ABB VD4 12.06.16 p150 Quick guide

VD4
Installation and service instructions
12 ... 24 kV - 630 ... 2500 A - 16 ... 31.5 kA
All manuals and user guides at all-guides.com
all-guides.com

All manuals and user guides at all-guides.com

1
For your safety!
Make sure that the installation room (spaces, divisions and ambi-
ent) is suitable for the electrical apparatus.
Checkthatalltheinstallation,puttingintoserviceandmaintenance
operations are carried out by personnel with suitable knowledge
of the apparatus.
Make sure that the standard and legal prescriptions are complied
with during installation, putting into service and maintenance, so
that installations according to the rules of good working practice
and safety in the work place are constructed.
Strictly follow the information given in this instruction manual.
Check that the rated performance of the apparatus is not exceeded
during service.
Checkthatthepersonneloperatingtheapparatushavethisinstruc-
tion manual to hand as well as the necessary information for cor-
rectintervention.
Pay special attention to the danger notes indicated in the manual
by the following symbol:
Responsible behaviour
safeguards your own and others’ safety!
For any requests, please contact the
ABB Assistance Service.
!
All manuals and user guides at all-guides.com

2
Index
I. Introduction 3
II. Programmeforenvironmental protection 3
1. Packing and transport 4
2. Checking on receipt 4
3. Storage 4
4. Handling 5
5. Description 6
5.1.Generalinformation 6
5.2. ReferenceStandards 6
5.3.Fixed circuit-breaker 6
5.4. Withdrawablecircuit-breaker 10
5.5. Characteristics of the electrical accessories 18
6. Instructionsforcircuit-breaker operation 19
6.1. Safety indications 19
6.2. Operating and signalling parts 19
6.3.Circuit-breakerclosing and opening operations 20
7. Installation 21
7.1. General 21
7.2. Installation and operating conditions 21
7.3. Preliminaryoperations 24
7.4. Installation of fixed circuit-breaker 24
7.5. Installationof withdrawablecircuit-breaker 24
7.6. Power circuit connection of fixed circuit-breaker 25
7.7. Earthing 26
7.8. Connection of the auxiliary circuits 26
7.9.Overall dimensions 29
Fixedcircuit-breakers 29
Withdrawablecircuit-breakers for UniGeartype ZS1 andUniSafe switchgear 33
8. Putting into service 37
8.1.Generalprocedures 37
9. Maintenance 39
9.1. General 39
9.2. Inspection and functional testing 39
9.3. Servicing 40
9.4. Repairs 41
10. Application of the standards for X-ray emission 42
11. Spare parts and accessories 42
11.1. List of spare parts 42
All manuals and user guides at all-guides.com

3
I. Introduction
This publication contains the information needed to install medium voltage VD4 circuit-breakers
and put them into service.
For correct use of the product, please read it carefully.
Like all the apparatus we manufacture, the VD4 circuit-breakers are designed for different installa-
tion configurations.
However, these pieces of apparatus do allow further technical and construction modifications (at
the customer’s request) to adapt to special installation requirements.
Consequently, the information given below may sometimes not contain instructions concerning
special configurations.
Apartfromthis manual, it isthereforealwaysnecessary to consult thelatesttechnicaldocumentation
(circuitandwiringdiagrams,assemblyandinstallationdrawings,anyprotectioncoordinationstudies,
etc.), especially regarding any variants requested in relation to the standardised configurations.
Only use original spare parts for maintenance operations.
Forfurther information, please alsosee the technicalcatalogueof the circuit-breakerandthe spare
parts catalogue.
All the installation, putting into service, running and maintenance operations must be
carried out by suitably qualified personnel with in-depth knowledge of the apparatus.
II. Environmental protection programme
The VD4 circuit-breakers are manufactured in accordance with the ISO 14000 Standards (Guide-
linesforenvironmental management).
The production processes are carried out in compliance with the Standards for environmental pro-
tection in terms of reduction in energy consumption as well as in raw materials and production of
waste materials. All this is thanks to the medium voltage apparatus manufacturing facility environ-
mental management system.
!
All manuals and user guides at all-guides.com

