FAAC 624 BLD User manual

624BLD

11
CE DECLARATION OF CONFORMITY
Manufacturer: FAAC S.p.A.
Address: Via Benini, 1 - 40069 Zola Predosa BOLOGNA - ITALY
Declares that: 624BLD control board,
• conforms to the essential safety requirements of the following directives:
73/23/CEE and subsequent amendment 93/68/CEE.
89/336/CEE and subsequent amendment 92/31/CEE and 93/68/CEE
Additional note:
This product underwent tests in a typical uniform configuration
(all products manufactured by FAAC S.p.A.).
Bologna, 01 October 2005
The Managing Director
A. Bassi
1) ATTENTION! To ensure the safety of people, it is important that you read
all the following instructions. Incorrect installation or incorrect use of the
product could cause serious harm to people.
2) Carefully read the instructions before beginning to install the product.
3) Do not leave packing materials (plastic, polystyrene, etc.) within reach of
children as such materials are potential sources of danger.
4) Store these instructions for future reference.
5) This product was designed and built strictly for the use indicated in this
documentation. Any other use, not expressly indicated here, could
compromise the good condition/operation of the product and/or be a
source of danger.
6) FAAC declines all liability caused by improper use or use other than that for
which the automated system was intended.
7) Do not install the equipment in an explosive atmosphere: the presence of
inflammable gas or fumes is a serious danger to safety.
8) The mechanical parts must conform to the provisions of Standards EN 12604
and EN 12605.
For non-EU countries, to obtain an adequate level of safety, the Standards
mentioned above must be observed, in addition to national legal
regulations.
9) FAAC is not responsible for failure to observe Good Technique in the
construction of the closing elements to be motorised, or for any deformation
that may occur during use.
10) The installation must conform to Standards EN 12453 and EN 12445.
For non-EU countries, to obtain an adequate level of safety, the Standards
mentioned above must be observed, in addition to national legal
regulations.
11) Before attempting any job on the system, cut out electrical power .
12) The mains power supply of the automated system must be fitted with an
all-pole switch with contact opening distance of 3mm or greater. Use of a
6A thermal breaker with all-pole circuit break is recommended.
13) Make sure that a differential switch with threshold of 0.03 A is fitted upstream
of the system.
14) Make sure that the earthing system is perfectly constructed, and connect
metal parts of the means of the closure to it.
15) The safety devices (EN 12978 standard) protect any danger areas against
mechanical movement Risks, such as crushing, dragging, and shearing.
16) Use of at least one indicator-light (e.g. FAACLIGHT ) is recommended for every
system, as well as a warning sign adequately secured to the frame structure,
in addition to the devices mentioned at point “15”.
17) FAAC declines all liability as concerns safety and efficient operation of
the automated system, if system components not produced by FAAC are
used.
18) For maintenance, strictly use original parts by FAAC.
19) Do not in any way modify the components of the automated system.
20) The installer shall supply all information concerning manual operation of
the system in case of an emergency, and shall hand over to the user the
warnings handbook supplied with the product.
21) Do not allow children or adults to stay near the product while it is
operating.
22) Keep remote controls or other pulse generators away from children, to prevent
the automated system from being activated involuntarily.
23) Transit is permitted only when the automated system is idle.
24) The user must not attempt any kind of repair or direct action whatever and
contact qualified personnel only.
25) Maintenance: check at least every 6 months the efficiency of the system, particularly
the efficiency of the safety devices (including, where foreseen, the operator thrust
force) and of the release devices.
26) Anything not expressly specified in these instructions is not permitted.
WARNINGS FOR THE INSTALLER
GENERAL SAFETY OBLIGATIONS

