Evco EVK614 User manual

Evco S.p.A. • Code 104K614E00 • page 1/7
EVK614 Digital controller for retarder-prover cabinets and rooms, with RTC function version 1.00
E ENGLISH
1 IMPORTANT
1.1 Important
Read these instructions carefully before installation and commission-
ing and follow the recommendations regarding installation and for
electric connection. Keep these instructions with the instrument for
future consultation.
The instrument must be disposed of in compliance with
the local Standards regarding the collection of electrical
and electronic appliances.
2 DIMENSIONS AND INSTALLATION
2.1 Dimensions
The dimensions are expressed in mm (in).
DIMENS. MINIMUM TYPICAL MAXIMUM
A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826)
B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)
2.2 Installation
Panel with click brackets supplied.
2.3 Installation recommendations
• the thickness of the panel must not exceed 8.0 mm (0.314 in)
• make sure that the work conditions (temperature of use, humidity,
etc.) lie within the limits indicated in the technical data
• do not install the instrument in vicinity of heat sources (resistances,
hot air pipes, etc.), appliances with strong magnets (large diffusers,
etc.), places subject to direct sunlight, rain, humidity, excessive dust,
mechanical vibrations or shocks
• in compliance with Safety Standards, the protection against any
contact with electric parts must be assured via correct installation of
the instrument; all parts that ensure protection must be fixed in a way
that they cannot be removed without using tools.
3 ELECTRIC CONNECTION
3.1 Preliminary considerations
With reference to the wiring diagram:
• port 1 is the serial port for communication with the supervision
system (through a serial interface, via TTL, with MODBUS communi-
cation protocol), with graphic diagram (through a serial interface)
or with the programming key; the port must be used just for one
purpose
• port 2 (on request) is the port for communication with the remote
indicator. The latter shows the temperature of the room.
3.2 Electric connection
3.3 Recommendations for the electric connection
• do not operate on terminal boards using electric or pneumatic screw-
ing devices
• if the instrument has been taken from a cold to a hot place, the
humidity could condense inside; wait about 1 hour before apply-
ing power
• make sure that the power supply voltage, the frequency and the
operational electric power of the instrument correspond with those
of the local power supply
• disconnect the power supply before proceeding with any type of
maintenance
• do not use the instrument as a safety device
• for repairs and information regarding the instrument, contact the
Evco sales network.
4 FUNCTIONING
4.1 Preliminary considerations
The following functioning cycles exist:
• automatic cycle
• heating manual cycle
• cooling manual cycle.
The automatic cycle is made up of the following phases:
- a retarding provering phase
- a storing phase
- an awakening phase
- a provering phase
- a slowing phase
On conclusion of one phase the instrument passes automatically to
the next one.
5 AUTOMATIC CYCLE
5.1 Start/stop of the automatic cycle
To start the cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Auto”
• press within 15 s: the display will show the following 3 times in
succession:
- the conclusion time of the provering phase (e.g. “02:00”)
-“dd” followed by the two numbers of the day of conclusion of the
provering phase (e.g. “dd26”)
-“MM” followed by the two numbers of the month of conclusion of
the provering phase (e.g. “MM03”)
• press within 9 s: the display will show “Go”
• press within 15 s: the LED will switch on and the retarding-
provering phase will be started.
If the automatic cycles are not enabled (parameter P7 = 0), the “Auto”
label will not be displayed.
The end time of the provering phase is displayed in the 24 hour format
(hours:minutes). The time proposed is the same as the last automatic
cycle started but relative to the next day.
In the example, the provering phase will be concluded at 02:00 on
26 March. The display will show all information for 1 s.
If parameter P9 is set at 0, the display will only show the conclusion
time of the provering phase.
To stop the cycle:
• press for 4 s.
5.2 Modifying the end time and date of the provering
phase
• make sure that the day and real time are set correctly, that the instru-
ment is in stand-by and that no procedure is in progress.
• press : the display will show the first label available
• press or within 15 s to select “Auto”
• press within 15 s: the display will show the end time and date
of the provering phase in succession
• press within 9 s: the display will show “hh” followed by the
two numbers regarding the hour
• press or within 15 s; parameter P8 is also seen
• press within 15 s: the display will show “nn” followed by the
two numbers regarding the minutes
• press or within 15 s; parameter P8 is also seen
• press within 15 s: the display will show “dd” followed by the
two numbers regarding the day
• press or within 15 s; parameter P8 is also seen
- if the two numbers of the day exceed the real ones, the end date of
the provering phase will refer to the real month (e.g., if it is 26 March
and the two numbers of the day are set at 27, the end date of the
provering phase will be 27 March)
- if the two numbers of the day are lower than the real ones, the end
date of the provering phase will refer to the following month (e.g.,
if it is 26 March and the two numbers of the day are set at 25, the end
date of the provering phase will be 25 April)
• press within 15 s: the display will show the end time and date
of the provering phase in succession again.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
5.3.1 Modifying the settings of the retarding-provering
phase
To set the duration of the retarding-provering phase:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Auto”
• press within 15 s: the display will show the end time and date
of the provering phase in succession
• press or within 9 s to select “PHA1” (it is the label of the
retarding-provering phase): the LED
will switch on
• press within 15 s: the display will show “hh” followed by the
two numbers regarding the hours
• press or within 15 s; parameter P8 is also seen
• press within 15 s: the display will show “nn” followed by the
two numbers regarding the minutes
• press or within 15 s; parameter P8 is also seen.
It is also possible to set the duration of the retarding-provering phase
via the dur0 parameter.
To set the work set-point during the retarding-provering phase:
• press during the modification of the duration of the retarding-
provering phase (i.e. during modification of the minutes):
the display will show “SEt” for 1 s after which the value is
shown
• press or within 15 s; parameters P8, rC1and rC2 are also
seen.
It is also possible to set the retarding-provering phase work set-point
via the SEt0 parameter.
To set the percentage of relative humidity during the retarding-
provering phase (only if parameter rU4 is set at 1):
• press during the modification of the work set-point during the
retarding-provering phase: the display will show “Ur” for
1 s after which the value is shown
• press or within 15 s; parameters P8, rU3, rU5 and rU6
are also seen.
• press within 15 s: the display will show “PHA2” (it is the label
of the storing phase), the LED will switch off and the
LED will switch on.
It is also possible to set the percentage of relative humidity during the
retarding-provering phase via the Ur0 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
5.3.2 The retarding provering phase
During the retarding provering phase:
• the activity of the compressor depends mainly on parameters SEt0,
rC0 and rC4
• the resistances remain off
• the evaporator fan activity depends mainly on parameter F0
• the activity of the humidifier mainly depends on parameters Ur0,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available.
• defrosting can be activated
• the LED is on.
The retarding-provering phase has duration of the time established
via parameter dur0. When this time has expired the instrument passes
automatically to the storing phase.
5.4.1 Modifying the settings of the storing phase
To set the work set-point during the storing phase:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press owithin 15 s to select “Auto”
• press within 15 s: the display will show the end time and date
of the provering phase in succession