4
Caption
A Circuit-breaker rating
plate.
B Operating mechanism
rating plate.
1 Type of apparatus.
2 Symbols of compliance
with Standards.
3 Serial number.
4 Circuit-breaker charac-
teristics.
5 Characteristics of the
operating mechanism
auxiliaries.
Should any damage or irregularity be noted in
the supply on unpacking, notify ABB (directly or
through the agent or supplier) as soon as possi-
ble and in any case within five days of receipt.
The apparatus is only supplied with the acces-
sories specified at the time of ordering and vali-
dated in the order confirmation sent by ABB.
The accompanying documents inserted in the
shippingpacking are:
– instruction manual (this document)
– test certification
– identificationlabel
– copy of the shipping document
– electricwiring diagram.
Other documents which are sent prior to ship-
ment of the apparatus are:
– orderconfirmation
– original shipping advice notes
– any drawings or documents referring to spe-
cial configurations/conditions.
3. Storage
When a period of storage is foreseen, our work-
shopscan(on request) providesuitablepacking
for the specified storage conditions.
On receipt the apparatus must be carefully un-
packed and checked as described in Checking
on receipt (chap. 2).
If immediate installation is not possible, the
packing must be replaced, using the original
materialsupplied.
Insert hygroscopic packets inside the packing,
with at least one standard packet for piece of
apparatus.
Shouldthe original packingnotbe available and
immediate installation is not possible, store in a
covered,well-ventilated,dry, dust-free, non-cor-
rosiveambient,away from any flammablemate-
rials and at a temperature between –5 °C and
+45 °C.
In any case, avoid any accidental impacts or
positioning which stresses the structure of the
apparatus.
Fig.1
1. Packing and transport
The circuit-breaker is shipped in special pack-
ing, in the open position and with the springs
discharged.
Each piece of apparatus is protected by a plas-
tic cover to prevent any infiltration of water dur-
ingtheloadingandunloadingstagesandtokeep
the dust off during storage.
2. Checking on receipt
Before carrying out any operation, al-
ways make sure that the operating
mechanism springs are discharged
and that the apparatus is in the open
position.
On receipt, check the state of the apparatus,
integrityofthepackingandcorrespondence with
thenameplatedata(seefig.1)withwhatisspeci-
fied in the order confirmation and in the accom-
panyingshipping note.
Also make sure that all the materials described
in the shipping note are included in the supply.
CIRCUIT-BREAKER IEC62271-100
VD4 ... CEI 17-1
NO. ... MASSE ... kg
RATEDVOLTAGE ... kV
IMPULSEWITHSTANDVOLTAGEATM. ... kV
RATEDFREQUENCY 50/60Hz
RATEDNORMALCURRENT ... A
SHORT-TIMECURRENT (...s) ... kA
CLOSING / OPENING TIME ... ms
BREAKINGCAPACITY ... kA
MAKINGCAPACITY ... kA
AT A VOLTAGE OF ... kV
OPERATIONSEQUENCE O-0,3s-CO-3Min-CO
OPERATINGMECHANISM IEC 62271-100
EL ... CEI 17-1
NO. ...
–MO ... V ...
–MO1 ... V ...
– MS ... V ...
Designed and manufactured by ABB
1
A
B
3
4
5
2
!
All manuals and user guides at all-guides.com
all-guides.com

5
C B A
123
3
4. Handling
Beforecarryingoutanyoperations,alwaysmake
sure that the operating mechanism springs are
dischargedandthat the apparatusisinthe open
position.
Toliftand handle thecircuit-breaker,proceed as
follows (fig. 2):
– use a special lifting tool (1) (not supplied) fit-
ted with ropes with safety hooks (2);
– insert the hooks (2) in the supports (3) fixed to
theframeof the circuit-breakerandlift.Put the
hooks (2) into the support holes (3) according
to the type of apparatus (see table);
– oncompletionoftheoperation(and in anycase
before putting into service) unhook the lifting
tool (1) and dismantle the supports (3) from
the frame.
Fig.2
Version Pole centre distance Rated current Hole
Fixed 150-210 mm up to 1250 A A
Fixed 275 mm from 1600 to 2500 A A
Fixed 210 mm from 1600 to 2000 A A
Withdrawable 150 mm up to 1250 A A
Withdrawable 210 mm from 1600 to 2500 A B
Withdrawable 275 mm up to 1250 A B
Withdrawable 275 mm from 1600 to 2500 A C
Withdrawable 210 mm up to 1250 A C
During handling, take great care not to stress
the insulating parts and the terminals of the cir-
cuit-breaker.
The apparatus must not be handled by
puttingliftingdevicesdirectly underthe
apparatusitself.Shoulditbe necessary
to use this technique, put the circuit-
breaker onto a pallet or a sturdy sup-
porting surface (see fig. 3).
In any case, it is always advisable to
carry out lifting using the supports (3).
Fig.3
!
All manuals and user guides at all-guides.com

6
5.2. Reference Standards
The VD4 circuit-breakers conform with the IEC
62271-100, DIN VDE 0670, CEI 17-1 file 1375
Standardsandthoseofmajorindustrialisedcoun-
tries.
5.3. Fixed circuit-breaker
The fixed circuit-breaker (fig. 4) is the basic ver-
sioncompletewith structure andfrontprotection
screen. The fixing holes are made in the lower
part of the structure.
For the electrical connections of the circuit-
breaker auxiliary circuits, the terminal box (10)
is available (also see par. 7.8.1.).
The earthing screw is placed in the rear part of
thecircuit-breaker.Forfurtherdetails,pleasesee
the caption to figure 4.
5. Description
5.1. General
The VD4 series of circuit-breakers are pieces of
apparatus under vacuum for indoor installation;
for the electrical performances, please refer to
the corresponding technical catalogue code
1VCP000001.
Forspecialinstallationrequirements,pleasecon-
tact ABB.
The following versions are available:
– fixed
– withdrawableforUniGearZS1typeandUniSafe
switchgear.
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated symmetrical short-
circuit current)
Rated short-time
withstand current (3 s)
Making capacity
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
Maximum overall dimensions
Pole centre distance
Standardised table of dimensions
Operating temperature
Tropicalisation
Electromagnetic compatibility
5.3.1. General characteristics of fixed circuit-breakers
IEC62271-100
CEI 17-1 (File 1375)
Ur [kV]
Us [kV]
Ud (1 min) [kV]
Up [kV]
fr [Hz]
Ir [A]
Isc [kA]
Ik [kA]
Ip [kA]
[O-0,3s-CO-3min-CO]
[ms]
[ms]
[ms]
[ms]
H[mm]
W[mm]
D[mm]
I[mm]
[°C]
IEC:60068-2-30
721-2-1
IEC: 60694, 61000-6-2
61000-6-4
VD4 12
12
12
28
75
50-60
630 630 1250 1250 1600 1600 2000 2000 2500
16 16 16 16 – – – – –
20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
16 16 16 16 – – – – –
20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 – – – – –
50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80
40 ... 60
10 ... 15
50 ... 75
60 ... 80
461 461 461 461 599 599 599 599 616
450 570 450 570 570 700 570 700 700
424 424 424 424 424 424 424 424 424
150 210 150 210 210 275 210 275 275
TN7405 TN7406 TN7405 TN7406 TN7407 TN7408 TN7407 TN7408 TN7408
– 5 ... + 40
All manuals and user guides at all-guides.com