12
-
DL
F
+
LED
F2
J4
J5
J6 J3
J1
J2
J11C
J11B J11A
J8
J9
F1
TF1
EMERG - DL5
STOP - DL4
FSW - DL3
CLOSE - DL2
OPEN - DL1
PIVOT - DL8
FCA - DL6
FCC - DL7
LOOP DETECTOR
1. WARNINGS
Attention: Before attempting any work on the control unit (connections, maintenance), always turn off power.
- Install, upstream of the system, a differential thermal breaker with adequate tripping threshold.
- Connect the earth cable to the terminal on the J9 connector of the unit (see fig. 2).
- Always separate power cables from control and safety cables (push-button, receiver, photocells, etc.). To avoid any electrical noise, use
separate sheaths or a screened cable (with the screen earthed).
CONTROL UNIT 624 BLD
3. LAYOUT AND COMPONENTS of 624 BLD
Power supply voltage
230 Vac (+6% -10%) - 50 Hz
Absorbed power
7 W
Motor max. load
300 W
Power supply for ac-
cessories
24 Vdc
Accessories max.
current
500 mA
Ambient temperature
-20°C - +55°C
Fuses
F1 = F 5A - 250V F2 = T 0.8A - 250V
Function logics
Automatic, Automatic 1, Semiautomatic,
Parking, Parking-Automatic,
Condo, Condo-automatic
FAAC-CITY, Dead-man, Remote, Custom
Work time
Programmable (from 0 to 4 minutes)
Pause time
Programmable (from 0 to 4 minutes)
Motor power
Programmable on 50 levels
Terminal board inputs
Loop1, Loop2, Open, Close,
Closing safety devices, Stop, Emergency,
Power supply 230Vac + Earth
Connector inputs
Opening and closing limit-switch, Detector
Motor capacitor, Beam detachment sensor
Terminal board
outputs
Flashing light, Fan, Motor,
Power supply 24 Vdc, Fail-safe, Status output,
Indicator light 24 Vdc, BUS
Rapid connector
5-pin Minidec board coupling, Decoder,
Receiver RP/RP2
Programming
No. 3 keys (+, -, F) and display
Programmable
functions
Logics, Pause Time, Power, Loop 1 and 2, Thrust
torque, Pre-flashing, Slow closure, Deceleration
time, Work time, Indicator light output, Fail-safe
output, Status output, BUS output, Assistance
request
2. TECHNICAL SPECIFICATIONS
3.1 DESCRIPTION OF COMPONENTS
DL SIGNALS AND PROGRAMMING DISPLAY
LED INPUT STATUS CONTROL LEDs
J1 LOW-VOLTAGE TERMINAL BOARD
J2 TERMINAL BOARD FOR CONNECTION OF MOTOR,
FLASHING LIGHT AND FAN
J3 OPENING LIMIT-SWITCH CONNECTOR
J4 CONNECTOR: DECODER MINIDEC / RP RECEIVER
J5 CLOSING LIMIT-SWITCH CONNECTOR
J6 CONNECTOR FOR ROD BREAKING SENSOR
J8 CONNECTOR FOR MOTOR THRUST CAPACITOR
J9 TERMINAL-BOARD FOR 230 VAC POWER SUPPLY
J11 CONNECTOR EXTERNAL LOOP DETECTOR
F1 FUSE FOR MOTORS AND TRANSFORMER PRIMARY
WINDING (F 5A)
F2
FUSE FOR LOW VOLTAGE AND ACCESSORIES (T 800mA)
FPROGRAMMING PUSH-BUTTON ”F”
+PROGRAMMING PUSH-BUTTON ”+”
-PROGRAMMING PUSH-BUTTON ”-”
TF1 TRANSFORMER
Fig. 1

13
252321
LNPE
26242220
191816 17151412 1310 118 96 74 52 31
230Vac
50Hz
J1
J2
J8
J9
OPEN
CLOSE
STOP
EMERGENCY
230Vac
max 60W
24Vdc
3W
J6
J3
J5
FCC FCA
4. ELECTRICAL CONNECTIONS
To connect the
photocells and
safety devices,
consult paragraph
4.1.
BLUE
Before you connect the photocells (or other devices) we advise you
to select the type of operation according to the movement zone
they have to protect.
Closing safety devices:
they are tripped only during the barrier
closing movement, and, therefore, are suitable for protecting
the closing zone against the risk of impact.
If two or more safety devices (NC contacts) have
to be connected, put them in series with each
other (see fig.3).
4.1. CONNECTION OF PHOTOCELLS AND SAFETY DEVICES
MOTOR THRUST
CAPACITOR
Connection of 1 pair of closing photocells
Connection of two pairs of closing photocells
Connection of 2 N.O. contacts in parallel
(E.g.: Open A, Open B)
Connection of 2 NC contacts in series
(E.g.: Photocells, Stop)
If two or more safety devices with N.O. contacts
have to be connected, put them in parallel with
each other (see fig.4).
FAN
MOTOR
BEAM BREAKING
Fig. 2
Fig. 5
Fig. 6
Fig. 4
Fig. 3