Evco S.p.A. • Code 104K614E00 • page 2/7
• press or within 9 s to select “PHA2” (it is the label of the
storing phase): the LED will switch on.
Alternatively:
• press during the modification of the percentage of relative
humidity during the retarding-provering phase.
Successively:
• press within 15 s: the display will show “SEt” for 1 s after which
the value is shown
• press or within 15 s; parameters P8, rC1and rC2 are also
seen.
It is also possible to set the storing phase work set-point via the SEt1
parameter.
To set the percentage of relative humidity during the storing phase
(only if parameter rU4 is set at 1):
• press during the modification of the work set-point during the
storing phase: the display will show “Ur” for 1 s after which
the value is shown
• press or within 15 s; parameters P8, rU3, rU5 and rU6
are also seen.
• press within 15 s: the display will show “PHA3” (it is the label
of the awakening phase), the LED will switch off and
the LED will switch on.
It is also possible to set the percentage of relative humidity during the
storing phase via the Ur1 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
5.4.2 The storing phase
During the storing phase:
• the activity of the compressor depends mainly on parameters SEt1,
rC0 and rC4
• the resistances remain off
• the evaporator fan activity depends mainly on parameter F1
• the activity of the humidifier mainly depends on parameters Ur1,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available
• defrosting can be activated
• the LED is on.
The duration of the storing phase adapts itself automatically to that of
the retarding-provering phase, to that of the awakening phase, to that
of the provering phase and the end time and date of the provering
phase. At the end of the storing phase, the instrument passes automati-
cally to the awakening phase.
5.5.1 Modifying the settings of the awakening phase
To set the duration of the awakening phase:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Auto”
• press within 15 s: the display will show the end time and date
of the provering phase in succession
• press or within 9 s to select “PHA3” (it is the label of the
awakening phase): the LED will switch on.
Alternatively:
• press during the modification of the percentage of relative
humidity during the storing phase
Successively:
• press within 15 s: the display will show “hh” followed by the
two numbers regarding the hours
• press or within 15 s; parameter P8 is also seen
• press within 15 s: the display will show “nn” followed by the
two numbers regarding the minutes
• press or within 15 s; parameter P8 is also seen.
It is also possible to set the duration of the awakening phase via the
dur2 parameter.
To set the work set-point during the awakening phase:
• press during the modification of the duration of the awakening
phase (i.e. during modification of the minutes): the dis-
play will show “SEt” for 1 s after which the value is shown
• press or within 15 s; parameters P8, rH1and rH2 are also
seen.
It is also possible to set the awakening phase work set-point via the SEt2
parameter.
To set the percentage of relative humidity during the awakening phase:
• press during the modification of the work set-point during the
awakening phase: the display will show “Ur” for 1 s after
which the value is shown
• press or within 15 s; parameters P8, rU3, rU5 and rU6 are
also seen.
• press within 15 s: the display will show “PHA4” (it is the label
of the provering phase), the LED will switch off and the
LED will switch on.
It is also possible to set the percentage of relative humidity during the
awakening phase via the Ur2 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
5.5.2 The awakening phase
During the awakening phase:
• compressor activity mainly depends on the SEt2, rC0 and rC3 pa-
rameters and that of the resistances from the SEt2, rH0 and rH3 pa-
rameters; see also parameter rn1
• the evaporator fan activity depends mainly on parameter F2
• the activity of the humidifier mainly depends on parameters Ur2,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available.
• defrosting is never activated
• the LED is on.
The awakening phase has duration of the time established via param-
eter dur2. When this time has expired, the instrument passes automati-
cally to the provering phase.
5.6.1 Modifying the settings of the provering phase
To set the duration of the provering phase:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Auto”
• press within 15 s: the display will show the end time and date
of the provering phase in succession
• press or within 9 s to select “PHA4” (it is the label of the
provering phase): the LED will switch on.
Alternatively:
• press during the modification of the percentage of relative
humidity during the awakening phase.
Successively:
• press within 15 s: the display will show “hh” followed by the
two numbers regarding the hours
• press or within 15 s; parameter P8 is also seen
• press within 15 s: the display will show “nn” followed by the
two numbers regarding the minutes
• press or within 15 s; parameter P8 is also seen.
It is also possible to set the duration of the provering phase via the dur3
parameter.
To set the work set-point during the provering phase:
• press during the modification of the duration of the provering
phase (i.e. during modification of the minutes): the dis-
play will show “SEt” for 1 s after which the value is shown
• press or within 15 s; parameters P8, rH1and rH2 are also
seen.
It is also possible to set the provering phase work set-point via the SEt3
parameter.
To set the percentage of relative humidity during the provering phase:
• press during the modification of the work set-point during the
provering phase: the display will show “Ur” for 1 s after
which the value is shown
• press or within 15 s; parameters P8, rU3, rU5 and rU6 are
also seen.
• press within 15 s: the display will show “PHA5” (it is the label
of the slowing phase), the LED will switch off and the
LED , , and will switch on.
It is also possible to set the percentage of relative humidity during the
provering phase via the Ur3 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
5.6.2 The provering phase
During the provering phase:
• compressor activity mainly depends on the SEt3, rC0 and rC3 pa-
rameters and that of the resistances from the SEt3, rH0 and rH3 pa-
rameters; see also parameter rn2
• the evaporator fan activity depends mainly on parameter F3
• the activity of the humidifier mainly depends on parameters Ur3,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available
• defrosting is never activated
• the LED is on.
The provering phase has duration of the time established via param-
eter dur3. When this time has expired, the instrument passes automati-
cally to the slowing phase.
5.7.1 Modifying the settings of the slowing phase
To set the work set-point during the slowing phase:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Auto”
• press within 15 s: the display will show the end time and date
of the provering phase in succession
• press or within 9 s to select “PHA5” (it is the label of the
slowing phase): the LEDs , ,
and will switch on.
Alternatively:
• press during the modification of the percentage of relative
humidity during the provering phase.
Successively:
• press within 15 s: the display will show “SEt” for 1 s after which
the value is shown
• press or within 15 s; parameters P8, rH1and rH2 are also
seen.
It is also possible to set the slowing phase work set-point via the SEt4
parameter.
To set the percentage of relative humidity during the slowing phase:
• press during the modification of the work set-point during the
slowing phase: the display will show “Ur” for 1 s after
which the value is shown
• press or within 15 s; parameters P8, rU3, rU5 and rU6 are
also seen.
• press within 15 s: the display will show the end time and date
of the provering phase in succession again and the LEDs
, , and will switch off.
It is also possible to set the percentage of relative humidity during the
slowing phase via the Ur4 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).

