manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. SMC Networks
  6. •
  7. Control Unit
  8. •
  9. SMC Networks 56-VQC4000 Series Manual

SMC Networks 56-VQC4000 Series Manual

56-VV5QC*1-TFL33-D
Installation and Maintenance Manual
5 Port Solenoid Valve
Series 56-VQC1000/2000/4000
ATEX Marking Description
II 3G Ex nA IIB T4..T5 Gc -10ºC Ta+50ºC
II 3D Ex tc IIIC T80..T86°C Dc IP67
Manifold with Serial Transmission System (56-EX500 or 56-EX250)
Refer to separate applicable documentation
Certificate reference: SMC 19.0030 X
For specific conditions of use see section 1.1.
1 Safety Instructions
This manual contains essential information for the protection of users and
others from possible injury and/or equipment damage.
Read this manual before using the product, to ensure correct handling,
and read the manuals of related apparatus before use.
Keep this manual in a safe place for future reference.
These instructions indicate the level of potential hazard by label of
“Caution”, “Warning” or “Danger”, followed by important safety
information which must be carefully followed.
To ensure safety of personnel and equipment the safety instructions in
this manual and the product catalogue must be observed, along with
other relevant safety practices.
Caution
Indicates a hazard with a low level of risk, which if
not avoided, could result in minor or moderate
injury.
Warning
Indicates a hazard with a medium level of risk,
which if not avoided, could result in death or
serious injury.
Danger
Indicates a hazard with a high level of risk, which
if not avoided, will result in death or serious
injury.
The compatibility of pneumatic equipment is the responsibility of the
person who designs the pneumatic system or decides its specifications.
Since the products specified here can be used in various operating
conditions, their compatibility with the specific pneumatic system must
be based on specifications or after analysis and/or tests to meet specific
requirements.
Only trained personnel should operate pneumatically operated
machinery and equipment.
Compressed air can be dangerous if an operator is unfamiliar with it.
Assembly, handling or repair of pneumatic systems should be performed
by trained and experienced personnel.
Do not service machinery/equipment or attempt to remove
components until safety is confirmed.
1) Inspection and maintenance of machinery/equipment should only be
performed after confirmation of safe locked-out control positions.
2) When equipment is to be removed, confirm the safety process as
mentioned above. Switch off air and electrical supplies and exhaust all
residual compressed air in the system.
1 Safety Instructions (continued)
3) Before machinery/equipment is re-started, ensure all safety measures to
prevent sudden movement of cylinders etc. (Supply air into the system
gradually to create back pressure, i.e. incorporate a soft-start valve).
Do not use this product outside of the specifications. Contact SMC
if it is to be used in any of the following conditions:
1) Conditions and environments beyond the given specifications, or if the
product is to be used outdoors.
2) Installations in conjunction with atomic energy, railway, air navigation,
vehicles, medical equipment, food and beverage, recreation equipment,
emergency stop circuits, press applications, or safety equipment.
3) An application which has the possibility of having negative effects on
people, property, or animals, requiring special safety analysis.
1.1 Specific recommendations:
Protect from impacts using an ATEX enclosure suitable for impacts.
Not suitable for Zones 0/20 and Zones 1/21. Only suitable for Zones
2/22.
This product has components made of aluminium alloy. When mounting
this product, it must be installed such that, even in the event of rare
incidents, ignition sources due to impact and friction sparks are excluded.
Do not brush or wipe this product to avoid static charge build up. Static
charge can cause a spark or ignition source.
Ensure that the air supply system is filtered to 5 microns.
2 Specifications
2.1 General Specifications
Series
56-VQC1000, 2000, 4000
Valve configuration
Metal seal