14
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
4.2. J1 TERMINAL-BOARD - ACCESSORIES (FIG.2)
LOOP 1 - Power supply to loop1 (OPEN - terminals 1-2): use these
terminals to connect the loop you wish to use as an OPEN pulse
generator.
LOOP 2 - Power supply to loop2 (SAFETY/CLOSE - terminals 3-4):
connect between these terminals the loop you wish to use as a
SAFETY/CLOSE pulse generator.
OPEN - “Opening” Command (N.O. - terminal 5): this refers to any
pulse generator (e.g.: push-button) which, by closing a contact,
commands the barrier to open and/or close.
To install several total opening pulse generators,
connect the N.O. contacts in parallel (see fig. 4)
CLOSE - “Closing” Command (N.O. - terminal 6): this refers to any
pulse generator (e.g.: push-button) which, by closing a contact,
commands the barrier to close.
To install several total opening pulse generators,
connect the N.O. contacts in parallel (see fig. 4)
FSW - Closing safety-devices contact (N.C. -. terminal 7) The purpose
of the closing safety devices is to protect the barrier movement
area during closure, by reversing motion. They are never tripped
during the opening cycle. If the closing safety devices are
engaged when the automated system is in open status, they
prevent the closing movement.
To install several closing safety devices, connect the
N.C. contacts in series(fig. 3).
If closing safety devices are not connected, jumper
connect the FSW and FAIL SAFE terminals (fig. 8).
STOP - STOP contact (N.C. - terminal 8): this refers to any device
(e.g.: push-button ) which, by opening a contact, can stop the
motion of the automated system.
To install several STOP devices, connect the N.C.
contacts in series (fig. 3.).
If stop safety devices are not connected, jumper
connect the STOP and GND terminals (fig. 8).
EMERGENCY - EMERGENCY contact (N.C. - terminal 9) this refers to
any switch which, by being activated in emergency state, opens
the barrier and stops its movement until the contact is restored.
If emergency safety devices are not connected,
jumper connect the EMERGENCY and GND
terminals (fig. 8).
GND (teminals 10-11-19) - Negative contact for feeding
accessories
24 Vdc (terminals 12-13) - Positive contact for feeding
accessories
Max. load of accessories: 500 mA. To calculate
absorption values, refer to the instructions for
individual accessories.
OUT 1 - Outout 1 (terminal 14): the output can be set to one of the
functions described in 2nd level Programming (see parag. 5.2).
The default value is FAILSAFE.
OUT 2 - Output 2 (terminal 15): the output can be set to one of the
functions described in 2nd level Programming (see parag. 5.2).
The default value is beam CLOSED.
OUT 3 - Output 3 (terminal 16-17): the output can be set to one of
the functions described in 2nd level Programming (see parag.
5.2). The default value is INDICATOR LIGHT.
Connect 24 Vdc - 3 W max. indicator light , if any, to these
terminals, following the instructions in fig. 2.
To avoid endangering correct operation of the
system, do not exceed the indicated power.
OUT 4 - Output 4 (terminal 18): the output can be set to one of the
functions described in 2nd level Programming (see parag. 5.2).
The default value is Beam LIGHTED.
Connection of one safety device
Connection of no device with NC contacts.
Fig. 7
Fig. 8
4.3. J2 TERMINAL-BOARD - MOTOR - FLASHING LIGHT AND
FAN (FIG.2)
M (COM-MOT1-MOT2): Motor connection
LAMP (LAMP-COM): Flashing light output ( 230 V ~)
FAN (FAN-COM): Fan output ( 230 V ~)
4.5. J9 TERMINAL-BOARD - POWER SUPPLY (FIG.2)
PE : Earth connection
N : Power supply 230 V~ ( Neutral )
L : Power supply 230 V~ ( Line )
To ensure correct operation, the board must be
connected to the earth conductor in the system.
Install an adequate differential thermal breaker
upstream of the system.
4.4. J8 CONNECTOR - MOTOR CAPACITOR (FIG.2)
Rapid connector for connecting the motor thrust capacitor.

