Page 2 of 6 DATA SHEET E85001-0609
Not to be used for installation purposes. Issue 1
Application
The operation of the SIGA-CC2A/MCC2A is determined by their sub-type code or “Personality Code”. The code is selected by the
installer depending upon the desired application and is downloaded from the loop controller. The following personality codes can be used
with the SIGA-CC2A/MCC2A:
When using the SIGA-CC2A/MCC2A as a single input module
Personality
code 5
Riser selector Class B, single input. The module operates as a single riser selector for signal power (24 VDC) or au-
dio evacuation (25 or 70 VAC). The output circuit is monitored for open or shorted wiring. If a short exists, the control
panel inhibits the activation of the audible or visible signal circuit, so that the riser is not connected to the wiring fault.
Personality
code 27 Riser selector Class A, single input. Operates the same as personality code 5, except wiring is Class A.
Personality
code 6
Riser selector Class B three-state, single input, ring tone. The module operates as a riser selector for a three-state
(open, normal, active) firefighter’s telephone. When a telephone handset is plugged into its jack or lifted from its
hook, the module generates its own ring-tone signal. A separate ring-tone riser is unnecessary. The module sends
this signal to the control panel to indicate the presence of an off-hook condition and waits for the system operator to
respond to the call. When the system operator responds, the ring-tone signal is disabled.
Personality
code 28
Riser selector Class A three-state, single input, ring tone. Operates the same as personality code 6, except wiring is
Class A.
Personality
code 26
Riser selector Class B four-state, single input, ring tone. The module operates as a riser selector for a four-state
(open, normal, active, trouble) firefighter’s telephone. Only one telephone can be used with the CC2A at any given
time. When a telephone handset is plugged into its jack or lifted from its hook, the module generates its own ring-
tone signal. A separate ring-tone riser is unnecessary. The module sends this signal to the control panel to indicate
the presence of an off-hook condition, and waits for the system operator to respond to the call. When the system
operator responds, the ring-tone signal is disabled.
Personality
code 29
Riser selector Class A four-state, single input, ring tone. Operates the same as personality code 26, except wiring is
Class A. Not compatible with Warden Phones.
Personality
code 25
Class B auto synchronization output. The module operates to provide synchronization of compatible fire alarm sig-
nals across multiple zones. The output wiring is monitored for opens and shorts. If a short exists, the module inhibits
the activation of the audible/visual signal circuit so that the riser is not connected to the wiring fault.
Note: You may use nonsynchronous fire alarm signals with or instead of compatible synchronized fire alarm signals, but the opera-
tion of these devices will not comply with UL 1971.
Personality
code 19 Class A auto synchronization output. Operates the same as personality code 25, except wiring is Class A.
When using the SIGA-CC2A/MCC2A as a dual input module:
Personality
code 7
Riser selector Class B, dual input. The module operates as a riser selector for dual signal power (24 Vdc) or dual
audio evacuation (25 V or 70 V) riser selector. The output circuit is monitored for open or shorted wiring. If a short
exists, the control panel inhibits the activation of the audible or visible signal circuit, so the riser is not connected to
the wiring fault.
Personality
code 30 Riser selector Class A, dual input. Operates the same as personality code 7, except wiring is Class A.