manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Evco
  6. •
  7. Controllers
  8. •
  9. Evco EV3401 User manual

Evco EV3401 User manual

EVCOS.p.A.|EV3401M|Instructionsheetver.1.0|Code1043401ME103|Page1of2|PT46/17
EV3401 Multi-sensor Universal controllers with one regulation output for industrial applications
EN
ENGLISH
- power supply 230 VAC or 12-24 VAC/DC (according to the model)
- multi-sensor input (PTC/NTC/J/K/Pt 100/Pt 1000/Ni 120/0-20 mA/4-20 mA/0-10 V/
2-10 V)
- multi-purpose input
- K1 relay 16 A res. @ 250 VAC
- alarm buzzer
- TTL MODBUS slave port for programming key or for TTL/RS-485 (BMS) serial interface
- hot or cold mode regulation.
1 MEASUREMENTS AND INSTALLATION
Measurements in mm (in); 59.0 (2 5/16) depth with fixed screw terminal blocks, 81,5
(3 3/16) depth with plug-in screw terminal blocks.
To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
- the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in);
- ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section;
- do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks;
- in compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
N.B.
- use cables of an adequate section for the current running through them.
- ensure that the thermocouple is properly insulated from contact with metal parts or
use already insulated thermocouples.
- if necessary, extend the thermocouple cable using a compensating cable.
- to reduce any electromagnetic interference locate the power cables as far away as
possible from the signal cables.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- if using an electrical or pneumatic screwdriver, adjust the tightening torque;
- if the device has been moved from a cold to a warm place, humidity may have caused
condensation to form inside. Wait about an hour before switching on the power;
- make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS;
- disconnect the power supply before carrying out any type of maintenance;
- do not use the device as safety device;
- for repairs and for further information, contact the EVCO sales network.
3 FIRST-TIME USE
1. Install following the instructions given in the section MEASUREMENTS AND
INSTALLATION.
2. Power up the device as set out in the section ELECTRICAL CONNECTION: an internal
test will start up.
The test normally takes a few seconds; when it is finished the display will switch off.
3. Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use.
PAR.
DEF.
PARAMETER
MIN... MAX.
SP 0.0 setpoint r1... r2
P0
2
type of probe
set the parameter before
connecting the probe
0 = PTC 1 = NTC
2 = J 3 = K
4 =
Pt 100 3 wires
5 =
Pt 100 3 wires
6 =
Pt 1000 3 wires
7 =
Pt 1000 3 wires
8 = 4-20 mA 9 = 0-20 mA
10= 2-10 V 11= 0-10 V
12=
Ni 120 3 wires
13=
Ni 120 2 wires
P2 0 temperature measurement unit
0 = °C 1 = °F
r5
0
hot or cold mode regulation regulator
0 = cold mode
1 = hot mode
Then check that the remaining settings are appropriate; see the section
CONFIGURATION PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION
without powering up the device.
6. When connecting to an RS-485 network, connect the EVIF22TSX interface; see the
relative instruction sheets.
7. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1.
If POF = 1 (default), touch the ON/STAND-BY key for 4s.
If the device is switched on, the display will show the P5 value ("regulation temperature"
default); if the display shows an alarm code, see the section ALARMS.
LED
ON
OFF
FLASHING
OUT1
regulator active
-
- regulator protection active
- setpoint being set
unused
-
-
OUT2
unused
-
-
alarm active
-
-
unused
-
-
device switched off
device switched on
device being switched on/off
°C/°F
temperature display
-
-
% percentage display
-
-
Bar pressure display
-
-
When 30s have elapsed without the keys being pressed, the display will show the "Loc" label
and the keypad will lock automatically.
4.2 Unlocking the keypad
Touch a key for 1s: the display will show the label “UnL”.
4.3 Setting the setpoint
Check that the keypad is not locked.
1.
Touch the SET key: the display will show the label “SP”.
2.
Touch the UP or DOWN key within 15s to set the value within the
limits r1 and r2 (default "0... 350”).
3.
Touch the SET key (or take no action for 15s).
4.4 Silencing the buzzer (if A13 = 1)
Touch a key.
5 FUNCTION MODES
Cold mode regulation (r5 = 0).
Hot mode regulation (r5 = 1).