15
RP / RP2
624BLD
J4
4.9. J4 QUICK FIT CONNECTOR - FOR MINIDEC, DECODER AND RP
It is used for rapid connection of Minidec, Decoder and RP/RP2
Receivers.
If you are using an RP2 twin-channel receiver, you will be able to
directly command the automated system’s OPEN and CLOSE from
a twin-channel radio control.
If using a single-channel RP type receiver, only OPEN can be
commanded.
Fit the accessory with the components side directed toward the
board interior.
Insert and remove the boards ONLY after cutting
power.
4.6. J3, J5 RAPID CONNECTORS - FOR OPENING AND CLOSING
LIMIT-SWITCHES (FIG.2)
Quick-fit connector for connection of the opening (13) and closing
(J5) limit-switches.
4.7. J6 CONNECTOR - BEAM BREAKING SENSOR (FIG: 2)
Quick-fit connector for connecting the beam breaking sensor
(where present). If this sensor is absent, leave the supplied jumper
in place.
4.8. J11A,B,C CONNECTOR - QUICK-FIT CONNECTOR FOR
EXTERNAL LOOP DETECTOR (FIG.2)
Quick-fit connector for connecting the external loop-detector. For
adjustment and programming consult the relevant instruction.
An example of a 624BLD radio accessory connection
modification of the programming parameters is
immediately effective, whereas definitive memory-
storage occurs only on exiting programming and
returning to the view of the automation status. If you
cut power to the unit before returning to view the
status, all the modifications made will be lost.
You can return to viewing the status from any point
of programming at any level, by pressing keys Fand
-simultaneously.
To restore the programming default settings,
simultaneously press keys +,-and Fand hold them
down for 5 seconds.
The following table indicates the sequence of functions accessible
in 1ST LEVEL PROGRAMMING:
5. PROGRAMMING
To program the operation of the automated system, you must access
the “PROGRAMMING” mode.
Programming is in two parts: 1st LEVEL and 2nd LEVEL
5.1. 1ST LEVEL PROGRAMMING
To access 1ST LEVEL PROGRAMMING, use push-button F:
• if you press it (and hold it down), the display shows the name
of the first function.
• if you release the push-button, the display shows the value of
the function, which can be changed with keys +and -.
• if you press Fagain (and hold it down), the display shows the
name of the next function, etc.
• when you reach the last function, press the Fpush-button
to exit programming, and the display resumes showing the
inputs status.
Fig. 9
1ST LEVEL PROGRAMMING
Display Function Default
LO
FUNCTION LOGICS:
A
Automatic
A1
Automatic 1
E
Semi-automatic
P
Parking
PA
Parking Automatic
Cn
Condo
CA
Condo Automatic
rb
Faac-City (traffic bollard logic)
C
Dead-man
r
Remote
Cu
Custom
E
PA
PAUSE TIME:
This operates only if an automatic logic
was selected. Can be adjusted from
0
to
59
in one second steps.
Next, the viewing changes in minutes and
tenths of a second (separated by a dot)
and time is adjusted in 10 second steps,
up to the maximum value of
4.1
minu-
tes.
E.g. if the display shows
2.5
, the pause
time will be 2 min and 50 sec.
20
FO
POWER:
adjusts motor power.
0 1 = minimum power
5 0 = maximum power
50
L 1
LOOP 1:
If this function is activated, the loop con-
nected to the Loop1 input will have the
OPEN function.
Y
= loop1 active
n o
= loop1 not active
Attention: if the function is not activated, loop1
status will nevertheless be available on one of
the outputs, if appropriately set (see second le-
vel programming).
no