Rubber seal
Fluid
Air/Inert gas
56-VQC1000
56-VQC2000
Maximum operating
pressure
0.7 MPa
Minimum
operating
pressure
Single
0.1 MPa
0.15 MPa
Double
0.1 MPa
3-position
0.1 MPa
0.2 MPa
4-position
-
0.15 MPa
56-
VQC4000
Maximum operating
pressure
1.0 MPa
Minimum
operating
pressure
Single
0.15 MPa
0.2 MPa
Double
0.15 MPa
3-position
0.15 MPa
0.2 MPa
Proof pressure
1.5 MPa
Fluid temperature
-10°C to 50°C
Lubrication
Not required
Manual override
Locking type (tool required)
Locking type (finger/thumb operation)
Slide locking type (56-VQC1000/2000)
Impact/Vibration resistance
150/30 m/s2 (Note 1)
Enclosure
IP67
Rated coil voltage
24VDC
Allowable voltage fluctuation
±10% of rated voltage
Coil insulation
Equivalent to B type
Power consumption (current)
at 24VDC
1W (42mA), inrush (Note 2)
0.35W (15mA), holding
Max operating frequency (Hz)
1
2 Specifications (continued)
Note 1) Impact resistance: There should be no malfunction of the valve
after testing, using a drop impact tester, along the valve axis and
at right-angles to the valve and armature. Carry out each test with
the valve energised and de-energised (Value at the initial stage).
Vibration resistance; There should be no malfunction of the valve
after testing, using a 8.3 to 2000 Hz sweep along the valve axis
and at right-angles to the valve and armature. Carry out each test
with the valve energised and de-energised (Value at the initial
stage).
Note 2) The power saving circuit is included in the manifold.
2.2 Batch codes and Construction month:
Year
Month
2012
2013
2014
…..
2021
2022
2023
…..
Q
R
S
…..
Z
A
B
…..
Jan
o
Qo
Ro
So
…..
Zo
Ao
Bo
…..
Feb
P
QP
RP
SP
…..
ZP
AP
BP
…..
Mar
Q
QQ
RQ
SQ
…..
ZQ
AQ
BQ
…..
Apr
R
QR
RR
SR
…..
ZR
AR
BR
…..
May
S
QS
RS
SS
…..
ZS
AS
BS
…..
Jun
T
QT
RT
ST
…..
ZT
AT
BT
…..
Jul
U
QU
RU
SU
…..
ZU
AU
BU
…..
Aug
V
QV
RV
SV
…..
ZV
AV
BV
…..
Sep
W
QW
RW
SW
…..
ZW
AW
BW
…..
Oct
X
QX
X
SX
…..
ZX
AX
BX
…..
Nov
y
Qy
RQy
Sy
…..
Zy
Ay
By
…..
Dec
Z
QZ
RZ
SZ
…..
ZZ
AZ
BZ
…..
2.3 Piping
56-VQC1000/2000 (M-Kit)
Figure 1
56-VQC1000/2000 (T-Kit)
Figure 2
2 Specifications (continued)
56-VQC1000/2000 (56-EX500)
Figure 3
56-VQC1000/2000 (56-EX250)
Figure 4
56-VQC4000 (M-Kit)
Figure 5
56-VQC4000 (T-Kit)
Figure 6
56-VV5QC*1-TFL33-D
2 Specifications (continued)
56-VQC4000 (56-EX500)
Figure 7
56-VQC4000 (56-EX250)
Figure 8
3 Installation
3.1 Installation
Do not install the product unless the safety instructions have been read
and understood.
Protect from impacts using an ATEX enclosure suitable for impacts.
3.2 Environment
Do not use in an environment where the product is directly exposed to
corrosive gases, chemicals, salt water, water or steam.
Do not use in an explosive atmosphere, except Zone 2/22.
The product should not be exposed to prolonged sunlight. Use a
protective cover.
Do not mount the product in a location where it is subject to excessive
vibrations and/or impacts.
Do not mount the product in a location exposed to radiant heat.
Remove emissive heat.
Employ suitable protective measures in locations where there is contact
with water droplets, oil or welding splatter, etc.
When the solenoid valve is mounted in a control panel or is energised for
a long time, make sure the ambient temperature is within the valve
specification range.
3.3 Piping
Before piping make sure to clean up chips, cutting oil, dust etc.
When installing piping or fittings, ensure sealant material does not enter
inside the port. When using seal tape, leave 1.5 to 2 threads exposed on
the end of the pipe/fitting.
Install piping so that it does not apply pulling, pressing, bending or other
forces on the valve body.
3 Installation (continued)
Tighten fittings to the specified tightening torque shown in Table 1.
Thread
Tightening Torque N•m
M5
By hand + 1/6 turn with a wrench (1/4 turn for miniature fittings)
Rc 1/8
7 to 9
Rc 1/4
12 to 14
Rc 3/8
22 to 24
Rc 1/2
28 to 30
Rc 3/4
28 to 30
Table 1
3.4 Electrical Connection
The manifold has negative common (-COM).
Avoid mis-wiring, as this can cause malfunction, damage and
combustion to the product.
Use voltage that is within ±10% of the rated voltage. Application of
incorrect voltage may cause malfunction or damage.