7
1
2
3
4
5
6
7
9
8
11 11 10
Caption
1 Lever for manual closing spring charging
2 Signalling device for circuit-breaker open/closed
3 Rating plate
4 Opening pushbutton
5 Closing pushbutton
Fig.4
6 Signallingdevice forclosingsprings charged/discharged
7 Operation counter
8 Terminals
9 Earthing screw
10 Delivery terminal box
11 Cabling connection
VD4 17
17.5
17.5
38
95
50-60
630 630 1250 1250 1600 1600 2000 2000 2500
16 16 16 16 – – – – –
20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
16 16 16 16 – – – – –
20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 – – – – –
50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80
40 ... 60
10 ... 15
50 ... 75
60 ... 80
461 461 461 461 599 599 599 599 616
450 570 450 570 570 700 570 700 700
424 424 424 424 424 424 424 424 424
150 210 150 210 210 275 210 275 275
TN7405 TN7406 TN7405 TN7406 TN7407 TN7408 TN7407 TN7408 TN7408
– 5 ... + 40
VD4 24
24
24
50
125
50-60
630 630 1250 1250 1600 2000 2500
16 16 16 16 16 16 –
20 20 20 20 20 20 –
25 25 25 25 25 25 25
–––––––
16 16 16 16 16 16 –
20 20 20 20 20 20 –
25 25 25 25 25 25 25
–––––––
40 40 40 40 40 40 –
50 50 50 50 50 50 –
63 63 63 63 63 63
–––––––
40 ... 60
10 ... 15
50 ... 75
60 ... 80
631 631 631 631 642 642 661
570 700 570 700 700 700 700
424 424 424 424 424 424 424
210 275 210 275 275 275 275
TN7409 TN7410 TN7409 TN7410 TN7411 TN7411 TN7411
– 5 ... + 40
All manuals and user guides at all-guides.com

8
5.3.2. Types of circuit-breakers available in the fixed version
24
VD4 fixed circuit-breaker without bottom and top terminals
17,5
12
Notes
H = Height of the circuit-
breaker.
W = Width of the circuit-
breaker.
D = Depth of the circuit-
breaker.
u/l= Distance between bot-
tom and top terminal.
l/g= Distance between the
bottom terminal and
the resting surface of
the circuit-breaker.
I = Pole horizontal centre
distance.
Ur Isc Rated uninterrupted current (40°C) [A]
kV kA H = 461 H = 599 H = 616 H = 631 H = 642 H = 661 Circuit-breakertype
D = 424 D = 424 D = 424 D = 424 D = 424 D = 424
u/l=205 u/l=310 u/l=310 u/l= 310 u/l = 310 u/l=310
l/g=217.5 l/g=237.5 l/g=237.5 l/g=282.5 l/g=282.5 l/g=282.5
I = 150 I = 210 I = 210 I = 275 I = 275 I = 210 I = 275 I = 275 I = 275
W = 450 W = 570 W = 570 W = 700 W = 700 W = 570 W = 700 W = 700 W = 700
16 630 VD4 12.06.16 p150
20 630 VD4 12.06.20 p150
25 630 VD4 12.06.25 p150
31.5 630 VD4 12.06.32 p150
16 1250 VD4 12.12.16 p150
20 1250 VD4 12.12.20 p150
25 1250 VD4 12.12.25 p150
31.5 1250 VD4 12.12.32 p150
16 630 VD4 12.06.16 p210
20 630 VD4 12.06.20 p210
25 630 VD4 12.06.25 p210
31.5 630 VD4 12.06.32 p210
16 1250 VD4 12.12.16 p210
20 1250 VD4 12.12.20 p210
25 1250 VD4 12.12.25 p210
31.5 1250 VD4 12.12.32 p210
20 1600 VD4 12.16.20 p210
25 1600 VD4 12.16.25 p210
31.5 1600 VD4 12.16.32 p210
20 2000 VD4 12.20.20 p210
25 2000 VD4 12.20.25 p210
31.5 2000 VD4 12.20.32 p210
20 1600 VD4 12.16.20 p275
25 1600 VD4 12.16.25 p275
31.5 1600 VD4 12.16.32 p275
20 2000 VD4 12.20.20 p275
25 2000 VD4 12.20.25 p275
31.5 2000 VD4 12.20.32 p275
20 2500 VD4 12.25.20 p275
25 2500 VD4 12.25.25 p275
31.5 2500 VD4 12.25.32 p275
16 630 VD4 17.06.16 p150
20 630 VD4 17.06.20 p150
25 630 VD4 17.06.25 p150
31.5 630 VD4 17.06.32 p150
16 1250 VD4 17.12.16 p150
20 1250 VD4 17.12.20 p150
25 1250 VD4 17.12.25 p150
31.5 1250 VD4 17.12.32 p150
16 630 VD4 17.06.16 p210
20 630 VD4 17.06.20 p210
25 630 VD4 17.06.25 p210
31.5 630 VD4 17.06.32 p210
16 1250 VD4 17.12.16 p210
20 1250 VD4 17.12.20 p210
25 1250 VD4 17.12.25 p210
31.5 1250 VD4 17.12.32 p210
20 1600 VD4 17.16.20 p210
25 1600 VD4 17.16.25 p210
31.5 1600 VD4 17.16.32 p210
20 2000 VD4 17.20.20 p210
25 2000 VD4 17.20.25 p210
31.5 2000 VD4 17.20.32 p210
20 1600 VD4 17.16.20 p275
25 1600 VD4 17.16.25 p275
31.5 1600 VD4 17.16.32 p275
20 2000 VD4 17.20.20 p275
25 2000 VD4 17.20.25 p275
31.5 2000 VD4 17.20.32 p275
20 2500 VD4 17.25.20 p275
25 2500 VD4 17.25.25 p275
31.5 2500 VD4 17.25.32 p275
16 630 VD4 24.06.16 p210
20 630 VD4 24.06.20 p210
25 630 VD4 24.06.25 p210
16 1250 VD4 24.12.16 p210
20 1250 VD4 24.12.20 p210
25 1250 VD4 24.12.25 p210
16 630 VD4 24.06.16 p275
20 630 VD4 24.06.20 p275
25 630 VD4 24.06.25 p275
16 1250 VD4 24.12.16 p275
20 1250 VD4 24.12.20 p275
25 1250 VD4 24.12.25 p275
16 1600 VD4 24.16.16 p275
20 1600 VD4 24.16.20 p275
25 1600 VD4 24.16.25 p275
16 2000 VD4 24.20.16 p275
20 2000 VD4 24.20.20 p275
25 2000 VD4 24.20.25 p275
25 2500 VD4 24.25.25 p275
All manuals and user guides at all-guides.com