16
Display Function Default
L 2
LOOP 2:
If you activate this function, the loop con-
nected to Loop2 input will have the SAFETY
/CLOSE function, i.e. it will operate as SAFETY
during the closing stage, and will command
CLOSE to the board at release.
Y= loop2 active
n o = loop2 not active
Attention: if the function is not activated, loop2
status will nevertheless be available on one of the
outputs, if appropriately set.
no
S 1
NO EFFECT
05
S2
NO EFFECT
05
S t
AUTOMATED SYSTEM STATUS:
Exit from programming, storage of set data
and return to automated system status
view.
00
Closed
0 1
Opening pre-flashing
02
Opening
03
Open
04
On pause
05
Closing pre-flashing
06
Closing
07
Stopped ready to close
08
Stopped ready to open
09
Emergency opening
10
Closing safety device in operation
5.2. 2nd LEVEL PROGRAMMING
To access 2ND LEVEL PROGRAMMING, press push-button Fand, while
holding it down, press push-button +.
• if you release the push-button +, the display shows the name
of the first function.
• if you also release the Fpush-button, the display shows the
value of the function, which can be changed with keys +
and -.
• if you press the Fkey (and hold it down), the display shows
the name of the next function; if you release it, the value is
shown and can be modified with keys +and -.
• when you reach the last function, press the Fpush-button
to exit programming, and the display resumes showing the
inputs status.
The following table indicates the sequence of functions accessible
in 2ndLEVEL PROGRAMMING:
2
nd
LEVEL PROGRAMMING
Display Function Default
bo MAXIMUM TORQUE AT THRUST:
the motor works at maximum torque
(ignoring the torque adjustment) during
the initial time of the movement.
Y
= Active
no
= Excluded
Y
PF PRE-FLASHING:
to activate the flashing light for 5 sec be-
fore the start of the movement
no
excluded
OC
before every movement
CL
before closing
PA
at end of pause only
no
SC SLOW CLOSING:
for setting the entire closing stage at slow
speed.
Y
= Active
no
= Excluded
no
tr DECELERATION TIME AFTER LIMIT-SWITCHES:
for setting deceleration time (in seconds)
after the opening and closing limit-switches
have operated.
Can be adjusted from
0
to
10
sec. in one
second steps.
00
= deceleration excluded
10
=
maximum deceleration
03
tWORK TIME (time-out):
We advise you to set a value from 5 to
10 seconds longer than the required by
the automated system to move from the
closing to the opening position and vice
versa.
Can be adjusted from
0
to
59
sec. in
one second steps.
Next, the viewing changes in minutes and
tenths of a second (separated by a dot)
and time is adjusted in 10 second steps,
up to the maximum value of
4.1
minutes.
20
FS FAIL SAFE:
If this function is activated, it enables a
function test of the photocells before any
automated system movement, indepen-
dently from the output used . If the test fai-
ls , the automated system does not start
the movement.
Y
= Active
no
= Excluded
no
o 1 OUTPUT 1:
The output can be set to one of the fol-
lowing functions:
00
FAILSAFE
01
INDICATOR LIGHT (lighted at ope-
ning and pause, flashing at closing, and
off when automated system closed)
02
Beam LIGHT
LIGHTHTED
(output active with
beam closed
and on pause, inactive with
beam open, flashing during movement)
03
Beam CLOSED
04
Beam OPEN or in PAUSE, it goes
OFF during closing pre-flashing.
05
Beam MOVING AT OPENING,
pre-flashing included.
06
Beam MOVING AT CLOSING, pre-
flashing included.
07
Beam STILL
08
Beam in EMERGENCY status
09
LOOP1 engaged
10
LOOP2 engaged
1 1
OPEN for 624 SLAVE
12
CLOSE for 624 SLAVE
13
Beam DETACHED
00