Evco S.p.A. • Code 104K614E00 • page 3/7
5.7.2 The slowing phase
During the slowing phase:
• compressor activity mainly depends on the SEt4, rC0 and rC5 pa-
rameters and that of the resistances from the SEt4, rH0 and rH4 pa-
rameters
• the evaporator fan activity depends mainly on parameter F4
• the activity of the humidifier mainly depends on parameters Ur4,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available
• defrosting is never activated
• the LEDs , , and are on.
The slowing phase lasts until the cycle is interrupted by pressing the
for 4 s.
6 HEATING MANUAL CYCLE
6.1 Start/stop of the heating manual cycle
To start the cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Hot”
• press within 15 s: the display will show “Go”
• press within 15 s: the LED will switch on and the cycle will
be started.
To stop the cycle:
• press for 4 s.
6.2.1 Modifying the settings of the heating manual
cycle
To set the duration of the heating manual cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Hot”
• press within 15 s: the display will show “hh” followed by the
two numbers regarding the hours and the LED will
switch on
• press or within 15 s
• press within 15 s: the display will show “nn” followed by the
two numbers regarding the minutes
• press or within 15 s.
To set the work set-point during the heating manual cycle:
• press during the modification of the duration of the heating
manual cycle (i.e. during modification of the minutes): the
display will show “SEt” for 1 s after which the value is
shown
• press or within 15 s; parameters rH1and rH2 are also
seen.
It is also possible to set the heating manual cycle work set-point via the
SEt5 parameter.
To set the percentage relative humidity during the heating manual
cycle:
• press during the modification of the work set-point during the
heating manual cycle: the display will show “Ur” for 1 s
after which the value is shown
• press or within 15 s; parameters rU3, rU5 and rU6 are
also seen.
• press within 15 s: the display will show “Hot” again.
It is also possible to set the percentage of relative humidity during the
heating manual cycle via the Ur5 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
6.2.2 The heating manual cycle
During the heating manual cycle:
• the activity of the resistances depends mainly on parameters SEt5,
rH0 and rH3
• the compressor stays off
• the evaporator fan activity depends mainly on parameter F3
• the activity of the humidifier mainly depends on parameters Ur5,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available.
• defrosting is never activated
• the LED is on.
The heating manual cycle lasts until it is interrupted by pressing the
for 4 s. When the duration of the heating manual cycle has ended,
the buzzer is activated for the time established with parameter dur5.
7 COOLING MANUAL CYCLE
7.1 Start/stop of the cooling manual cycle
To start the cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Cold”
• press within 15 s: the display will show “Go”
• press within 15 s: the LED will switch on and the cycle will
be started.
To stop the cycle:
• press for 4 s.
7.2.1 Modifying the settings of the cooling manual
cycle
To set the work set-point during the cooling manual cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press : the display will show the first label available
• press or within 15 s to select “Cold”
• press within 15 s: the display will show “SEt” for 1 s after which
the value is shown
• press or within 15 s; parameters rC1 and rC2 are also
seen.
• press within 15 s: the display will show “Cold” again.
It is also possible to set the heating manual cycle work set-point via the
SEt6 parameter.
To go back to previous levels:
• press during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
7.2.2 The cooling manual cycle
During the cooling manual cycle:
• the activity of the compressor depends mainly on parameters SEt6,
rC0 and rC4
• the resistances remain off
• the evaporator fan activity depends mainly on parameter F0
• the humidifier remains off
• defrosting can be activated
• the LED is on.
The cooling manual cycle lasts until it is interrupted by pressing the
for 4 s.
8 USER INTERFACE
8.1 Preliminary considerations
The following functioning states exist:
• the “on” status (the instrument is powered and a functioning cycle
is in progress: the regulators can be switched on)
• the “stand-by” status (the instrument is powered but no functioning
cycle is in progress: the regulators are off)
• the “off” status (the instrument is not powered).
Successively, the term “switch-on” means the passage from the stand-
by status to the on status; the term “switch-off” means the passage from
the on status to the stand-by status.
If the power supply is shut-off during the stand-by status, the same
status will be proposed again when the power supply is restored.
If the power supply is shut-off during the on status, instrument function-
ing will depend on parameter P6 when the power supply is restored.
8.2 The display
If the instrument is on, during normal functioning the display will
show the size established via parameter P4:
• if P4 = 0, the display will show the temperature of the room if a
functioning cycle is in progress and will be off if the instrument is in
stand-by
• if P4 = 1, the display will show the end time of the provering phase
if a functioning cycle is in progress and will be off if the instrument
is in stand-by
• if P4 = 2, the display will show the temperature of the room (for 3 s)
alternating with the end time of the provering phase (for 1 s) if a
functioning cycle is in progress and will be off if the instrument is in
stand-by
• if P4 = 3, the display will show the temperature of the room if a
functioning cycle is in progress and the real time if the instrument is
in stand-by
• if P4 = 4, the display will show the end time of the provering phase
if a functioning cycle is in progress and the real time if the instrument
is in stand-by
• if P4 = 5, the display will show the temperature of the room (for 3 s)
alternating with the end time of the provering phase (for 1 s) if a
functioning cycle is in progress and the real time if the instrument is
in stand-by.
8.3 Displaying the room temperature
• make sure that no procedure is in progress
• press for 1 s: the display will show the first label available
• press or to select “Pb1”
• press
To exit the procedure:
• press or do not operate for 60 s
• press or until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
8.4 Displaying the evaporator temperature
• make sure that no procedure is in progress
• press for 1 s: the display will show the first label available
• press or to select “Pb2”
• press
To exit the procedure:
• press or do not operate for 60 s
• press or until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
If the evaporator probe is absent (parameter P3 = 0), the “Pb2” label
will not be displayed.
8.5 Displaying the end time and date of the provering
phase
• make sure that an automatic cycle is in progress and no procedure
is in progress
• press for 1 s: the display will show the first label available
• press or to select “End”
• press : the display will show the following in succession:
- the conclusion time of the provering phase (e.g. “02:00”)
-“dd” followed by the two numbers of the day of conclusion of the
provering phase (e.g. “dd26”)
-“MM” followed by the two numbers of the end month of the
provering phase (e.g. “MM03”)
To exit the procedure:
• press or do not operate for 60 s
• press or until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
If a heating or cooling manual cycle is in progress, the “End” label will
not be displayed.
The end time of the provering phase is displayed in the 24 hour format
(hours: minutes).
In the example, the provering phase will be concluded at 02:00 on
26 March. the display will show all information for 1 s.
If parameter P9 is set at 0, the display will only show the conclusion
time of the provering phase.