9
5.3.3. Standard fittings for fixed circuit-breakers
The basic versions of the fixed circuit-breakers are three-pole and fitted
with:
– EL type manual operating mechanism
– mechanical signalling device for closing springs charged/discharged
– mechanical signalling device for circuit-breaker open/closed
– closingpushbutton
– openingpushbutton
– operationcounter
– set of ten circuit-breaker open/closed auxiliary contacts.
Note
With the group of ten auxiliary contacts, as standard, and the maximum of the
requested applications, the following are available: three opening contacts
(signalling circuit-breaker open) and five closing contacts (signalling circuit-
breaker closed).
– lever for manual closing spring charging
– auxiliary circuit support terminal box.
All manuals and user guides at all-guides.com
all-guides.com

10
5.4. Withdrawable circuit-breaker
Thewithdrawablecircuit-breakers(seefig.5)are
available for UniGear type ZS1 and UniSafe
switchgear.
They consist of a truck on which the supporting
structure of the circuit-breaker is fixed.
The cord with the connector (14) (plug) for con-
nection of the operating mechanism electrical
accessories comes out of the connection (15).
The strikers for operating the contacts
(connected/isolated) located in the switchgear
are fixed in the top part of the circuit-breaker.
The slides (9) for operating the segregation
shutters of the medium voltage contacts of the
switchgear enclosure are fixed on the sides of
thecircuit-breaker.
On the front part of the circuit-breaker truck, the
crosspiece is mounted with the handles (12) for
hookingup the circuit-breakerforthe racking-in/
out operations by means of the special operat-
ing lever (16). The circuit-breaker is completed
with the isolating contacts (8).
(1) Rated uninterrupted
currents guaranteed
with withdrawable cir-
cuit-breakers installed
in UniGear ZS1 type
switchgear with air tem-
perature of 40 °C.
(2) The rated uninterrupted
current of 2300 A is
guaranteed with natural
ventilation.
The rated uninterrupted
current of 2500 A is
guaranteed with forced
ventilation.
5.4.1.Generalcharacteristicsof withdrawablecircuit-breakersforUniGear ZS1typeswitchgear
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated symmetrical
short-circuit current)
Rated short-time
withstand current (3 s)
Making capacity
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
Maximum overall dimensions
Pole centre distance
Standardised table of dimensions
Operating temperature
Tropicalisation
Electromagnetic compatibility
The withdrawable circuit-breaker is fitted with
special locks on the front crosspiece, which al-
lowhookingupinto the correspondingcouplings
of the switchgear.
The locks can only be activated by the handles
withthetruckfullyrestingagainstthecrosspiece.
The operating lever (16) must be fully inserted
(also see par. 7.5.). A lock prevents the truck
from advancing into the enclosure or fixed part
whenthe earthing switchisclosed.Anotherlock
prevents racking-in and racking-out with the cir-
cuit-breakerclosed.With the truck inaninterme-
diate position between isolated and connected,
a further lock prevents circuit-breaker closing
(either mechanical or electrical).
A locking magnet is also mounted on the truck
which, when de-energised, prevents the truck
racking-inoperation.
On request, an interlock is also available which
preventsracking-inofthecircuit-breakerwiththe
door open, and door opening with the circuit-
breakerclosed.
Ur [kV]
Us [kV]
Ud (1 min) [kV]
Up [kV]
fr [Hz]
(1) Ir [A]
Isc [kA]
Ik [kA]
Ip [kA]
[O-0,3s-CO-3min-CO]
[ms]
[ms]
[ms]
[ms]
H[mm]
W[mm]
D[mm]
I[mm]
[°C]
VD4/P 12
IEC 62271-100; CEI 17-1 (File 1375)
12
12
28
75
50-60
630 1250 1600 1600 2000 2000 2500
1616–––––
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
1616–––––
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
4040–––––
50 50 50 50 50 50 50
63 63 63 63 63 63 63
80 80 80 80 80 80 80
40 ... 60
10 ... 15
50 ... 75
60 ... 80
632 632 690 690 690 690 690
503 503 653 853 653 853 853
664 664 642 642 642 642 642
150 150 210 275 210 275 275
TN7412 TN7412 TN7415 TN7416 TN7415 TN7416 TN7417
– 5 ... + 40
IEC:60068-2-30;721-2-1
IEC: 60694, 61000-6-2; 61000-6-4
All manuals and user guides at all-guides.com