To prevent noise and surge in signal lines, keep all wiring separate from
power lines and high voltage lines. Otherwise this can cause malfunction.
Use electrical circuits that do not generate chattering in their contacts.
Do not bend or pull cables repeatedly.
Disconnect power supply before removing or making electrical
connections
Multiple connector wiring (M-Kit)
Figure 9
3 Installation (continued)
Terminal block wiring (T-Kit)
Figure 10
3.5 Mounting
Never remove a valve from the manifold when energised.
Never remove terminal box cover when power is connected to the
manifold.
Never disconnect or reconnect cables or connectors when power is
connected to the manifold.
Install 56-VQC valves only.
Install 56-VV5QC manifolds only, as it has an integrated power saving
circuit.
56-VQC1000/2000 Valve mounting:
Figure 11
Removal procedure:
Loosen clamp screws until they turn freely (they do not come out).
Remove the solenoid valve from Clamp B by lifting the coil side of the
valve, while pushing on the screw top.
3 Installation (continued)
Mounting procedure:
Push the clamp screw. Clamp A now opens.
Insert the end plate hook of the valve into Clamp B from an angle.
Push the valve down into place (when the clamp screw is released,
Clamp A will lock).
56-VQC4000 Valve mounting:
Figure 12
Removal procedure:
Loosen mounting screws until they turn freely.
Remove the solenoid valve from Clamp B by lifting the coil side of the
valve first.
Mounting procedure:
Push the coil side of the valve into the connector on the manifold.
Tighten the mounting screws to torque 0.8 to 1.2 N•m.
Ensure all gaskets are present before mounting valves.
Do not let foreign matter stick to gaskets or sealing faces of the valve to
avoid air leaks
3.6 Lubrication
SMC products have been lubricated for life at manufacture, and do not
require lubrication in service.
If a lubricant is used in the system, use turbine oil Class 1 (no additive),
ISO VG32. Once lubricant is used in the system, lubrication must be
continued because the original lubricant applied during manufacturing
will be washed away.
4 Settings
4.1 Manual Override
Since connected equipment will operate when the manual override is
activated, confirm that conditions are safe prior to activation.
Non-locking push type (tool required)
Push down the manual override button with a small screwdriver, etc.
until it stops.
The manual override will return when released.
Figure 13
Slotted locking push type (tool required)
Push down the manual override button with a small flat head screwdriver
until it stops and turn 90° clockwise to lock.
56-VV5QC*1-TFL33-D
4 Settings (continued)
Turn anti-clockwise to release.
Figure 14
Locking type (manual). 56-VQC1000/2000
Push down the manual override button with a small flat head screwdriver
or finger until it stops and turn 90° clockwise to lock.
Turn anti-clockwise to release
Figure 15
Slide locking type (manual). 56-VQC1000/2000
Push down the manual override button with a small flat head screwdriver
or finger until it stops and slide towards the coil to lock.
To unlock, slide the override away from the coil.
Figure 16
5 Circuit Symbols
Figure 17
6 Options
6.1 Mounting
Disconnect power supply before removing or making electrical
connections.
Do not use options other than specified in the 56-VQC catalogues.
The options are standard parts without “56-“ prefix.
Removal and mounting procedure:
Blanking plate assembly, individual SUP spacer and individual EXH
spacer are mounted in the same way as valves. Please refer to section
3.5 Mounting.
6.2 Adding manifold stations (see Figure 18)
When adding manifold stations, ensure the correct number of power
saving units are installed, as operating the valves could exceed the
marked surface temperatures.
1 to 12 solenoids –1 power saving unit required.
13 to 24 solenoids –2 power saving units required.
Install 56-VQC valves only.
Undo the bolts (Item 3) to the tie-rods and remove the U-side end plate
assembly (Item 6). If DIN rail is fitted, first release the DIN rail.
Screw in tie-rod extensions (Item 2) supplied with the manifold block
assembly (standard VQC type) and assemble the manifold block (Item 1).