Evco S.p.A. • Code 104K614E00 • page 4/7
8.6 Displaying the real time
• make sure that no procedure is in progress
• press for 1 s: the display will show the first label available
• press or to select “tiME”
• press
To exit the procedure:
• press or do not operate for 60 s
• press or until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
The real time is displayed in 24 hour format (hour:minutes).
If the automatic cycles are not enabled (parameter P7 = 0), the “tiME”
label will not be displayed.
8.7 Displaying the output states
To display the state of the compressor:
• make sure that a functioning cycle is in progress and no procedure
is in progress
• press : the display will show the first label available
- if the display shows “C-1”, the compressor is on
- if the display shows “C-0”, the compressor is off
- if the display shows “C-P”, a compressor protection is in progress
(parameters C0, C1, C2 and C3).
To display the state of the evaporator fan:
• make sure that a functioning cycle is in progress and no procedure
is in progress
• press twice: the display will show the first label available.
Alternatively:
• press during the display of the compressor status
- if the display shows “F-1”, the evaporator fan is on
- if the display shows “F-0”, the evaporator fan is off.
To display the state of the resistances:
• make sure that a functioning cycle is in progress and no procedure
is in progress
• press 3 times: the display will show the first label available.
Alternatively:
• press during the display of the evaporator fan status
- if the display shows “r-1”, the resistances are on
- if the display shows “r-0”, the resistances are off.
To display the state of the humidifier:
• make sure that a functioning cycle is in progress and no procedure
is in progress
• press 4 times: the display will show the first label available.
Alternatively:
• press during the display of the status of the resistances
- if the display shows “i-1”, the humidifier is on
- if the display shows “i-0”, the humidifier is off.
To exit the procedure:
• press until the display shows the size established via parameter
P4 or do not operate for 15 s.
8.8 Defrosting activation in manual mode
• make sure that a retarding-provering phase, a storing phase or a
cooling manual cycle is in progress and no procedure is in
• press for 4 s: the defrosting LED will switch on.
If the evaporator probe is enabled (parameter P3 = 1) and on activa-
tion of the defrosting, the temperature of the evaporator is over that
established via parameter d2, defrosting will not be activated.
8.9 Silencing the buzzer
• make sure that no procedure is in progress
• press a key.
9 SETTINGS
9.1 Setting the day and real time
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press for 1 s: the display will show the first label available
• press or to select “rtc”.
To modify the year:
• press : the display will show “yy” followed by the two numbers
regarding the year
• press or within 15 s.
To modify the month:
• press during modification of the year: the display will show
“nn” followed by the two numbers regarding the month
• press or within 15 s.
To modify the day of the month:
• press during modification of the month: the display will show
“dd” followed by the two numbers regarding the day
• press or within 15 s.
To modify the hour:
• press during modification of the day of the month: the display
will show “hh” followed by the two numbers regarding
the hour
• press or within 15 s.
To modify the minutes:
• press during modification of the hour: the display will show
“nn” followed by the two numbers regarding the minutes
• press or within 15 s
• press : the instrument will exit the procedure.
To exit the procedure ahead of time:
• do not operate for 60 s.
Alternatively:
• press twice.
The time is displayed in 24 hour format.
If the automatic cycles are not enabled (parameter P7 = 0), the “rtc”
label will not be displayed.
9.2 Setting the configuration parameters
To access the procedure:
• make sure that no procedure is in progress
• press and for 4 s: the display will show “PA”
• press
• press or within 15 s to set “-19”
• press or do not operate for 15 s
• press and for 4 s: the display will show “SP”.
To select a parameter:
• press or
To modify a parameter:
• press
• press or within 15 s
• press or do not operate for 15 s.
To exit the procedure:
• press and for 4 s or do not operate for 60 s (any modifications
will be saved).
Shut-off the instrument power supply after the modifica-
tion of the parameters.
9.3 Restoring factory settings
To access the procedure:
• make sure that no procedure is in progress
• press and for 4 s: the display will show “PA”
• press
• press or within 15 s to set “149”
• press or do not operate for 15 s
• press and for 4 s: the display will show “dEF”