11
14
4
5
6
7
12 8
13
9
10
1
11
2
3
16
15
Caption
1 Lever for manually charging the closing
springs
2 Signalling device for circuit-breaker open/
closed
3 Rating plate
4 Opening pushbutton
Fig.5
VD4/P 17
IEC 62271-100; CEI 17-1 (File 1375)
17.5
17.5
38
95
50-60
630 1250 1600 1600 2000 2000 2500
1616–––––
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
1616–––––
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
4040–––––
50 50 50 50 50 50 50
63 63 63 63 63 63 63
80 80 80 80 80 80 80
40 ... 60
10 ... 15
50 ... 75
60 ... 80
632 632 690 690 690 690 690
503 503 653 853 653 853 853
664 664 642 642 642 642 642
150 150 210 275 210 275 275
TN7412 TN7412 TN7415 TN7416 TN7415 TN7416 TN7417
– 5 ... + 40
IEC:60068-2-30;721-2-1
IEC: 60694, 61000-6-2; 61000-6-4
VD4/P 24
IEC 62271-100; CEI 17-1 (File 1375)
24
24
50
125
50-60
630 630 1250 1250 1600 2000 2500 (2)
16 16 16 16 16 16 16
20 20 20 20 20 20 20
25 25 25 25 25 25 25
–––––––
16 16 16 16 16 16 16
20 20 20 20 20 20 20
25 25 25 25 25 25 25
–––––––
40 40 40 40 40 40 40
50 50 50 50 50 50 50
63 63 63 63 63 63 63
–––––––
40 ... 60
10 ... 15
50 ... 75
60 ... 80
794 794 794 794 838 838 838
653 853 653 853 853 853 853
802 802 802 802 790 790 790
210 275 210 275 275 275 275
TN7413 TN7414 TN7413 TN7414 TN7418 TN7418 TN7418
– 5 ... + 40
IEC:60068-2-30;721-2-1
IEC: 60694, 61000-6-2; 61000-6-4
5 Closing pushbutton
6 Signalling device for closing springs charged/
discharged
7 Operation counter
8 Isolating contacts
9 Slide for operating the switchgear shutters
10 Truck
11 Locks for hooking into the fixed part
12 Handles for activating the locks (11)
13 Strikers for activating the contacts placed in
the enclosure
14 Connector (plug)
15 Cabling connection
16 Operating lever of circuit-breaker racking-
in/out
All manuals and user guides at all-guides.com

12
Notes
W = Width of the switchgear.
I = Pole horizontal centre distance.
u/l= Distance between bottom and top terminal.
ø = Diameter of the isolating contact.
5.4.2. Types of withdrawable circuit-breakers available for UniGear type ZS1 switchgear
12
17.5
VD4/P withdrawable circuit-breaker for UniGear type ZS1 switchgear
Ur Isc Rated uninterrupted current (40°C) [A]
kV kA W = 650 W = 800 W = 1000 W = 1000 W = 800 W = 1000 W = 1000 Circuit-breakertype
I = 150 I = 210 I = 275 I = 275 I = 210 I = 275 I = 275
u/l = 205 u/l = 310 u/l = 310 u/l = 310 u/l = 310 u/l = 310 u/l = 310
ø = 35 ø = 79 ø = 79 ø = 109 ø = 35 ø = 35 ø = 79
16 630 VD4/P 12.06.16 p150
20 630 VD4/P 12.06.20 p150
25 630 VD4/P 12.06.25 p150
31.5 630 VD4/P 12.06.32 p150
16 1000 VD4/P 12.12.16 p150
20 1000 VD4/P 12.12.20 p150
25 1000 VD4/P 12.12.25 p150
31.5 1000 VD4/P 12.12.32 p150
16 1250 VD4/P 12.12.16 p150
20 1250 VD4/P 12.12.20 p150
25 1250 VD4/P 12.12.25 p150
31.5 1250 VD4/P 12.12.32 p150
20 1600 VD4/P 12.16.20 p210
25 1600 VD4/P 12.16.25 p210
31.5 1600 VD4/P 12.16.32 p210
20 2000 VD4/P 12.20.20 p210
25 2000 VD4/P 12.20.25 p210
31.5 2000 VD4/P 12.20.32 p210
20 1600 VD4/P 12.16.20 p275
25 1600 VD4/P 12.16.25 p275
31.5 1600 VD4/P 12.16.32 p275
20 2000 VD4/P 12.20.20 p275
25 2000 VD4/P 12.20.25 p275
31.5 2000 VD4/P 12.20.32 p275
20 2500 VD4/P 12.25.20 p275
25 2500 VD4/P 12.25.25 p275
31.5 2500 VD4/P 12.25.32 p275
16 630 VD4/P 17.06.16 p150
20 630 VD4/P 17.06.20 p150
25 630 VD4/P 17.06.25 p150
31.5 630 VD4/P 17.06.32 p150
16 1000 VD4/P 17.12.16 p150
20 1000 VD4/P 17.12.20 p150
25 1000 VD4/P 17.12.25 p150
31.5 1000 VD4/P 17.12.32 p150
16 1250 VD4/P 17.12.16 p150
20 1250 VD4/P 17.12.20 p150
25 1250 VD4/P 17.12.25 p150
31.5 1250 VD4/P 17.12.32 p150
20 1600 VD4/P 17.16.20 p210
25 1600 VD4/P 17.16.25 p210
31.5 1600 VD4/P 17.16.32 p210
20 2000 VD4/P 17.20.20 p210
25 2000 VD4/P 17.20.25 p210
31.5 2000 VD4/P 17.20.32 p210
20 1600 VD4/P 17.16.20 p275
25 1600 VD4/P 17.16.25 p275
31.5 1600 VD4/P 17.16.32 p275
20 2000 VD4/P 17.20.20 p275
25 2000 VD4/P 17.20.25 p275
31.5 2000 VD4/P 17.20.32 p275
20 2500 VD4/P 17.25.20 p275
25 2500 VD4/P 17.25.25 p275
31.5 2500 VD4/P 17.25.32 p275
All manuals and user guides at all-guides.com

