation at mains voltage
AC 120 V / AC 230 V ±10% is ensured
Flame supervision with ionization probe is accomplished by making use of the conductivity
and rectifying effect of the flame. The flame signal amplifier only responds to the DC cur-
rent component of the flame signal. A short-circuit between ionization probe and ground
causes the burner to initiate lockout.
LME39... 1
7106v01/0405
M
C
+
+-
ION
Legend
C Electrolytic capacitor 100...470 µF; DC 10...25 V
ION Ionization probe
M Microammeter, Ri max. 5,000 Ω
For detector currents, refer to «Technical data».
Life cycle
Flame supervision
with ionization probe
Measuring circuit
10/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Technical data (cont´d)
Only in connection with LME39…A2 (AC 230 V)!
Mains voltage AC 230 V +10% / -15%
Mains frequency 50...60 Hz ±6%
Perm. cable length from QRA... to
AGQ3…A27 (lay separate cable) Max. 20 m
Perm. cable length from AGQ3...A27 to
LME39...A2 Max. 2 m
Weight of AGQ3...A27 Approx. 140 g
Mounting position Optional
Degree of protection IP40, to be ensured through mounting
Power consumption 4.5 VA
At mains voltage UNAC 220 V AC 240 V
Detector voltage at QRA... (with no load)
Terminal 3 off (refer to control sequence) DC 400 V DC 400 V
Terminal 3 on (refer to control sequence) DC 300 V DC 300 V
Detector voltage
Load by DC measuring instrument Ri >10 MΩ
Terminal 3 off (refer to control sequence) DC 380 V DC 380 V
Terminal 3 on (refer to control sequence) DC 280 V DC 280 V
DC current detector signals with UV detector
QRA... Min. required Max. possible
Measurement at the UV detector QRA… 200 µA 500 µA
With LME39…A2 burner controls, use of the AGQ3...A27 UV ancillary unit is mandatory.
(A) The correct functioning of aged UV cells can be checked with a UV test by ap-
plying a higher voltage to the UV cell after controlled shutdown until terminal 3
carries voltage.
Connection diagram Measuring circuit for measuring
the UV detector current
12 23
1
7106a02/1107
GP/SB
L
L
N
QRA... +
-
br bl rt sw AGQ3...A27
sw bl
(A)
LME39...A2
R/W
11
br bl rt sw
AGQ3...A27
sw bl
QRA
7101a06/1107
Measurement made at the UV
detector QRA…
C Electrolytic capacitor 100...470 µF; DC 10...25 V bl Blue
M Microammeter Ri max. 5,000 Ωbr Brown
QRA... UV detector gr Grey
GP Gas pressure switch rt Red
SB Safety limit thermostat sw Black
R Control thermostat or pressurestat
W Limit thermostat or pressure switch
Flame supervision
with AGQ3…A27 and
UV detector QRA...
A
ncillary unit
A
GQ3...A27
Legend
11/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Functions
•Burner control must be reset
•All contacts in the line are closed, request for heat
•No undervoltage
•Air pressure switch «LP» or CPI must be in its no-load position, or DBR2 is connected
•Fuel valve «BV1» is connected
•Fan motor or AGK25 is connected
•Flame detector is darkened and there is no extraneous light
•Safety shutdown from the operating position takes place should mains voltage drop
below about AC 85 V (at UN= AC 120 V)
•Restart is initiated when mains voltage exceeds about AC 90 V (at UN= AC 120 V)
•Safety shutdown from the operating position takes place should mains voltage drop
below about AC 175 V (at UN= AC 230 V)
•Restart is initiated when mains voltage exceeds about AC 185 V (at UN= AC 230 V)
After no more than 24 hours of continuous operation, the burner control initiates automatic
controlled shutdown followed by a restart.
If the connections of live conductor (terminal 12) and neutral conductor (terminal 2) are
mixed up, the burner control initiates lockout at the end of «TSA».
If lockout occurs, the outputs for the fuel valves, the burner motor and the ignition equip-
ment are immediately deactivated (<1 second).
Cause Response
Mains failure Restart
Voltage below undervoltage threshold Safety shutdown
Voltage above undervoltage threshold Restart
Extraneous light during «t1» Lockout
Extraneous light during «tw» Prevention of startup, lockout after 30 sec-
onds at the latest
No flame at the end of «TSA» Factory setting:
Lockout at the end of «TSA»
Can be parameterized:
Max. 3 repetitions, followed by lockout at the
end of «TSA»
Loss of flame during operation Factory setting:
Lockout
Can be parameterized:
•Establishment of flame at the end of
«TSA»
→Max. 3 repetitions
•No establishment of flame at the end of
«TSA»
→Lockout
«LP» welded in working position Prevention of startup, lockout after max. 65
seconds at the latest
«LP» welded in normal position Lockout on completion of «t10»
No air pressure signal after completion «t10» Lockout
«CPI» contact is open during «tw» Prevention of startup, lockout after 60 sec-
onds at the latest
In the event of lockout, the LME39… remains locked and the red signal lamp (LED) lights up.
The burner control can immediately be reset. This state is also maintained in the case of
mains failure.
Preconditions for
burner startup
Undervoltage
Controlled intermittent
operation
Reversed polarity
protection with
ionization
Control sequence in the
event of fault
12/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Functions (cont´d)
When lockout occurs, the burner control can immediately be reset. To do this, press the
lockout reset button for about 1 second (<3 seconds). The LME39… can only be reset when
all contacts in the line are closed and when there is no undervoltage.
If no flame is established at the end of «TSA», or if the flame is lost during operation, a
maximum of 3 repetitions per controlled startup can be performed via «R», or else lockout
will be initiated. Counting of repetitions is restarted each time a controlled startup via «R»
takes place.
Duty of PC tool software:
The PC tool is a component of the LME39… system and serves primarily as an operator
module for the following basic tasks:
•Visualization of system status with the following data:
- Parameters
- Process data
•Configuration and parameterization of the basic unit (individual parameters)
•Reset
)For operating and commissioning instructions, refer to User Handbook J7352.
Resetting the burner
control
Limitation of repetitions
(can be parameterized)
PC software ACS410
13/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Operation, indication, diagnostics
EK
7106z01/0405
Lockout reset button «EK...» is the key operating element for resetting
the burner control and for activating / deactivating the diagnostics func-
tions.
LED
7106z02e/0706
Red
Yellow
Green
The multicolor signal lamp (LED) in the lockout reset button is the key
indicating element for visual diagnostics and interface diagnostics.
Both «EK...» and LED are located under the transparent cover of the lockout reset button.
There are 3 diagnostics choices:
1. Visual diagnostics: Operational status indication or diagnostics of the cause of fault
2. Interface diagnostics: With the help of the OCI400 / OCI410 interface adapter and the
ACS410 PC software or flue gas analyzers of different makes
3. On the display of the AZL2…
Visual diagnostics:
In normal operation, the different operating states are indicated in the form of color codes
according to the color code table given below.
During startup, status indication takes place according to the following table:
Color code table for multicolor signal lamp (LED)
Status Color code Color
Waiting time «tw», other waiting states ......................................... Off
Ignition phase, ignition controlled zzzzzzFlashing yellow
Operation, flame o.k. .......................................... Green
Operation, flame not o.k. Flashing green
Extraneous light on burner startup SSSSSGreen-red
Undervoltage zSzSzSzSzSYellow-red
Fault, alarm S......................................... Red
Error code output (refer to «Error code
table»)
SSSSFlashing red
Interface diagnostics SSSSSSSSRed flicker light
...... Steady on SRed
Off zYellow
Green
Operation
Operational status
indication
Legend
14/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Operation, indication, diagnostics (cont´d)
After lockout, the red fault signal lamp is steady on. In that condition, visual diagnostics of
the cause of fault according to the error code table can be activated by pressing the lock-
out reset button for at least 3 seconds. Pressing the reset button again for at least 3 sec-
onds activates interface diagnostics. If, by accident, interface diagnostics has been acti-
vated, in which case the slightly red light of the signal lamp flickers, it can be deactivated