17
19 19
18 18
16 17 16 17
15 15
14 14
12 13 12 13
10 11 10 11
8 9 8 9
6 7 6 7
4 5 4 5
2 3 2 3
11
OPEN A
OPEN A
STOP
STOP
LOOP 1
LOOP 1
LOOP 2
LOOP 2
LOOP 2
LOOP 2
LOOP 1
LOOP 1
CLOSE
CLOSE
FSW
FSW
EMERGENCY
EMERGENCY
OUT 1
OUT 1
OUT 2
OUT 2
OUT 4
OUT 4
OUT 3
OUT 3
GND
GND
GND
GND
GND
GND
+24 V
+24 V
+24 V
+24 V
OUT 3
OUT 3
J1 J1
624BLD
MASTER
624BLD
SLAVE
Logica
Logic
Logique
Nur Logik
Lógica
De logica
per ilresto lasciare il default
for the rest leave the default
pour lereste laisser par défaut
programmieren die anderen werkeinstellungen lassen
por lo demas dejar el default
voor de rest default laten
OUT2: = =
OUT3: = =
o2 P2 no
o3 12 P3 no
1 1
LO C
=
8. MASTER-SLAVE
Display
Function
Default
n C CYCLE PROGRAMMING IN HUNDREDS OF
THOUSANDS:
For setting a count-down of the system
operating cycles. Settable value from
0
to
99
(hundreds of thousands of cycles).
The displayed value is reset as the cycles
progress, interacting with the
n c
value
(1 decrement of
n C
corresponds to 99
decrements of
n c
).
The function can be used combined with
n c
to check the use of the system and to
make use of the “Assistance request”.
0 1
h 1 NO EFFECT oo
h 2 NO EFFECT oo
S t AUTOMATED SYSTEM STATUS:
Exit from programming, storage of data
and return to gate status view (see par.
5.1.).
LED Description ON (closed contact) OFF (Open contact)
DL1 OPEN Command enabled Command disabled
DL2 CLOSE Command enabled Command disabled
DL3 FSW Safety devices released Safety devices engaged
DL4 STOP Command disabled Command enabled
DL5 EMERGENCY Command disabled Command enabled
DL6 FCA Opening limit switch free Opening limit switch engaged
DL7 FCC Closing limit switch free Closing limit switch engaged
DL8 PIVOT Beam attached Beam detached
Display Function Default
P1 OUTPUT 1 POLARITY:
for configuring the output polarity status.
Y
= N.C. polarity
n o
= N.O. polarity
Note: if the output is set to FAIL-SAFE (
00
)
leave the default value.
no
o2 OUTPUT 2:
See output 1. 03
P2 OUTPUT 2 POLARITY:
See output 1 polarity. no
o3 OUTPUT 3:
See output 1. 01
P3 OUTPUT 3 POLARITY:
See output 1 polarity. no
o4 OUTPUT 4:
See output 1
, except to functions 00, 11 ,
12
that in this case have not effect.
02
P4 OUTPUT 4 POLARITY:
for configuring the output polarity status.
Y
= N.C. polarity
n o
= N.O. polarity
no
AS ASSISTANCE REQUEST (coupled to the
next two functions):
If activated at the end of the count-down
(settable with the next two functions under
“Cycle programming”), it activates LAMP
output for 4 sec every 30 sec. Can be
useful for setting scheduled maintenance
Y
= Active
no
= Excluded
.
no
nc CYCLE PROGRAMMING IN THOUSANDS:
For setting a count-down of the system
operating cycles. Settable value from
0
to
99
(thousands of cycles). The displayed
value is reset as the cycles progress, inte-
racting with the
n C
value (99
n c
decre-
menting steps correspond to one
n C
de-
crement).
The function can be used combined with
n C
, to check the use of the system and
to make use of the “Assistance request”.
00
7. AUTOMATED SYSTEM TEST
When you have finished programming, check if the system is operating
correctly.
Above all, check if power is adequately adjusted and if the safety
devices operate correctly.
6. START-UP
6.1. LEDS CHECK
The following table shows the status of the LEDs in relation to the
status of the inputs (the closed at rest automated system condition
is shown in bold).
Check the status of the signalling LEDs as per table below:
Note that: Led on = closed contact
Led off = open contact
Operation of status signalling LEDs
Fig. 10

18
Tab. 1/b
Tab. 1/a
Tab. 1/c
LOGIC “A” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect
no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect
reverses
immediately at
closing
stops operation no effect no effect no effect
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time
recharges pause
time
(closing disabled)
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening and closes
at end of opening if
released
reverses
immediately at
opening
STOPPED closes closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
LOGIC “A1” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect
reverses
immediately at
closing
stops operation closes immediately
at end of opening no effect closes immediately
at end of opening
OPEN IN PAUSE recharges pause time closes stops operation closes recharges pause time closes
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening and closes
at end of opening if
released
reverses
immediately at
opening
STOPPED closes closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
LOGIC “E” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING stops operation
reverses
immediately at
closing
stops operation no effect no effect no effect
OPEN closes closes no effect
(closing disabled)
no effect
(closing disabled) no effect no effect
(closing disabled)
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening and closes
at end of opening if
released
reverses
immediately at
opening
STOPPED closes closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
In brackets: effects on the other inputs when pulse active

19
Tab. 1/d
Tab. 1/e
Tab. 1/f
LOGIC “P” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN no effect
(closing disabled) closes no effect
(closing disabled)
no effect
(closing disabled) no effect closes
CLOSING reverses immediately
at opening no effect stops operation stops and continues
to close on release
reverses immediately
at opening and closes
at end of opening if
released
stops and continues
to close on release
STOPPED opens closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
In brackets: effects on the other inputs when pulse active
LOGIC “PA” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time closes
CLOSING reverses immediately
at opening no effect stops operation stops and continues
to close on release
reverses immediately
at opening and closes
at end of opening if
released
stops and continues
to close on release
STOPPED opens closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
LOGIC “Cn” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN no effect
(closing disabled) closes no effect
(closing disabled)
no effect
(closing disabled) no effect closes
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening and closes
at end of opening if
released
reverses
immediately at
opening
STOPPED opens closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)