13
Notes
W= Width of the switch-
gear.
I = Pole horizontal centre
distance.
u/l= Distance between bot-
tom and top terminal.
ø = Diameter of the isolat-
ing contact.
(*) The rated current of
2300A is guaranteed
with natural ventilation.
The rated current of
2500A is guaranteed
with forced ventilation.
5.4.3. Standard fittings for withdrawable circuit-breakers for
UniGear type ZS1 switchgear
Thebasicversionsofthewithdrawablecircuit-breakers are three-pole and
fitted with:
– EL type manual operating mechanism
– mechanical signalling device for closing springs charged/discharged
– mechanical signalling device for circuit-breaker open/closed
– closingpushbutton
– openingpushbutton
– operationcounter
– set of ten circuit-breaker open/closed auxiliary contacts.
Note
With the group of ten auxiliary contacts, as standard, and the maximum of the
requested applications, the following are available: three opening contacts
(signalling circuit-breaker open) and five closing contacts (signalling circuit-
breaker closed).
– lever for manually charging the closing springs
– isolating contacts
– cordwithconnector(plugonly)forauxiliarycircuits, with striker pin which
doesnot allow connectionofthe plug inthesocket if therated current of
the circuit-breaker is different from the rated current of the panel
– racking-in/outlever(thequantitymust bedefinedaccordingtothenumber
ofpieces ofapparatus ordered)
– locking electromagnet in the truck. It prevents racking-in of the circuit-
breaker in the panel with auxiliary circuits not connected (plug not in-
serted in the socket).
24
Ur Isc Rated uninterrupted current (40°C) [A]
kV kA W = 650 W = 800 W = 1000 W = 1000 W = 800 W = 1000 W = 1000 Circuit-breakertype
I = 150 I = 210 I = 275 I = 275 I = 210 I = 275 I = 275
u/l = 205 u/l = 310 u/l = 310 u/l = 310 u/l = 310 u/l = 310 u/l = 310
ø = 35 ø = 79 ø = 79 ø = 109 ø = 35 ø = 35 ø = 79
16 630 VD4/P 24.06.16 p210
20 630 VD4/P 24.06.20 p210
25 630 VD4/P 24.06.25 p210
16 1000 VD4/P 24.12.16 p210
20 1000 VD4/P 24.12.20 p210
25 1000 VD4/P 24.12.25 p210
16 1250 VD4/P 24.12.16 p210
20 1250 VD4/P 24.12.20 p210
25 1250 VD4/P 24.12.25 p210
16 630 VD4/P 24.06.16 p275
20 630 VD4/P 24.06.20 p275
25 630 VD4/P 24.06.25 p275
16 1000 VD4/P 24.12.16 p275
20 1000 VD4/P 24.12.20 p275
25 1000 VD4/P 24.12.25 p275
16 1250 VD4/P 24.12.16 p275
20 1250 VD4/P 24.12.20 p275
25 1250 VD4/P 24.12.25 p275
16 1600 VD4/P 24.16.16 p275
20 1600 VD4/P 24.16.20 p275
25 1600 VD4/P 24.16.25 p275
16 2000 VD4/P 24.20.16 p275
20 2000 VD4/P 24.20.20 p275
25 2000 VD4/P 24.20.25 p275
16 2300 VD4/P 24.25.16 p275
20 2300 VD4/P 24.25.20 p275
25 2300 VD4/P 24.25.25 p275
16 2500 (*) VD4/P 24.25.16 p275
20 2500 (*) VD4/P 24.25.20 p275
25 2500 (*) VD4/P 24.25.25 p275
VD4/D withdrawable circuit-breaker for UniGear type ZS1 switchgear
All manuals and user guides at all-guides.com

14
5.4.4. General characteristics of withdrawable circuit-breakers for UniSafe switchgear
(1)Rated uninterrupted currents guaranteed with withdrawable circuit-breakers installed
in UniSafe switchgear with air temperature of 40 °C.
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated symmetrical
short-circuit current)
Rated short-time
withstand current (3 s)
Making capacity
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
Maximum overall dimensions
Pole centre distance
Standardised table of dimensions
Operating temperature
Tropicalisation
Electromagnetic compatibility
IEC62271-100
CEI 17-1 (File 1375)
Ur [kV]
Us [kV]
Ud (1 min) [kV]
Up [kV]
fr [Hz]
(1) Ir [A]
Isc [kA]
Ik [kA]
Ip [kA]
[O-0,3s-CO-3min-CO]
[ms]
[ms]
[ms]
[ms]
H[mm]
W[mm]
D[mm]
I[mm]
[°C]
IEC:60068-2-30
721-2-1
IEC: 60694, 61000-6-2
61000-6-4
VD4/P 12
12
12
28
75
50-60
630 1250 630 1250 1600 2000 2500
16 16 16 16 – – –
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
16 16 16 16 – – –
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 – – –
50 50 50 50 50 50 50
63 63 63 63 63 63 63
80 80 80 80 80 80 80
40 ... 60
10 ... 15
50 ... 75
60 ... 80
632 632 632 632 690 690 690
503 503 503 503 653 653 853
664 664 664 664 642 642 642
150 150 210 210 210 210 275
TN7412 TN7412 TN7420 TN7420 TN7415 TN7415 TN7417
– 5 ... + 40
All manuals and user guides at all-guides.com
all-guides.com