Re-assemble the U-side end plate assembly (Item 6) and tighten the tie-
rod screws (Item 3) to torque shown in Table 2.
Ensure all seals and gaskets are installed.
Install valve to added manifold block as described in section 3.5
Mounting.
Check the correct number of power saving units (Item 5) are present.
Valve Series
Tightening Torque N•m
56-VQC1000
0.85 to 0,95
56-VQC2000
1,2 to 1,6
56-VQC4000
1,7 to 2,3
Table 2
Figure 18
6.3 Adding power saving unit (Item 5)
If a second power saving unit is required due to exceeding 12 solenoids
on the manifold, contact SMC for the correct part.
The second power saving unit must be positioned next to the D-side end
plate assembly (Item 4).
7 How to Order
Refer to the catalogue for this product.
8 Outline Dimensions
Refer to the catalogue for this product.
9 Maintenance
9.1 General Maintenance
Not following proper maintenance procedures could cause the product to
malfunction and lead to equipment damage.
If handled improperly, compressed air can be dangerous. Maintenance
of pneumatic systems should be performed only by qualified personnel.
Before performing maintenance, turn off the power supply and be sure to
cut off the supply pressure. Confirm that the air is released to
atmosphere.
After installation and maintenance, apply operating pressure and power
to the equipment and perform appropriate functional and leakage tests to
make sure the equipment is installed correctly.
Do not make any modification to the product.
Do not disassemble the product, unless required by installation or
maintenance instructions.
Drain: remove condensate from the filter bowl on regular basis.
Low frequency operation:
Switch valves at least once every 30 days to prevent malfunction. Also,
in order to use it under optimum state, conduct a regular inspection once
every 6 months.
Filters and strainers:
oBe careful regarding clogging of filters and strainers
oReplace filter elements after one year of use, or earlier if the
pressure drop reaches 0.1 MPa.
oClean strainers when the pressure drop reaches 0.1 MPa.
9.2 Replacing One-touch fittings
Cylinder port fittings are available in cassette type and can be replaced
easily.
56-VQC 1000/2000
Remove the valve.
Extract clip with flat head screwdriver.
Pull fitting to remove.
Refitting is the reversal of removal.
Figure 19
Applicable tube O.D.
Fitting assembly part no.
56-VQC1000
56-VQC2000
Ø3.2
VVQ1000-50A-C3
-
Ø4
VVQ1000-50A-C4
VVQ1000-51A-C4
Ø6
VVQ1000-50A-C6
VVQ1000-51A-C6
Ø8
-
VVQ1000-51A-C8
M5
VVQ1000-50A-M5
-
Ø1/8”
VVQ1000-50A-N1
-
Ø5/32”
VVQ1000-50A-N3
VVQ1000-51A-N3
Ø1/4”
VVQ1000-50A-N7
VVQ1000-51A-N7
Ø5/16”
-
VVQ1000-51A-N9
Table 3
9 Maintenance (continued)
56-VQC 4000
Remove the valve.
Extract clip with flat head screwdriver.
Pull fitting to remove.
Refitting is the reversal of removal.
Figure 20
Applicable tube O.D.
Fitting assembly part no.
56-VQC4000
Ø8
VVQ4000-50B-C8
Ø10
VVQ4000-50B-C10
Ø12
VVQ4000-50B-C12
Ø1/4”
VVQ4000-50B-N7
Ø5/16”
VVQ4000-50B-N9
Ø3/8”
VVQ4000-50B-N11
Table 4
10 Limitations of Use
Do not exceed any of the specifications in section 2 of this document or
the specific product catalogue.
10.1 Maintenance space
The installation should allow sufficient space for maintenance activities.
10.2 Ambient environment
Use within the allowable ambient temperature range.
10.3 Mounting orientation
In the case of a single solenoid, the mounting orientation is unrestricted.
In the case of double solenoid or 3 position valves, mount so the spool is
horizontal.
When mounting for an application that will involve vibration or impact,
mount so the spool is at right angles to the direction of vibration.
Do not use in applications where vibration or impact exceed the products
specification.
11 Contacts
Refer to Declaration of Conformity and www.smcworld.com for contacts.
URL :
http// www.smcworld.com (Global) http// www.smceu.com (Europe)
'SMC Corporation, Akihabara UDX15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo
101 0021
Specifications are subject to change without prior notice from the manufacturer.
© 2019 SMC Corporation All Rights Reserved.
Template DKP50047-F-085H