• press
• press or within 15 s to set “1”
• press or do not operate for 15 s: the display will show “dEF”
flashing for 4 s, after which the instrument will exit the
procedure
• shut-off the instrument power supply.
To exit the procedure ahead of time:
• press and for 4 s during the procedure (i.e. before setting
“1”: restore will not be performed).
Make sure that the factory settings are appropriate (see
chapter 14).
10 SIGNALS AND INDICATIONS
10.1 Signals
LED MEANING
Retarding-provering phase/cooling manual cycle LED
if it is on:
• the retarding-provering phase is in progress
• the cooling manual cycle is in progress
• the modification of the settings of the retarding-proving
phase is in progress (with the procedure indicated in
paragraph 5.3.1)
• the modification of the settings of the cooling manual
cycle is in progress (with the procedure indicated in
paragraph 7.2.1)
Storing phase LED
if it is on:
• the storing phase is in progress
• the modification of the settings of the storing phase is in
progress (with the procedure indicated in paragraph 5.4.1)
Awakening phase LED
if it is on:
• the awakening phase is in progress
• the modification of the settings of the awakening phase
is in progress (with the procedure indicated in para-
graph 5.5.1)
Provering phase/heating manual cycle LED
if it is on:
• the provering phase is in progress
• heating manual cycle is in progress
• the modification of the settings of the provering phase is in
progress (with the procedure indicated in paragraph 5.6.1)
• the modification of the settings of the heating manual
cycle is in progress (with the procedure indicated in
paragraph 6.2.1)
Slowing phase LED
if they are all on:
• the slowing phase is in progress
• the modification of the settings of the slowing phase is in
progress (with the procedure indicated in paragraph 5.7.1)
red Defrosting LED
circle if on, defrosting is in progress
Alarm LED
if on, an alarm or error is in progress
°CDegree Celsius LED
if on, the unit of measurement is the degree Celsius:
- parameter P2
°FDegree Fahrenheit LED
if on, the unit of measurement is the degree Fahrenheit:
- parameter P2
% r.H. Percentage of relative humidity LED
if on, the measurement of the size displayed will be the
percentage of relative humidity
On/stand-by LED
if on, the instrument will be in stand-by
11 ALARMS
11.1 Alarms
CODE MEANING
AH Maximum temperature alarm
Solutions:
• check the temperature of the evaporator
• see:
- parameters A0 and A1
Main consequences:
• the instrument will continue to function regularly
id Door micro switch input alarm
Solutions:
• check the causes for the activation of the input
• see parameters i0 and i1
Main consequences:
• the effect established with parameter i1
iA Safety thermostat input alarm
Solutions:
• check the causes for the activation of the input
• see parameter i2
Main consequences:
• the functioning cycle will be interrupted
• all charges will be switched off
PF Power supply shut-off alarm
Solutions:
• check the causes for the shut-off of the power supply
• see parameters P5 and P6
Main consequences:
• the effect established with parameter P5
When the cause of the alarm disappears, the instrument restores nor-
mal functioning, except for the following alarms:
• the safety thermostat input alarm (code “iA”) that requires a key to be
pressed
• the power supply shut-off alarm (code “PF”) that requires a key to be
pressed.
12 ERRORS
12.1 Errors
CODE MEANING
Pr1 Room probe error
Solutions:
• see parameter P0
• check the integrity of the probe
• check the instrument-probe connection
• check the temperature of the room
Main consequences:
• the functioning cycle will be interrupted
• all charges will be switched off
Pr2 Evaporator probe error
Solutions:
• the same as the previous case but relative to the evapora-
tor probe
Main consequences:
• defrosting will have duration of the time established with
parameter d3
Err End time and/or date error of the provering phase
Solutions:
• set the end time and date of the provering phase again
Main consequences:
• the functioning cycle will not be started
rtc Clock error
Solutions:
• set the day and real time again
Main consequences:
• the functioning cycle will be interrupted
• all charges will be switched off
When the cause of the error disappears, the instrument restores nor-
mal functioning, except for the following errors:
• the room probe error (code “Pr1”) that requires a key to be pressed
• the clock error (code “rtc”) that requires a key to be pressed and the
date and time to be set.
The display shows the end time and/or date error of the provering
phase (code “Err”) for 15 s after which the instrument passes to the
stand-by status. Pressing a key during the error causes the access to the
procedure for the modification of this variable.