20
Tab. 1/i
Tab. 1/g
Tab. 1/h
LOGIC “CA” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time closes
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening and closes
at end of opening if
released
reverses
immediately at
opening
STOPPED opens closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
LOGIC “rb” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
released
no effect
OPENING no effect
reverses
immediately at
closing
stops operation no effect no effect no effect
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time
recharges pause
time
(closing disabled)
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening and closes
at end of opening if
released
reverses
immediately at
opening
STOPPED opens closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
released
no effect
(closing disabled)
In brackets: effects on the other inputs when pulse active
LOGIC “C” MAINTAINED COMMANDS PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect no effect no effect
OPENING / no effect stops operation no effect no effect no effect
OPEN no effect
(closing disabled) closes stops operation no effect no effect
(closing disabled)
no effect
(closing disabled)
CLOSING reverses immediately
at opening / stops operation
reverses
immediately at
opening
stops operation stops operation
STOPPED opens closes
no effect
(opening and clo-
sing disabled)
no effect
(closing disabled)
no effect
(closing disabled)
no effect
(closing disabled)

Le descrizioni e le illustrazioni del presente manuale non sono impegnative. La FAAC si riserva il diritto, lasciando
inalterate le caratteristiche essenziali dell’apparecchiatura, di apportare in qualunque momento e senza im-
pegnarsi ad aggiornare la presente pubblicazione, le modifiche che essa ritiene convenienti per miglioramenti
tecnici o per qualsiasi altra esigenza di carattere costruttivo o commerciale.
The descriptions and illustrations contained in the present manual are not binding. FAAC reserves the right, whilst
leaving the main features of the equipments unaltered, to undertake any modifications it holds necessary for
either technical or commercial reasons, at any time and without revising the present publication.
Les descriptions et les illustrations du présent manuel sont fournies à titre indicatif. FAAC se réserve le droit d’ap-
porter à tout moment les modifications qu’elle jugera utiles sur ce produit tout en conservant les caractéristiques
essentielles, sans devoir pour autant mettre à jour cette publication.
Die Beschreibungen und Abbildungen in vorliegendem Handbuch sind unverbindlich. FAAC behält sich das Recht
vor, ohne die wesentlichen Eigenschaften dieses Gerätes zu verändern und ohne Verbindlichkeiten in Bezug auf
die Neufassung der vorliegenden Anleitungen, technisch bzw. konstruktiv/kommerziell bedingte Verbesserungen
vorzunehmen.
Las descripciones y las ilustraciones de este manual no comportan compromiso alguno. FAAC se reserva el dere-
cho, dejando inmutadas las características esenciales de los aparatos, de aportar, en cualquier momento y sin
comprometerse a poner al día la presente publicación, todas las modificaciones que considere oportunas para
el perfeccionamiento técnico o para cualquier otro tipo de exigencia de carácter constructivo o comercial.
De beschrijvingen in deze handleiding zijn niet bindend. FAAC behoudt zich het recht voor op elk willekeurig
moment de veranderingen aan te brengen die het bedrijf nuttig acht met het oog op technische verbeteringen
of alle mogelijke andere productie- of commerciële eisen, waarbij de fundamentele eigenschappen van de
apparaat gehandhaafd blijven, zonder zich daardoor te verplichten deze publicatie bij te werken.
Timbro del Rivenditore:/Distributor’s Stamp:/Timbre de l’Agent:/ Fachhändlerstempel:/Sello del Revendedor:/Stempel van de dealer:
732535- Rev. B -
FAAC S.p.A.
Via Benini, 1
40069 Zola Predosa (BO) - ITALIA
Tel.: 051/61724 - Fax: 051/758518
www.faacgroup.com
Other manuals for 624 BLD
2
Table of contents
Other FAAC Control Unit manuals
Popular Control Unit manuals by other brands

Ampak
Ampak AP6330 user manual

Infineon
Infineon GPT12 PWM Capture 1 manual

Captron
Captron CANEO 41 Series Original operating instructions

Generac Power Systems
Generac Power Systems SMM Owners & installation manual

Delta Computer Systems
Delta Computer Systems TMC 188/40 Series manual

Whadda
Whadda WPI322 user manual