This manual suits for next models

9

Other SMC Networks Control Unit manuals

SMC Networks XGTP31 50336 Series User manual

SMC Networks

SMC Networks XGTP31 50336 Series User manual

SMC Networks EX430-SIL1 User manual

SMC Networks

SMC Networks EX430-SIL1 User manual

SMC Networks SYJ300 Manual

SMC Networks

SMC Networks SYJ300 Manual

SMC Networks VP4 Series User manual

SMC Networks

SMC Networks VP4 Series User manual

SMC Networks EX260 Series User manual

SMC Networks

SMC Networks EX260 Series User manual

SMC Networks IL201 Series User manual

SMC Networks

SMC Networks IL201 Series User manual

SMC Networks VTA301 Series User manual

SMC Networks

SMC Networks VTA301 Series User manual

SMC Networks S0700 Manual

SMC Networks

SMC Networks S0700 Manual

SMC Networks VFR6000 Series User manual

SMC Networks

SMC Networks VFR6000 Series User manual

SMC Networks VV100 Series User manual

SMC Networks

SMC Networks VV100 Series User manual

SMC Networks VP 46 Series User manual

SMC Networks

SMC Networks VP 46 Series User manual

SMC Networks VQ100 Series Manual

SMC Networks

SMC Networks VQ100 Series Manual

SMC Networks ProtoCessor FPC-ED2 User guide

SMC Networks

SMC Networks ProtoCessor FPC-ED2 User guide

SMC Networks VHS20 Series User manual

SMC Networks

SMC Networks VHS20 Series User manual

SMC Networks MPCXX-XXX-XXX-XX-DUT01607 User manual

SMC Networks

SMC Networks MPCXX-XXX-XXX-XX-DUT01607 User manual

SMC Networks VQC1000 User manual

SMC Networks

SMC Networks VQC1000 User manual

SMC Networks 56-VQC1000 Series Manual

SMC Networks

SMC Networks 56-VQC1000 Series Manual

SMC Networks IBV1 Series User manual

SMC Networks

SMC Networks IBV1 Series User manual

SMC Networks VM400 Series User manual

SMC Networks

SMC Networks VM400 Series User manual

SMC Networks VP31 5 Series User manual

SMC Networks

SMC Networks VP31 5 Series User manual

SMC Networks VXS23 Manual

SMC Networks

SMC Networks VXS23 Manual

SMC Networks JSXFA Series User manual

SMC Networks

SMC Networks JSXFA Series User manual

SMC Networks VHS20-D Series User manual

SMC Networks

SMC Networks VHS20-D Series User manual

SMC Networks VP500 Series User manual

SMC Networks

SMC Networks VP500 Series User manual

Popular Control Unit manuals by other brands

Terra UC380 user manual

Terra

Terra UC380 user manual

Lenze E94AZHY0025 Mounting instructions

Lenze

Lenze E94AZHY0025 Mounting instructions

Definox DPX1EBC Maintenance notice

Definox

Definox DPX1EBC Maintenance notice

LSI MegaRAID LSIiBBU01 Quick installation guide

LSI

LSI MegaRAID LSIiBBU01 Quick installation guide

Compac OPT SCR200 installation manual

Compac

Compac OPT SCR200 installation manual

Arduino HM-11 user manual

Arduino

Arduino HM-11 user manual

schmersal SRB 304ST operating instructions

schmersal

schmersal SRB 304ST operating instructions

DAZE Dynamic Power Manager installation manual

DAZE

DAZE Dynamic Power Manager installation manual

Zamel EXTA EDM-01 instruction manual

Zamel

Zamel EXTA EDM-01 instruction manual

SpeedTurtle Easy Flash Module 3.0 user manual

SpeedTurtle

SpeedTurtle Easy Flash Module 3.0 user manual

entegris NT 6300 user guide

entegris

entegris NT 6300 user guide

Franklin Wireless S600 manual

Franklin Wireless

Franklin Wireless S600 manual

Baldwin Boxall BT10 operating instructions

Baldwin Boxall

Baldwin Boxall BT10 operating instructions

Emerson ALCO Thermo TX6 installation instructions

Emerson

Emerson ALCO Thermo TX6 installation instructions

Marvell Avastar SP88W8782-MA0 user guide

Marvell

Marvell Avastar SP88W8782-MA0 user guide

DOLD SAFEMASTER PRO UG 6951 user manual

DOLD

DOLD SAFEMASTER PRO UG 6951 user manual

Dataton SMARTPAX QC Product Sheets

Dataton

Dataton SMARTPAX QC Product Sheets

Valmet Flowrox PVEG Installation, operation and maintenance instructions

Valmet

Valmet Flowrox PVEG Installation, operation and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.