6 ADDITIONAL FUNCTIONS
6.1 Displaying the number of start-ups of the relay
Check that the keypad is not locked.
1.
Touch the DOWN key for 4s.
2.
Touch the UP or DOWN key within 15s to select a label.
LAB.
DESCRIPTION
nS1
display of the number of start-ups of the K1 relay in thousands
3.
Touch the SET key.
4.
Touch the ON/STAND-BY key (or take no action for 60s) to exit
the procedure.
6.2 Displaying the temperature detected by the regulation probe
Check that the keypad is not locked.
1.
Touch the DOWN key for 4s.
2.
Touch the UP or DOWN key within 15s to select a label.
LAB.
DESCRIPTION
Pb1
regulation temperature
3.
Touch the SET key.
4.
Touch the ON/STAND-BY key (or take no action for 60s) to exit
the procedure.
7 SETTINGS
7.1 Setting configuration parameters
N.B.
Changing parameter P2 from °C to °F (and vice versa) causes the value of the
parameters whose unit of measurement is °C or °F to be changed automatically.
1.
Touch the SET key for 4s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set the PAS value
(default "-19").
4.
Touch the SET key (or take no action for 15s): the display will
show the label “SP”.
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15s to set the value.
8.
Touch the SET key (or take no action for 15s).
9.
Touch the SET key for 4s (or take no action for 60s) to exit the
procedure.
7.2 Restoring factory settings (default) and saving customised settings
N.B.
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- Saving customised settings overwrites the factory settings.
1.
Touch the SET key for 4s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set the value.
VAL.
DESCRIPTION
149 value for restoring the factory information (default)
161 value for saving customised settings
4. Touch the SET key (or take no action for 15s): the display will
show the label “dEF” (for setting the “149” value) or the label
“MAP” (for setting the “161” value)
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15s to set "4".
7. Touch the SET key (or take no action for 15s): the display will
show “- - -“ flashing for 4s, after which the device will exit the
procedure.
8. Disconnect the device from the power supply.
9.
Touch the SET key for 2s before action 6 to exit the procedure
beforehand.
8 CONFIGURATION PARAMETERS
N.
PAR.
DEF.
SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOGUE INPUTS
MIN... MAX.
2 CA1 0.0 regulation probe offset
-25... 25 °C/°F
3
P0
2
type of probe
0 = PTC 1 = NTC
2 = J 3 = K
4 = Pt 100 3 wires
5 = Pt 100 2 wires
6 = Pt 1000 3 wires
7 = Pt 1000 2 wires
8 = 4-20 mA 9 = 0-20 mA
10= 2-10 V 11= 0-10 V
12= Ni 120 3 wires
13= Ni 120 2 wires
4
P1
0
enable decimal point °C
0 = no 1 = yes
if P0 = 2 or 3, not effective
if P0 = 8... 11, position of
decimal point:
0 = none
1 = tens digit
5
P2
0
measurement unit
0 = °C 1 = °F
2 = % 3 = bar
4 = none
options 2… 4 effective only on
LEDs and if P0 = 8… 11
6
P3
0.0
minimum transducer calibration
value
-199... 999 points
7
P4
100
maximum transducer calibration
value -199... 999 points
8
P5
0
value displayed
0 = regulation temperature
1 = setpoint
9 P8 5 display refresh time
0... 250 s : 10
N. PAR. DEF. REGULATION
MIN... MAX.
10
r0 2.0 setpoint differential 1... 99 °C/°F
11
r1 0.0 minimum setpoint
-199 °C/°F... r2
12
r2 350 maximum setpoint
r1... 999 °C/°F
13
r5
0
hot or cold mode regulation
regulator
0 = cold mode
1 = hot mode
14
r11
0.0
digital input second setpoint
-199... 999 °C/°F
setpoint + r11
N. PAR. DEF. REGULATOR PROTECTION
MIN... MAX.
15
C1
0
minimum time between two
power-ons of regulator 0... 240 min
16
C2
0
minimum time off and delay from
power-on of regulator
0... 240 min
17
C3 0 minimum time on regulator
0... 240 s
18
C4
0
regulator activity during
regulation probe alarm 0 = off 1 = on
N. PAR. DEF. ALARMS
MIN... MAX.
19
A1 0.0 temperature alarm threshold
-199... 999 °C/°F
20
A2
0
temperature alarm type
0 = disabled
1 = absolute minimum
2 = absolute maximum
3 = minimum relative to SP
4 = maximum relative to SP
21
A3 0 temperature alarm delay
0... 999 min
22
A7
0
temperature alarm delay after
modifying setpoint and power-on
0... 999 min
23
A8
0
additional alarm signal delay
after silencing if the condition
persists
0... 999 min
24
A11
2.0
temperature alarm switch off
differential 1... 99 °C/°F
25
A13 1 enable alarm buzzer
0 = no 1 = yes
N. PAR. DEF. DIGITAL INPUTS
MIN... MAX.
26
i5
0
multi-purpose input function
