1 Function
1.1 The alerter is intended for light and sound alerting about
current status of an object equipped with a control panel of a
fire/intrusion detection and alarming system.
1.2 The alerter is designed for continuous 24-hours operation.
1.3 Power supply of the alerter is performed by 12V
3
2
DC.
1.4 The alerter generates 4 types of alerting signals:
–LED indicators are ON;
–LED indicators are OFF;
–Piezoelectric acoustic emiter is ON;
–Piezoelectric acoustic emiter is OFF;
by means of voltage supply through control panel output relay
contacts or through open collector outputs.
1.5 The alerter is not considered to be a source of interference as
regards similar devices, alerters of other types and purposes, as
well as regards domestic radio equipment.
2 Specifications
Contrast perception of light signal
against ambient light background, Lx, min.................................. 500
Acoustic pressure level at 1m distance, dB .................................. 95
Generated signal frequency, kHz, min............................................ 3
Light signal viewing angle,° ........................................................ 180
Supply voltage, V......................................................... from 10 to 15
Current consumption, mA, max:
Light channel ................................................................................ 50
Sound channel............................................................................ 100
Overall dimensions, mm ................................diameter 90, height 31
Weight, kg.................................................................................. 0,08
Operating Conditions
Temperature range, °C ........................................from -30 up to +55
Relative air humidity, %....................................... up to 93 at +40 °С
without moisture condensation
3 Delivery Set
Light Alerter Astra-10 ver.3.......................................................1 pcs
Screw 2-3x30............................................................................2 pcs
Dowel 5x25...............................................................................2 pcs
User Instruction.......................................................................1 copy
4 Structure
The alerter consists of a base, printed circuit board (PCB) with
radioelements, and removable cover (Figure 1).
Alerter’s design provides for possibility of installation on a wall sur-
face.
Figure 1
5 Installation and Pre-Starting Procedures
5.1 Works on installation, mounting, maintenance and operation
of the alerter should be performed by qualified persons only.
5.2 After transportation in conditions differing from those of op-
eration keep the alerter packed under supposed operation condi-
tions for at least 4 hours.
5.3 Installation Place
- Installation on a wall surface is allowed;
- Installation place should avoid exposure to sunlight;
- Inside permanent structures the preferable places of installation
are those well viewed from outside;
5.4 Installation Procedure:
5.4.1 Remove the cover by turning it counterclockwise with
respect to the base;
5.4.2 Make marking on installation surface by applying the
base;
5.4.3 Lead wires from power supply source through the wire
insertion holes on the base (see Figure 1); Squeeze an additional
wire insertion hole on the base if necessary.
5.4.4 Fix alerter’s base on the wall;
5.4.5 Connect power supply source’s wires to the appropriate
screw terminals in accordance with selected connection diagram
(see Figure 2):
Figure 2

10-3_v3_10_en
2
5.4.6 Wiring options:
- when connecting to control panel Astra-812 or Astra-812M –
see Figure 3;
- when connecting to control panel Astra-712/x –see Figure 4;
Figure 3
Figure 4
5.4.7 Seal hermetically the wire insertion hole to protect the alerter
from ingress of dust and insects
5.4.8 Re-install the cover:
–align cover’s ledges with base’s slots;
–clasp the cover to the base;
–turn the cover clockwise until it stops (until it clicks).
6 Maintenance
To provide failsafe operating of an alarm system, do the mainten-
ance works at least one time per 6 months.
Maintenance of the alerter includes the following works:
–Inspection of alerter’s housing integrity;
–Inspection of reliability of alerter’s fixation on installation sur-
face;
–Inspection of reliability of wire connections;
–Cleaning from contaminants;
–Inspection of alerter’s operability by connecting it to a power
supply source. LEDs should light on with equal brightness, em-
bedded piezoelectric acoustic emitter should issue sound sig-
nals.
7 Labeling
On a label attached to the housing of the alerter are:
–manufacturer’s trademark;
–abbreviated name of the alerter;
–firmware version;
–month (the first three letters) and year (the last two digits) of manu-
facture;
–conformity mark (if certificate is available);
–bar-code duplicating the textual information.
8 EC Conformity Declarations
This product is in conformity with the provisions of:
EMC 89/336/EEC
EN 61000-6-3:2005 Electromagnetic compatibility (EMC) - Part 6-3: Ge-
neric standards - Emission standard for residential, commercial and light-
industrial environments
EN 50130-4/1995 + A1:1998 + A2:2003 + Corrig. 2003 Alarm systems -
Part 4: Electromagnetic compatibility - Product family standard: Immunity
requirements for components of fire, intruder and social alarm systems
EN 60950-1: 2001+A11:2004+Corrig.2004 Safety of information technol-
ogy equipment
9 Recycling
The alerter is not dangerous for life and health of people and is safe for
environment. On expiry of service life it should be recycled without spe-
cial environment protective measures.
10 Warranty
10.1 Quality Management System meets provisions of ISO 9001-2011.
10.2 The manufacturer guarantees compliance of the alerter with the
technical requirements provided the customer observes the standards of
operation, transportation, storage and installation of the device.
10.3 The storage warranty period is 2 years and 6 months from the date
of manufacture.
10.4 The operation warranty time is 2 years from the date of operation
startup but not longer than 2 years 6 months from the date of manufac-
ture.
10.5 The manufacturer commits to replace or repair the product during
the warranty period.
10.6 The warranty does not come into effect in following cases:
-in case of non-observance of this operation manual;
-mechanical damage of the product;
-repair of the alerter by any other party except the manufacturer.
10.7 This warranty applies to the alerter only, not to equipment of third
part manufacturers used jointly with the detector.
User should keep in mind that correctly installed signalling system serves
to decrease the risk of such events as larceny, robbery or fire, but not to
avoid them at all.
The manufacturer bear no responsibility for death, injury, damage of
property or any other kinds of accidental or premeditated damages,
based on user’s statement that the device failed to implement its
function.
Sales:
Controlex GmbH
Warranty service and
technical support:
ТЕКО-TD
Philosophenweg 31-33
47051 Duisburg, Germany
Phone: +49 (0) 203 / 393 91 188
Fax: +49 (0) 203 / 393 91 189
GSM: +49 (0) 178 / 218 48 22
E-mail: info@controlex.eu
Web: www.controlex.eu
Prospekt Pobedy str. 19
420138 Kazan, Russia
Phone: +7 (843) 261-55-75
Fax: +7 (843) 261-58-08
E-mail: info@teko.biz
support@teko.biz
Web: www.teko.biz
Made in Russia
Table of contents
Other teko Security System manuals

teko
teko Astra-322 User manual

teko
teko Astra-Z-6145 User manual

teko
teko Astra-10 ver.3 User manual

teko
teko Astra-R User manual

teko
teko Astra-R Installation manual

teko
teko Astra-321 User manual

teko
teko Astra-10 Ver.2 Installation instructions

teko
teko Astra-321 User manual

teko
teko Astra-4511 User manual
Popular Security System manuals by other brands

Soundoff Signal
Soundoff Signal Armada A200 manual

brennenstuhl
brennenstuhl BrematicPRO WM868 01 Instructions for use

Critical Environment Technologies
Critical Environment Technologies AST-IS14 manual

Lorex
Lorex SG4230 instruction manual

DSC
DSC PC 2500 installation manual

Siemens
Siemens FDM221 Technical manual