
Page 1 of 3
50 Hanover Road, Florham Park, New Jersey 07932 www ascovalve com All Rights Reserved
E176939
Installation & Maintenance Instructions SERIES
I&M No.V7533
8314NORMALLY O EN AND UNIVERSAL O ERATION
3/64I, 3/32I, 1/8I AND 5/32I ORIFICES
1/8I AND 1/4I N T
MIDGET 3-WAY SOLENOID VALVES NORMALLY CLOSED,
NOTICE: See separate solenoid installation and
maintenance instructions for information on: Wiring,
Solenoid Temperature, Cause of Improper Operation and
Coil Replacement.
DESCRIPTION
Series 8314 valves are midget 3-way solenoid valves . Valve bodies
are of brass constr ction. Series 8314 valves may be provided with a
general p rpose/watertight, open-frame or explosionproof/watertight
solenoid.
OPER TION
Normally Closed: Applies press re when solenoid is energized; exha sts
press re when solenoid is de-energized. Flow is Connection 2" to 1"
when solenoid is energized. Connection 3" is closed. Flow is from
Connection 1" to 3" when solenoid is de-energized. Connection 2"
is closed. Press re is applied at Connection 2".
Normally Open: Applies press re when solenoid is de-energized;
exha sts press re when solenoid is energized. Flow is Connection 1" to
2" when solenoid is energized. Connection 3" is closed. Flow is from
Connection 3" to 1" when solenoid is de-energized. Connection 2"
is closed. Press re is applied at Connection 3".
Universal: For normally closed or normally open operation, selection or
diversion of press re can be applied at Connections 1", 2" or 3". Flow
is between Connection 1" to 2" when solenoid is energized.
Connection 3" is closed. Flow is between Connection 1" to 3" when
solenoid is de-energized. Connection 2" is closed. Press re may be
applied at Connection 1", 2" or 3".
IMPORT NT: No minimum operating pressure differential
required.
DE-ENERGIZED
ENERGIZED
NORMALLY CLOSEDNORMALLY OPEN
DE-ENERGIZED
DE-ENERGIZED
ENERGIZEDENERGIZED
12
3
12
3
12
3
12
3
12
3
12
3
UNIVERSAL
PRESSURE ANY ORIFICE
PRESSURE ANY ORIFICE
Flow Diagram
INST LL TION
Check nameplate for correct catalog n mber, press re, voltage,
freq ency, and service. Never apply incompatible fl ids or exceed
press re rating of the valve. Installation and valve maintenance to be
performed by q alified personnel.
Temperature Limitations
Valves with design change letter K" or P" within the catalog n mber
(example: 8314K035) have a maxim m fl id temperat re of 180F.
Refer to separate solenoid Installation and Maintenance Instr ctions
for maxim m ambient temperat re.
Positioning
This valve is designed to perform properly when mo nted in any
position. However, for optim m life and performance, the solenoid
sho ld be mo nted vertically and pright to red ce the possibility of
foreign matter acc m lating in the solenoid base s b-assembly area.
Piping
Connect piping or t bing to valve according to markings on valve
body. Apply pipe compo nd sparingly to male pipe threads only. If
applied to valve threads, the compo nd may enter the valve and ca se
operational diffic lty. Avoid pipe strain by properly s pporting and
aligning piping. When tightening the pipe, do not se valve or
solenoid as a lever. Locate wrenches applied to valve body or piping
as close as possible to connection point.
IMPORT NT: To protect the solenoid valve, install a
strainer or filter, suitable for the service involved, in the inlet
side as close to the valve as possible. Clean periodically
depending on service conditions. See SCO Series 8600,
8601 and 8602 for strainers.
M INTEN NCE
WARNING: To prevent the possibility of
death, personal injury or property damage, turn
off electrical power, depressurize valve, and vent
fluid to a safe area before servicing the valve.
NOTE: It is not necessary to remove the valve from the pipeline for
repairs.
Cleaning
All solenoid valves sho ld be cleaned periodically. The time between
cleanings will vary depending on the medi m and service conditions. In
general, if the voltage to the coil is correct, sl ggish valve operation,
excessive noise or leakage will indicate that cleaning is req ired. In the
extreme case, fa lty valve operation will occ r and the valve may fail to
open or close. Clean valve strainer or filter when cleaning the valve.
Preventive Maintenance
Keep medi m flowing thro gh the valve as free from dirt and
foreign material as possible.