Evco S.p.A. • Code 104K614E00 • page 5/7
PT • 31/09
13 TECHNICAL DATA
13.1 Technical data
Container: grey self-extinguishing.
Frontal protection rating: IP 65.
Connections: terminal board with screws (power supply, inputs
and outputs), 6-pole connector (serial port) 4-pole connector (at the
remote indicator on request); sprung extractable terminal board
(power supply, inputs and outputs) on request.
Temperature of use: from 0 to 55 °C (from 32 to 131 °F, 10 ... 90%
relative humidity without condensate).
Power supply: 12 VAC/DC (or 12-24 VAC/DC), 50/60 Hz, 3.5 VA
(approx) or 115 ... 230 VAC, 50/60 Hz, 5 VA (approx).
Keeping the clock data in the case of a power cut: 24 h with
charged battery.
Battery charging time: 2 min without interruptions (the battery is
charged by the instrument power supply).
Alarm buzzer: built-in.
Measure inputs: 2 (room probe and evaporator probe) for PTC/
NTC probes.
Digital inputs: 2 (door micro switches and safety thermostat) for nor-
mally open/normally closed contact (potential-free contact,5 V 1 mA).
Field of measurement: from -50.0 to 150.0 °C (from -50 to 300 °F)
for PTC probe, from -40.0 to 105.0 °C (from -40 to 220 °F) for NTC probe.
Resolution: 0.1 °C/1 °C/1 °F.
Digital outputs: 4 relays:
•compressor relay: 16 A res. @ 250 VAC
(change-over contact)
•humidifier relay: 8 A res. @ 250 VAC (change-
over contact)
•evaporator fan relay: 8 A res. @ 250 VAC
(NO contact)
•resistances relay: 8 A res. @ 250 VAC (change-
over contact).
The maximum current accepted on charges is 10 A.
Serial port: port for communication with the supervision system
(through a serial interface, via TTL, with MODBUS communication
protocol), with the graphic diagram (through a serial interface) or
with the programming key.
Other communication ports (on request): serial port for the
communication with the remote indicator.