15
VD4/P 24
24
24
50
125
50-60
630 1250 1600 2000
16 16 16 16
20 20 20 20
25 25 25 25
––––
16 16 16 16
20 20 20 20
25 25 25 25
––––
40 40 40 40
50 50 50 50
63 63 63 63
––––
40 ... 60
10 ... 15
50 ... 75
60 ... 80
794 794 853 853
653 653 853 853
802 802 790 790
210 210 275 275
TN7413 TN7413 TN7418 TN7418
– 5 ... + 40
VD4/P 17
17.5
17.5
38
95
50-60
630 1250 630 1250 1600 2000 2500
16 16 16 16 – – –
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
16 16 16 16 – – –
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 – – –
50 50 50 50 50 50 50
63 63 63 63 63 63 63
80 80 80 80 80 80 80
40 ... 60
10 ... 15
50 ... 75
60 ... 80
632 632 632 632 690 690 690
503 503 503 503 653 653 853
664 664 664 664 642 642 642
150 150 210 210 210 210 275
TN7412 TN7412 TN7420 TN7420 TN7415 TN7415 TN7417
– 5 ... + 40
All manuals and user guides at all-guides.com

16
Notes
W = Width of the switchgear.
I = Pole horizontal centre distance.
u/l= Distance between bottom and top terminal.
ø = Diameter of the isolating contact.
5.4.5. Types of withdrawable circuit-breakers available for UniSafe switchgear
12
VD4/P withdrawable circuit-breaker for UniSafe switchgear
24
Ur Isc Rated uninterrupted current (40°C) [A]
kV kA W = 600 W = 750 W = 750 W = 1000 W = 800 W = 1000 Circuit-breakertype
I = 150 I = 210 I = 210 I = 275 I = 210 I = 275
u/l = 205 u/l = 310 u/l = 310 u/l = 310 u/l = 310 u/l = 310
ø = 35 ø = 35 ø = 79 ø = 109 ø = 35 ø = 79
16 630 VD4/P 12.06.16 p150
20 630 VD4/P 12.06.20 p150
25 630 VD4/P 12.06.25 p150
31.5 630 VD4/P 12.06.32 p150
16 1250 VD4/P 12.12.16 p150
20 1250 VD4/P 12.12.20 p150
25 1250 VD4/P 12.12.25 p150
31.5 1250 VD4/P 12.12.32 p150
16 630 VD4/W 12.06.16 p210
20 630 VD4/W 12.06.20 p210
25 630 VD4/W 12.06.25 p210
31.5 630 VD4/W 12.06.32 p210
16 1250 VD4/W 12.12.16 p210
20 1250 VD4/W 12.12.20 p210
25 1250 VD4/W 12.12.25 p210
31.5 1250 VD4/W12.12.32p210
20 1600 VD4/P 12.16.20 p210
25 1600 VD4/P 12.16.25 p210
31.5 1600 VD4/P 12.16.32 p210
20 2000 VD4/P 12.20.20 p210
25 2000 VD4/P 12.20.25 p210
31.5 2000 VD4/P 12.20.32 p210
20 2500 VD4/P 12.25.20 p275
25 2500 VD4/P 12.25.25 p275
31.5 2500 VD4/P 12.25.32 p275
16 630 VD4/P 17.06.16 p150
20 630 VD4/P 17.06.20 p150
25 630 VD4/P 17.06.25 p150
31.5 630 VD4/P 17.06.32 p150
16 1250 VD4/P 17.12.16 p150
20 1250 VD4/P 17.12.20 p150
25 1250 VD4/P 17.12.25 p150
31.5 1250 VD4/P 17.12.32 p150
16 630 VD4/W 17.06.16 p210
20 630 VD4/W 17.06.20 p210
25 630 VD4/W 17.06.25 p210
31.5 630 VD4/W 17.06.32 p210
16 1250 VD4/W 17.12.16 p210
20 1250 VD4/W 17.12.20 p210
25 1250 VD4/W 17.12.25 p210
31.5 1250 VD4/W 17.12.32 p210
20 1600 VD4/P 17.16.20 p210
25 1600 VD4/P 17.16.25 p210
31.5 1600 VD4/P 17.16.32 p210
20 2000 VD4/P 17.20.20 p210
25 2000 VD4/P 17.20.25 p210
31.5 2000 VD4/P 17.20.32 p210
20 2500 VD4/P 17.25.20 p275
25 2500 VD4/P 17.25.25 p275
31.5 2500 VD4/P 17.25.32 p275
16 630 VD4/P 24.06.16 p210
20 630 VD4/P 24.06.20 p210
25 630 VD4/P 24.06.25 p210
16 1250 VD4/P 24.12.16 p210
20 1250 VD4/P 24.12.20 p210
25 1250 VD4/P 24.12.25 p210
16 1600 VD4/P 24.16.16 p275
20 1600 VD4/P 24.16.20 p275
25 1600 VD4/P 24.16.25 p275
16 2000 VD4/P 24.20.16 p275
20 2000 VD4/P 24.20.20 p275
25 2000 VD4/P 24.20.25 p275
17.5
All manuals and user guides at all-guides.com

17
5.4.6. Standard fittings for withdrawable circuit-breakers for UniSafe switchgear
The basic versions of the withdrawable circuit-breakers are always three-pole and fitted with:
– EL type manual operating mechanism
– mechanical signalling device for closing springs charged/discharged
– mechanical signalling device for circuit-breaker open/closed
– closingpushbutton
– openingpushbutton
– operationcounter
– set of ten circuit-breaker open/closed auxiliary contacts.
Note
With the group of ten auxiliary contacts, as standard, and the maximum of the requested applications, the
following are available: three opening contacts (signalling circuit-breaker open) and five closing contacts
(signalling circuit-breaker closed).
– lever for manually charging the closing springs
– isolating contacts
– cord with connector (only plug) for auxiliary circuits, with striker pin which does not allow
connection of the plug in the socket if the rated current of the circuit-breaker is different from
the rated current of the panel
– racking-in/out lever (the quantity must be defined according to the number of pieces of appara-
tusordered)
– locking electromagnet in the truck. It prevents racking-in of the circuit-breaker in the panel with
auxiliary circuits not connected (plug not inserted in the socket).
All manuals and user guides at all-guides.com