by pressing again the lockout reset button for at least 3 seconds. The instant of switching
over is indicated by a yellow light pulse.
The following sequence activates the diagnostics of the cause of fault:
EK
> 3 s
Flashing
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
Error code table
EK
> 3 s
Interface diagnostics
PC / analyzer
OCI400
EK
< 3 s
7106z04e/0706
Reset
On
Visual diagnostics
Lockout position Lockout position Lockout position
Error code table
Red blink code of
signal lamp (LED) «AL» at
term. 10 Possible cause
2 blinks On No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
3 x blinks On «LP» faulty
- Loss of air pressure signal after «t10»
- «LP» welded in normal position
4 blinks On Extraneous light when burner startup
5 blinks On Time out «LP»
- «LP» welded in working position
6 blinks On Free
7 blinks On Too many losses of flame during operation (limitation of repetitions)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
8 x blinks On Free
9 blinks On Free
10 blinks Off Wiring error or internal error, output contacts, other fault
14 blinks On CPI contact not closed
During the time the cause of fault is diagnosed, the control outputs are dead.
- Burner remains shut down
- External fault indication remains deactivated
- Fault status signal «AL» at terminal 10, according to the error code table
The diagnostics of the cause of fault is quit and the burner switched on again by resetting
the burner control. Press the lockout reset button for about 1 second (<3 seconds).
Diagnostics of the
cause of fault
15/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Connection diagram and control sequence of LME39.100...
NT RESET
EK
FSV
ION
L
N
MBV1 BV2
Z
AL
P
12
GP
STB SA
7106a05e/1206
pa LP
EK
K1
K2/1
K2/2
K3
K4
K5
BCI
H
Si
T
R / W
23
10 7459 6 11 81
μC control
SB / GP
AL
LP
SA
BV1
(LR) BV2
Z
FS
tw t1* t3n*
TSA* t4*
7106d02/0606
t11*
t12*
EK2
10
3
7
4
5
12
1
8
ABB´C
D
9
t3*
t10*
LK
M
I
6
E
R / W
A´
t8
**
11
* Times can be parameterized within the min. / max. limits
** TSA = t3n + 0.7 s
Connection diagram and control sequence of LME39.400...
NT RESET
EK
FSV
ION
L
N
MBV1 BV2
Z
AL
P
12
GP
STB
7106a07e/1206
EK
K1
K2/1
K2/2
K3
K4
K5
BCI
H
Si
T
R / W
23
10 7459 6 11 81
CPI
DBR2
ZV1
μC control
R / W
AL
ZV1
BV1
BV2
Z
FS
tw
t1´* t3n*
TSA*
t4* 7106d03/0706
11
10
3
7
4
5
1
t3*
M
9
CPI 6
t22*
**
SB / GP 12
ABB´ C D
EK2 8
A´
* Times can be parameterized within the min. / max. limits
** TSA = t3n + 0.7 s
Other application examples
The connection diagrams shown are merely examples which must be adapted in the individual
case depending on the application!
Only for burners with fan control via auxiliary contactor «HS» with «LP»
12 23 11 6
GP/SB
R/W
L
N
M
AGK25
7106a04/1106
HS LP
R/W
1)
¹) AGK25 is required only if an auxiliary relay with a coil resistance of
≥50 kΩis used
16/17
Building Technologies CC1N7106en
HVAC Products 20.02.2008
Legend
A Start command (switching on by «R»)
B-B´ Interval for establishment of flame
C Operating position of burner reached
C-D Burner operation (generation of heat)
D Controlled shutdown by «R»
•Burner is immediately shut down
•Burner control is immediately ready for new startup
I Cam Iactuator
t1 Prepurge time
t1´ Purge time
t3 Preignition time
t3n Postignition time
t4 Interval between ignition «Off» and release of «BV2»
t8 Postpurge time
t10 Specified time for air pressure signal
t11 Programmed opening time for actuator «SA»
t12 Programmed closing time for actuator «SA»
t22 2nd safety time
TSA Ignition safety time
tw Waiting time
AGK25... PTC resistor
AL Error message (alarm)
BV... Fuel valve
CPI Closed Position Indicator
DBR2 Wire link
EK... Remote lockout reset button
FS Flame signal
GP Gas pressure switch
HS Auxiliary contactor, relay
ION Ionization probe
KL Low-fire
LK Air damper
LKP Air damper position
LP Air pressure switch
LR Load controller
M Fan motor
MS Synchronous motor
NL Nominal load
QRA... Flame detector
R Control thermostat / pressurestat
RV Gas regulation damper
SA Actuator SQN...
STB Safety limit thermostat
Si External fuse
t Time
W Limit thermostat / pressure switch
Z Ignition transformer
Control signals
Required input signals
Permissible input signals