Evco S.p.A. • Code 104K614E00 • page 6/7
14 CONFIGURATION PARAMETERS
14.1 Configuration parameters
PARAM. MIN. MAX. U. M. DEF.
SEt0 rC1 rC2 °C/°F (1) -2.0
SEt1 rC1 rC2 °C/°F (1) 4.0
SEt2 rH1 rH2 °C/°F (1) 16.0
SEt3 rH1 rH2 °C/°F (1) 26.0
SEt4 rH1 rH2 °C/°F (1) 15.0
SEt5 rH1 rH2 °C/°F (1) 26.0
SEt6 rC1 rC2 °C/°F (1) -2.0
PARAM. MIN. MAX. U. M. DEF.
Ur0 rU5 rU6 % 0
Ur1 rU5 rU6 % 0
Ur2 rU5 rU6 % 70
Ur3 rU5 rU6 % 75
Ur4 rU5 rU6 % 75
Ur5 rU5 rU6 % 0
PARAM. MIN. MAX. U. M. DEF.
dur0 00:00 23:59 h:min 04:00
dur2 00:00 23:59 h:min 02:00
dur3 00:00 23:59 h:min 02:00
dur5 00:00 23:59 h:min 00:00
PARAM. MIN. MAX. U. M. DEF.
CA1 -25.0 25.0 °C/°F (1) 0.0
CA2 -25.0 25.0 °C/°F (1) 0.0
P0 0 1 - - - - 1
P1 0 1 - - - - 1
P2 0 1 - - - - 0
P3 0 1 - - - - 1
P4 0 5 - - - - 2
P5 1 30 min 15
P6 0 2 - - - - 1
P7 0 1 - - - - 1
P8 0 1 - - - - 0
P9 0 1 - - - - 1
PARAM. MIN. MAX. U. M. DEF.
rC0 0.1 15.0 °C/°F (1) 3.0
rC1 -99.0 rC2 °C/°F (1) -3.0
rC2 rC1 99.0 °C/°F (1) 15.0
rC3 0.0 10.0 °C/°F (1) 3.0
rC4 0.0 10.0 °C/°F (1) 1.0
rC5 0.0 10.0 °C/°F (1) 1.0
PARAM. MIN. MAX. U. M. DEF.
rH0 0.1 15.0 °C/°F (1) 3.0
rH1 0.0 rH2 °C/°F (1) 0.0
rH2 rH1 99.0 °C/°F (1) 35.0
rH3 0.0 10.0 °C/°F (1) 1.0
rH4 0.0 10.0 °C/°F (1) 3.0
rn1 1 3 - - - - 1
rn2 1 3 - - - - 1
PARAM. MIN. MAX. U. M. DEF.
rU1 0.0 90.0 °C/°F (1) 10.0
rU2 30 600 s 60
rU3 0 rU2 s 30
rU4 0 1 - - - - 0
rU5 0 rU6 % 0
rU6 rU5 100 % 100
WORK SET-POINT
work set-point during the retarding-provering phase; also see rC4
work set-point during the storing phase; also see rC4
work set-point during the awakening phase; also see rC3 and rH3
work set-point during the provering phase; also see rC3 and rH3
work set-point during the slowing phase; also see rC5 and rH4
work set-point during the heating manual cycle, see also rH3
work set-point during the cooling manual cycle; see also rC4
PERCENTAGE OF RELATIVE HUMIDITY
percentage of relative humidity during the retarding-provering phase (intended as percentage of time rU3); see also rU1
percentage of relative humidity during the storing phase (intended as percentage of time rU3); see also rU1
percentage of relative humidity during the awakening phase (intended as percentage of time rU3); see also rU1
percentage of relative humidity during the provering phase (intended as percentage of time rU3); see also rU1
percentage of relative humidity during the slowing phase (intended as percentage of time rU3); see also rU1
percentage of relative humidity during the heating manual cycle (intended as percentage of time rU3); see also rU1
DURATION OF THE PHASES
duration of the retarding-provering phase
duration of the awakening phase
duration of the provering phase
duration of the activation of the buzzer and the end of the duration of the heating manual cycle
MEASURE INPUTS
room probe offset
evaporator probe offset
type of probe
0 = PTC
1 = NTC
degree Celsius decimal point (for the size displayed during normal functioning)
1 = YES
temperature unit of measurement (2)
0=°C
1=°F
enabling the evaporator probe
1 = YES
size displayed during normal functioning
0 = room temperature if a functioning cycle is in progress
display off if the instrument is in stand-by
1 = end time of the provering phase if an automatic cycle is in progress
display off if the instrument is in stand-by (3)
2 = room temperature (for 3 s) alternately with the end time of the provering phase (for 1 s) if an automatic cycle is in progress
display off if the instrument is in stand-by (3)
3 = room temperature if a functioning cycle is in progress
real time if the instrument is in stand-by
4 = end time of the provering phase if an automatic cycle is in progress
real time if the instrument is in stand-by (4)
5 = room temperature (for 3 s) alternately with the end time of the provering phase (for 1 s) if an automatic cycle is in progress
real time if the instrument is in stand-by (4)
duration of a power cut (that occurs during a functioning cycle) after which the cycle is interrupted (only if P6=2)
functioning of the instrument when the power supply is restored after shut-off that occurs during a functioning cycle
0 = the cycle will be interrupted
1 = the cycle will be restored
2 = depending on P5
enabling of the automatic cycle
1 = YES
blocking the modification of the automatic cycle settings (operate with the procedures indicated in chapter 5).
1 = YES
enabling of the display of the end time and date of the provering phase in succession (instead of just the end time of the provering phase)
during the modification of the automatic cycle settings (operate with the procedures indicated in chapter 5)
1 = YES
COOLING REGULATOR
differential of the rC3, rC4 and rC5 parameters
minimum value of the SEt0, SEt1 and SEt6 parameters
maximum value of the SEt0, SEt1 and SEt6 parameters
value of the neutral zone for cooling functioning during the awakening phase and during the provering phase (relative to the work set-point, i.e. “SEt2 and SEt3 + rC3”); see
also rC0
value of the neutral zone for cooling functioning during the retarding provering phase, during the storage phase and during the cooling manual cycle (relative to the work
set-point i.e. "SEt0, SEt1 or SEt6 + rC4"); see also rC0
value of the neutral zone for cooling functioning during the slowing phase (relative to the work set-point, i.e. “SEt4 + rC5”); see also rC0
HEATING REGULATOR
differential of the rH3 and rH4 parameters
minimum value of the SEt2, SEt3, SEt4 and SEt5 parameters
maximum value of the SEt2, SEt3, SEt4 and SEt5 parameters
value of the neutral zone for heating functioning during the awakening phase and during the provering phase and during the heating manual cycle (relative to the work set-
point, i.e. “SEt2, SEt3 and SEt5 + rH3”); see also rH0
value of the neutral zone for heating functioning during the slowing phase (relative to the work set-point, i.e. “SEt4 + rH5”); see also rH0
number of steps by which the “room temperature on activation of the awakening phase - SEt2” difference is divided, depending on the time dur2, for the calculation of the
work set-point during the same phase (5)
number of steps by which the “room temperature on activation of the provering phase - SEt3” difference is divided, depending on the time dur3, for the calculation of the work
set-point during the same phase (6)
HUMIDIFIER
temperature of the room below which humidification is not available (7)
cycle time for humidifier switch-on; see also rU3
duration of humidifier switch-on (during time rU2) such to cause 100% relative humidity
enabling of setting the percentage relative humidity during the modification of the settings of the retarding-provering phase and during modification of the storing phase
settings (with the procedures indicated in paragraphs 5.3.1 and 5.4.1)
1 = YES
minimum value of the Ur0, Ur1, Ur2, Ur3, Ur4 and Ur5 parameters
maximum value of the Ur0, Ur1, Ur2, Ur3, Ur4 and Ur5 parameters