0 = disabled
1 = alarm iA
2 = alarm iA + regulator off
3 =
switches device on/off
4 = modifies setpoint
27
i6
0
multi-purpose input activation
0 = with contact closed
1 = with contact open
28
i7 0 multi-purpose input alarm delay
0... 999 s
N. PAR. DEF. SECURITY
MIN... MAX.
29
POF 1 enable ON/STAND-BY key
0 = no 1 = yes
30
PAS -19 password -99... 999
N. PAR. DEF. MODBUS MIN... MAX.
31
LA 247 MODBUS address
1... 247
32
Lb
3
MODBUS baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
even
EVCOS.p.A.|EV3401M|Instructionsheetver.1.0|Code1043401ME103|Page2of2|PT46/17
9 ALARMS
COD. DESCRIPTION
RESET
TO CORRECT
Pr1
regulation probe alarm
automatic
- check P0
- check probe integrity
- check electrical connection
AL
temperature alarm
automatic
check A1, A2 and A3
iA multi-purpose input alarm
automatic check i5 and i6
10 TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container
Black, self-extinguishing
Category of heat and fire resistance
D
Measurements
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks
75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
3 3/16 in) with plug-in screw terminal blocks
Mounting methods for the control device
To be fitted to a panel, snap-in brackets
provided
Degree of protection provided by the
covering
IP65 (front)
Connection method
Fixed screw terminal blocks
for wires up to 2.5 mm²
Plug-in screw terminal blocks
for wires up to 2.5 mm² (on
request)
Pico-Blade connector
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)
Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft)
Digital outputs: 10 m (32.8 ft)
Operating temperature
From -5 to 55 °C (from 23 to 131 °F)
Storage temperature
From -25 to 70 °C (from -13 to 158 °F)
Operating humidity
Relative humidity without condensate from 10
to 90%
Pollution status of the control device
2
Compliance:
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH (EC) Regulation
1907/2006
EMC 2014/30/EU
LVD 2014/35/EU
Power supply:
230 VAC (+10 % -15 %), 50/60 Hz (±3 Hz), max. 4 VA in EV3... M7
12-24 VAC/DC (+10% -15%), 50/60 Hz (±3 Hz), max. 5 VA/3W in EV3... M3
Earthing methods for the control device
None
Rated impulse-withstand voltage
4 KV in EV3... M7; 330 V in EV3... M3
Over-voltage category
III in EV3... M7; I in EV3... M3
Software class and structure
A
Analogue inputs
1 for PTC, NTC, Pt 100, Pt 1000 or Ni 120
probes, J or K thermocouples, 0-20 mA, 4-20
mA, 0-10 V or 2-10 V transducers (regulation
probe)
PTC probes
Measurement field:
from -50 to 150
℃
(from -58 to 302 °F)
Resolution:
0.1 °C (1 °F)
NTC probes
Measurement field:
from -40 to 110 °C (from -58 to 230 °F)
Resolution:
0.1 °C (1 °F)
Pt 100 and Pt
1000 probes
Measurement field:
from -100 to 650
℃
(from -148 to 999 °F)
Resolution:
0.1 °C (1 °F)
Ni 120 probes
Measurement field:
from -80 to 300 °C (from -112 to 999 °F)
Resolution:
0.1 °C (1 °F)
J thermo-
couples
Measurement field:
from 0 to 700 °C (from 32 to 999 °F)
Resolution:
1 °C (1 °F)
K thermo-
couples
Measurement field:
from 0 to 999 °C (from 32 to 999 °F)
Resolution:
1 °C (1 °F)
0-20 mA, 4-20 mA, 0-10 V and 2-10 V
transducers:
can be configured
Digital inputs
1 dry contact (multi-purpose), not available if the analogue
input is configured for Pt 100, Pt 1000 or NI 120 3 wires
Dry contact
Contact type:
3.3 V, 1 mA
Protection:
none
Digital outputs
1 with electromechanical relay (K1 relay)
K1 relay
SPDT, 16 A res. @ 250 VAC
Type 1 or Type 2 Actions
Type 1
Additional features of Type 1 or Type 2
actions
C
Displays
LED display, 3 digit, with function icons
Alarm buzzer
Built-in
Communications ports
1 TTL MODBUS slave port for programming
key or for serial interface (BMS)
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic equipment.
This document and the solutions contained therein are the intellectual property of EVCO and thus
protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the
full or partial reproduction and disclosure of the content other than with the express approval of EVCO.
The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the
device.
EVCO accepts no liability for any possible errors in this document and reserves the right to make any
changes, at any time without prejudice to the essential functional and safety features of the equipment.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
telefono 0437 8422 | fax 0437 83648
email [email protected] | web www.evco.it