Other manuals for LME39 Series

1

Other Siemens Controllers manuals

Siemens SIRIUS S0 User manual

Siemens

Siemens SIRIUS S0 User manual

Siemens SQM40 Series Owner's manual

Siemens

Siemens SQM40 Series Owner's manual

Siemens N 567/01 User manual

Siemens

Siemens N 567/01 User manual

Siemens Simatic S7-1500/ET 200MP User guide

Siemens

Siemens Simatic S7-1500/ET 200MP User guide

Siemens OpenAir GEB 131.1E User manual

Siemens

Siemens OpenAir GEB 131.1E User manual

Siemens SINUMERIK 840D sl Quick start guide

Siemens

Siemens SINUMERIK 840D sl Quick start guide

Siemens GBB 1E Series User manual

Siemens

Siemens GBB 1E Series User manual

Siemens SIRIUS ET 200S User manual

Siemens

Siemens SIRIUS ET 200S User manual

Siemens SSD31 Series User manual

Siemens

Siemens SSD31 Series User manual

Siemens SINAMICS G120 User manual

Siemens

Siemens SINAMICS G120 User manual

Siemens GDB 9E Series User manual

Siemens

Siemens GDB 9E Series User manual

Siemens SINUMERIK 828D Turning User manual

Siemens

Siemens SINUMERIK 828D Turning User manual

Siemens GIB 1 Series User manual

Siemens

Siemens GIB 1 Series User manual

Siemens GNA 1E Series User manual

Siemens

Siemens GNA 1E Series User manual

Siemens SSC31 User manual

Siemens

Siemens SSC31 User manual

Siemens SINUMERIK 840DE User manual

Siemens

Siemens SINUMERIK 840DE User manual

Siemens Climatix S300 HRV User guide

Siemens

Siemens Climatix S300 HRV User guide

Siemens GGA Series User manual

Siemens

Siemens GGA Series User manual

Siemens RLU2 Series User manual

Siemens

Siemens RLU2 Series User manual

Siemens SIMATIC HMI TP700 Comfort User manual

Siemens

Siemens SIMATIC HMI TP700 Comfort User manual

Siemens OZS164 series User manual

Siemens

Siemens OZS164 series User manual

Siemens SIMATIC S7-200 User manual

Siemens

Siemens SIMATIC S7-200 User manual

Siemens SIMATIC S7 User guide

Siemens

Siemens SIMATIC S7 User guide

Siemens BACnet User manual

Siemens

Siemens BACnet User manual

Popular Controllers manuals by other brands

Furious FPV Acrowhoop v2 Quick connect guide

Furious FPV

Furious FPV Acrowhoop v2 Quick connect guide

Emerson Dixell Wing XW570L Installing and operating instructions

Emerson

Emerson Dixell Wing XW570L Installing and operating instructions

m-Dimension D3208 user guide

m-Dimension

m-Dimension D3208 user guide

BWT Manager Connect Duo instruction manual

BWT

BWT Manager Connect Duo instruction manual

PRECISION DIGITAL ProVu PD6310 instruction manual

PRECISION DIGITAL

PRECISION DIGITAL ProVu PD6310 instruction manual

Vive Comfort TP-S-905 Operation manual

Vive Comfort

Vive Comfort TP-S-905 Operation manual

BBE MOVISTROB Series 2100 instruction manual

BBE

BBE MOVISTROB Series 2100 instruction manual

nilan Compact S CTS 602 installation guide

nilan

nilan Compact S CTS 602 installation guide

Naked NKD-pH Installation & start?up guide

Naked

Naked NKD-pH Installation & start?up guide

ccei Phileo VP operating instructions

ccei

ccei Phileo VP operating instructions

Kramer SL-1N quick start guide

Kramer

Kramer SL-1N quick start guide

Regulus UR1 A-DT Installation and operation manual

Regulus

Regulus UR1 A-DT Installation and operation manual

World Uniqueen EN-508 manual

World Uniqueen

World Uniqueen EN-508 manual

Dynamatic 4000 instruction sheet

Dynamatic

Dynamatic 4000 instruction sheet

Lawler 805 Installation & maintenance manual

Lawler

Lawler 805 Installation & maintenance manual

Minco 820B manual

Minco

Minco 820B manual

Paragon EC7000 Series General instructions

Paragon

Paragon EC7000 Series General instructions

PVR sub-zero NANOCHILL NC-110A user manual

PVR

PVR sub-zero NANOCHILL NC-110A user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.