EVCO S.p.A. This publication is the exclusive property of Evco, which prohibits distribution, if not expressly authorised by Evco itself.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY Evco does not assume any liability regarding features, the technical data and possible errors stated in this document.
Telephone 0437-852468 • Fax 0437-83648 Evco cannot be held responsible for damage caused by failure to comply with the recommendations.
[email protected] • www.evco.it Evco reserves the right to make modifications without forewarning without jeopardising the essential functionality and safety features.
Evco S.p.A. • Code 104K614E00 • page 7/7
PARAM. MIN. MAX. U. M. DEF.
C0 0 240 min 2
C1 0 240 min 2
C2 0 240 min 2
C3 0 240 s 0
PARAM. MIN. MAX. U. M. DEF.
d0 0 99 h 6
d2 -99.0 99.0 °C/°F (1) 2.0
d3 0 120 min 30
PARAM. MIN. MAX. U. M. DEF.
A0 0.0 99.0 °C/°F (1) 55.0
A1 0 1 - - - - 1
PARAM. MIN. MAX. U. M. DEF.
F0 0 1 - - - - 0
F1 0 1 - - - - 0
F2 0 1 - - - - 1
F3 0 1 - - - - 1
F4 0 1 - - - - 1
F5 0 1 - - - - 0
PARAM. MIN. MAX. U. M. DEF.
i0 0 1 - - - - 0
i1 0 2 - - - - 2
i2 0 1 - - - - 0
PARAM. MIN. MAX. U. M. DEF.
LA 1 247 - - - - 247
Lb 0 3 - - - - 2
LP 0 2 - - - - 2
PARAM. MIN. MAX. U.M. DEF.
E901--- 1
(1) the unit of measurement depends on parameter P2
(2) appropriately set the parameters relative to the regulators after the modification of parameter P2
(3) if the parameter P4 is set at 1 or 2 and a heating or cooling manual cycle is in progress, the instrument will function as if the parameter P4 is set at 0
(4) if the parameter P4 is set at 4 or 5 and a heating or cooling manual cycle is in progress, the instrument will function as if the parameter P4 is set at 3
(5) for example: if on activation of the awakening phase, the room temperature is 4.0 °C, the SEt2 parameter is set at 16.0, the dur2 parameter is set at 02:00 h:min and the rn1 parameter is set at 2, for the first 60 min
of the awakening phase the work set-point will be 10.0 °C and for the remaining 60 min it will be 16.0 °C
(6) for example: if on activation of the provering phase, the room temperature is 16.0 °C, the SEt3 parameter is set at 26.0, the dur2 parameter is set at 02:00 h:min and the rn2 parameter is set at 2, for the first 60 min
of the awakening phase the work set-point will be 21.0 °C and for the remaining 60 min it will be 26.0 °C
(7) humidification is not available during the cooling manual cycle
(8) the parameter has effect also after the interruption of the power supply, which takes place when a functioning cycle is in progress
(9) the time established via the parameter is counted also when the instrument is in the stand-by status
(10) defrosting is only activated during the retarding-provering phase, during the storing phase and during the cooling manual cycle. If at the end of a storing phase defrosting is in progress, this will be interrupted
on start-up of the awakening phase (during the phases and functioning cycles in which the defrosting is not activated, the count of the defrosting interval remains frozen)
(11) the instrument memorises the count of the defrosting every 30 mins. The modification of parameter d0 has effect from the end of the previous defrosting interval or from the activation of defrosting in manual mode.
(12) the differential of the A0 parameter is 2.0 °C/4 °F.
COMPRESSOR PROTECTIONS
compressor switch-on delay from instrument switch-on (8)
minimum time between the two consecutive compressor switch-ons (9)
minimum duration of compressor switch-off (9)
minimum duration of compressor switch-on
DEFROSTING (10)
defrosting interval (11)
0 = defrosting will never be activated at intervals
defrosting end temperature (only if P3 = 1); see also d3
if P3 = 0, defrosting duration
if P3 = 1, maximum defrosting duration; see also d2
0 = defrosting will never be activated
TEMPERATURE ALARMS
evaporator temperature above which the maximum temperature alarm is activated (code “AH”); see also A1 (12)
enabling of the maximum temperature alarm (code “AH”); se also A0
1 = YES
EVAPORATOR FAN
evaporator fan activity during the retarding-provering phase and during the cooling manual cycle
0 = parallel to the compressor
1=on
evaporator fan activity during the storing phase
0 = parallel to the compressor
1=on
evaporator fan activity during the awakening phase
0 = parallel to the compressor
1=on
evaporator fan activity during the provering phase and during the heating manual cycle
0 = parallel to the compressor
1=on
evaporator fan activity during the slowing phase
0 = parallel to the compressor
1=on
evaporator fan activity during defrosting
0 = off
1=on
DIGITAL INPUTS
door micro switch input contact type
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
effect caused by the activation of the door micro switch input
0 = no effect
1 = the resistances and the evaporator fan are off. The display shows the code “id” flashing and the buzzer will be activated (until the input is deactivated)
2 = all charges will be switched off. The display shows the code “id” flashing and the buzzer will be activated (until the input is deactivated)
type of contact of the safety thermostat input
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
SERIAL NETWORK (MODBUS)
instrument address
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
parity
0 = none (no parity)
1 = odd
2 = even
RESERVED
reserved
Table of contents
Other Evco Controllers manuals

Evco
Evco Vcolor 318 M User guide

Evco
Evco EVBOX Light JS200 User manual

Evco
Evco EVK004 User manual

Evco
Evco Vcolor 318 M User guide

Evco
Evco C-PRO NANO User manual

Evco
Evco EVJH95 User manual

Evco
Evco C-pro 3 giga User manual

Evco
Evco EV3 CHIL User manual

Evco
Evco Vcolor 379 User guide

Evco
Evco EVF215 User manual

Evco
Evco EV3802 User manual

Evco
Evco Vcolor 818 User guide

Evco
Evco EVF204 User manual

Evco
Evco EV3B33N7VXRX04 User manual

Evco
Evco EV3802 User manual

Evco
Evco EV9376 User manual

Evco
Evco EVBOX Light J500 Series User manual

Evco
Evco c-pro 3 micro AHU User manual

Evco
Evco EVX225 User manual

Evco
Evco C-PRO NANO Series User manual