18
5.5. Characteristics of the electrical
accessories
Shunt opening release (-M01);
Additional shunt opening release (-M02);
Shunt closing release (-MC)
Un: 24 - 30 - 48 - 60 - 110 - 125
- 220 - 250 V–
Un: 24 - 48 - 60 - 110 - 120 ...
127 - 220 ... 240 V~ 50 Hz
Un: 110 - 120 - 127 - 220 - 240
V~ 60 Hz
Operating limits: 70 … 110 % Un
Inrush power (Ps): DC 200 W; AC = 200 VA
Inrush time approx. 100 ms
Maintenance power (Pc): DC = 5 W; AC = 5 VA
Opening time: 40 ... 60 ms
Closing time: 60 ... 80 ms
Insulation voltage: 2500 V 50 Hz (for 1 min)
Undervoltage release (-MU)
Un: 24 - 30 - 48 - 60 - 110 - 125
- 220 - 250 V–
Un: 24 - 48 - 60 - 110 - 120 -
127 - 220 ... 240 V~ 50 Hz
Un: 110 - 120 ... 127 - 220 ...
240 V~ 60 Hz
Operating limits:
– circuit-breaker opening: 35-70% Un
– circuit-breaker closing: 85-110% Un
Inrush power (Ps): DC 200 W; AC = 200 VA
Inrush time approx. 100 ms
Maintenance power (Pc): DC = 5 W; AC = 5 VA
Opening time: 30 ms
Insulation voltage: 2500 V 50 Hz (for 1 min)
Electronic time delay device
for undervoltage release
(mounted outside the circuit-breaker)
Un: 24 ... 30 - 48 - 60 - 110 ...
127 - 220 ... 250 V–
Un: 48 - 60 - 110 ... 127 - 220
... 240 V~ 50/60 Hz
Adjustable opening time (release + time delay device):
0.5-1-1.5-2-3 s
Auxiliary contacts of the circuit-breaker
Un: 24 ... 220 V AC-DC
Rated current: Ith2= 10 A
Insulation voltage: 2500 V 50 Hz (for 1 min)
Electrical resistance: 3 mOhm
Rated current and breaking capacity
in category AC11 and DC11:
Un CosjT In Icu
220 V ~ 0.7 -- 2.5 A 25 A
24 V – -- 15 ms 10 A 12 A
60 V – -- 15 ms 6 A 8 A
110 V – -- 15 ms 4 A 5 A
220 V – -- 15 ms 1 A 2 A
Note
With the group of ten auxiliary contacts, as standard, and
the maximum of the requested applications, the following
are available: three opening contacts (signalling circuit-
breaker open) and five closing contacts (signalling circuit-
breaker closed).
With the group of fifteen auxiliary contacts, depending on
therequested electricalapplications, thefollowing are avail-
able:
– fixed circuit-breaker: thirteen auxiliary contacts, shared
between opening contacts and closing contacts accord-
ing to the diagram figure used;
– withdrawablecircuit-breaker: asthe auxiliarycircuitsplug-
socket connector has a limited number of pins: five open-
ingcontacts (signalling circuit-breakeropen)and five clos-
ing contacts (signalling circuit-breaker closed).
Motor operator (-MS)
Un: 24 ... 30 - 48 ... 60 - 110
... 130 - 220 ... 250 V–
Un: 100 ... 130 - 220 ... 250
V~ 50/60 Hz
Operating limits: 85 … 110 % Un
Inrush power (Ps): DC 500 W; AC = 500 VA
Rated power (Pn): DC = 200 W;AC = 200
VA
Inrush time 0,2 s
Charging time: 4-5 s
Insulation voltage: 2500 V 50 Hz (for 1 min)
Locking magnet on the operating
mechanism (-RL1)
Un: 24 - 30 - 48 - 60 - 110 -
132 - 220 - 250 V–
Un: 48 - 60 - 110 - 120 ... 127
- 220 ... 240 V~ 50/60 Hz
Operating limits: 85 … 110 % Un
Inrush power (Ps): DC 250 W; AC = 250 VA
Continuous power (Pc): DC = 5 W; AC = 5 VA
Inrush time: 150 ms
Locking magnet on the truck (-RL2)
Un: 24 - 30 - 48 - 60 - 110 -
125 - 127 - 132 - 220 -
240 V–
Un: 24 - 30 - 48 - 60 - 110 -
125 - 127 - 220 - 230 ...
240 V~ 50/60 Hz
Operating limits: 85 … 110 % Un
Inrush power (Ps): DC 250 W; AC = 250 VA
Continuous power (Pc): DC = 5 W; AC = 5 VA
Inrush time: 150 ms
All manuals and user guides at all-guides.com
This manual suits for next models
165
Other ABB Circuit Breaker manuals

ABB
ABB SACE Tmax T6 User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB Emax User manual

ABB
ABB TMAX MOE User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB SACE Tmax XT2 User manual

ABB
ABB GE Power Break II GEH6271 User manual

ABB
ABB F204 125 Series User manual

ABB
ABB MS 450 User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB VHK-R Installation and operating instructions

ABB
ABB F200 B Service manual

ABB
ABB VM1/A/P Quick guide

ABB
ABB SACE Tmax XT User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB Infinity S User manual

ABB
ABB F-ARI Test Series User manual

ABB
ABB SACE Tmax XT Series User manual

ABB
ABB R-MAG Series User manual

ABB
ABB K-Line Plus KP-8 Installation and operating instructions