Other Evco Controllers manuals

Evco Vcolor 229 Series User manual

Evco

Evco Vcolor 229 Series User manual

Evco C-pro 3 giga User manual

Evco

Evco C-pro 3 giga User manual

Evco EVK004 User manual

Evco

Evco EVK004 User manual

Evco EVJ 700 User guide

Evco

Evco EVJ 700 User guide

Evco Vcolor 338 L User guide

Evco

Evco Vcolor 338 L User guide

Evco Vcolor 318 M User guide

Evco

Evco Vcolor 318 M User guide

Evco EV3221 User manual

Evco

Evco EV3221 User manual

Evco EV3 200 WEB User manual

Evco

Evco EV3 200 WEB User manual

Evco EVJ 500 Series User manual

Evco

Evco EVJ 500 Series User manual

Evco Vcolor 869 User guide

Evco

Evco Vcolor 869 User guide

Evco EV3B23 User manual

Evco

Evco EV3B23 User manual

Evco C-PRO MEGA Instructions for use

Evco

Evco C-PRO MEGA Instructions for use

Evco EV9376 User manual

Evco

Evco EV9376 User manual

Evco EV3 Mix User manual

Evco

Evco EV3 Mix User manual

Evco c-pro 3 OEM HRV User guide

Evco

Evco c-pro 3 OEM HRV User guide

Evco Vcolor 579 User guide

Evco

Evco Vcolor 579 User guide

Evco C-PRO CLIMA SYSTEMA User guide

Evco

Evco C-PRO CLIMA SYSTEMA User guide

Evco EVXV 800 Series User guide

Evco

Evco EVXV 800 Series User guide

Evco EVJ825P9VX3 User guide

Evco

Evco EVJ825P9VX3 User guide

Evco EV3B94 User manual

Evco

Evco EV3B94 User manual

Evco c-pro 3 NODE kilo User manual

Evco

Evco c-pro 3 NODE kilo User manual

Evco EV3B24 User manual

Evco

Evco EV3B24 User manual

Evco c-pro 3 OEM User manual

Evco

Evco c-pro 3 OEM User manual

Evco Vcolor 819 User guide

Evco

Evco Vcolor 819 User guide

Popular Controllers manuals by other brands

Heath Zenith Dual Brite SL-5512 user manual

Heath Zenith

Heath Zenith Dual Brite SL-5512 user manual

MPPT MPPT-DC Series user manual

MPPT

MPPT MPPT-DC Series user manual

IBS Batching Master 110 installation guide

IBS

IBS Batching Master 110 installation guide

LS Smart I/O datasheet

LS

LS Smart I/O datasheet

Ruska Instrument 7215 user manual

Ruska Instrument

Ruska Instrument 7215 user manual

Ingersoll-Rand ESCB20 manual

Ingersoll-Rand

Ingersoll-Rand ESCB20 manual

Athena S Series instruction manual

Athena

Athena S Series instruction manual

Martinsound MonitorMAX user manual

Martinsound

Martinsound MonitorMAX user manual

Sungrow EMS300 user manual

Sungrow

Sungrow EMS300 user manual

Lindab UltraLink FTCU technical information

Lindab

Lindab UltraLink FTCU technical information

MULTISPAN APFC 112 user manual

MULTISPAN

MULTISPAN APFC 112 user manual

RS 846-452 installation instructions

RS

RS 846-452 installation instructions

Brink Air for life Installation regulations

Brink

Brink Air for life Installation regulations

Siemens SQS65 Mounting instructions

Siemens

Siemens SQS65 Mounting instructions

Tern CAN-Engine Technical manual

Tern

Tern CAN-Engine Technical manual

EVC IDrive quick start guide

EVC

EVC IDrive quick start guide

Emerson Fisher FIELDVUE DVC6005 Series quick start guide

Emerson

Emerson Fisher FIELDVUE DVC6005 Series quick start guide

Milesight UC300 user guide

Milesight

Milesight UC300 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.