FAAC 624 BLD User manual

1
INDEX
1. . WARNINGS .......................................................................................................................................................... 3
2. . TECHNICAL SPECIFICATIONS................................................................................................................................ 3
3. . LAYOUT AND COMPONENTS OF 624 BLD............................................................................................................. 3
3.1 Description of components................................................................................................................................... 3
4. . ELECTRICAL CONNECTIONS................................................................................................................................. 4
4.1 Connection of photocells and safety devices ...................................................................................................... 4
4.2 J1 Terminal-board - Accessories (Fig.2) ................................................................................................................ 5
4.3 J2 Terminal-board - motor - flashing light and fan (Fig.2) ................................................................................... 5
4.4 J8 Connector - Motor capacitor (Fig.2) ................................................................................................................ 5
4.5 J9 Terminal-board - Power supply (Fig.2) .............................................................................................................. 5
4.6 J3, J5 Rapid connectors - for opening and closing limit-switches (Fig.2)............................................................. 5
4.7 J6 Connector - Beam breaking sensor (Fig. 2)...................................................................................................... 6
4.8 J11a,b,c Connector - Quick-fit connector for external loop detector (Fig.2) ...................................................... 6
4.9 J4 Quick fit Connector - for Minidec, Decoder and RP ...................................................................................... 6
5. . PROGRAMMING .................................................................................................................................................. 6
5.1 1ST LEVEL PROGRAMMING..................................................................................................................................... 6
5.2 2nd LEVEL PROGRAMMING .................................................................................................................................... 7
5.3 3rd LEVEL PROGRAMMING..................................................................................................................................... 8
5.4 MODIFICATION OF FUNCTION LOGIC ..................................................................................................................... 9
5.5 MODIFICATION OF PRE-SETTING OF LOGICAL PARAMETERS.................................................................................... 10
6. . START-UP .............................................................................................................................................................. 10
6.1 LEDS CHECK ........................................................................................................................................................... 10
7. . AUTOMATED SYSTEM TEST .................................................................................................................................... 10
8. . MASTER-SLAVE ..................................................................................................................................................... 11
9. . FUNCTION LOGICS TABLES................................................................................................................................... 12
ENGLISH

2
EC DECLARATION OF CONFORMITY
Manufacturer: FAAC S.p.A.
Address: Via Benini, 1 - 40069 Zola Predosa BOLOGNA - ITALY
Declares that: 624BLD control board
• conforms to the essential safety requirements of the following directives:
73/23/EEC and subsequent amendment 93/68/EEC.
89/336/EEC and subsequent amendment 92/31/EEC and 93/68/EEC
Additional note:
This product underwent tests in a typical uniform configuration
(all products manufactured by FAAC S.p.A.).
Bologna, 01 January 2006
The Managing Director
A. Bassi
1) ATTENTION! To ensure the safety of people, it is important that you read
all the following instructions. Incorrect installation or incorrect use of the
product could cause serious harm to people.
2) Carefully read the instructions before beginning to install the product.
3) Do not leave packing materials (plastic, polystyrene, etc.) within reach of
children as such materials are potential sources of danger.
4) Store these instructions for future reference.
5) This product was designed and built strictly for the use indicated in this
documentation. Any other use, not expressly indicated here, could
compromise the good condition/operation of the product and/or be a
source of danger.
6) FAAC declines all liability caused by improper use or use other than that for
which the automated system was intended.
7) Do not install the equipment in an explosive atmosphere: the presence of
inflammable gas or fumes is a serious danger to safety.
8) The mechanical parts must conform to the provisions of Standards EN 12604
and EN 12605.
For non-EU countries, to obtain an adequate level of safety, the Standards
mentioned above must be observed, in addition to national legal
regulations.
9) FAAC is not responsible for failure to observe Good Technique in the
construction of the closing elements to be motorised, or for any deformation
that may occur during use.
10) The installation must conform to Standards EN 12453 and EN 12445.
For non-EU countries, to obtain an adequate level of safety, the Standards
mentioned above must be observed, in addition to national legal
regulations.
11) Before attempting any job on the system, cut out electrical power.
12) The mains power supply of the automated system must be fitted with an
all-pole switch with contact opening distance of 3mm or greater. Use of a
6A thermal breaker with all-pole circuit break is recommended.
13) Make sure that a differential switch with threshold of 0.03 A is fitted upstream
of the system.
14) Make sure that the earthing system is perfectly constructed, and connect
metal parts of the means of the closure to it.
15) The safety devices (EN 12978 standard) protect any danger areas against
mechanical movement Risks, such as crushing, dragging, and shearing.
16) Use of at least one indicator-light (e.g. FAACLIGHT ) is recommended for every
system, as well as a warning sign adequately secured to the frame structure,
in addition to the devices mentioned at point “15”.
17) FAAC declines all liability as concerns safety and efficient operation of
the automated system, if system components not produced by FAAC are
used.
18) For maintenance, strictly use original parts by FAAC.
19) Do not in any way modify the components of the automated system.
20) The installer shall supply all information concerning manual operation of
the system in case of an emergency, and shall hand over to the user the
warnings handbook supplied with the product.
21) Do not allow children or adults to stay near the product while it is
operating.
22) Keep radio controls or other pulse generators away from children, to prevent
the automated system from being activated involuntarily.
23) Transit is permitted only when the automated system is idle.
24) The user must not attempt any kind of repair or direct action whatever and
contact qualified personnel only.
25) Maintenance: check at least every 6 months the efficiency of the system, particularly
the efficiency of the safety devices (including, where foreseen, the operator thrust
force) and of the release devices.
26) Anything not expressly specified in these instructions is not permitted.
WARNINGS FOR THE INSTALLER
GENERAL SAFETY OBLIGATIONS
ENGLISH

3
-
DL
F
+
LED
F2
J4
J5
J6 J3
J1
J2
J11C
J11B J11A
J8
J9
F1
TF1
EMERG - DL5
STOP - DL4
FSW - DL3
CLOSE - DL2
OPEN - DL1
PIVOT - DL8
FCA - DL6
FCC - DL7
LOOP DETECTOR
1. WARNINGS
Attention: Before attempting any work on the control unit (connections, maintenance), always turn off power.
- Install, upstream of the system, a differential thermal breaker with adequate tripping threshold.
- Connect the earth cable to the terminal on the J9 connector of the unit (see fig.2).
- Always separate power cables from control and safety cables (push-button, receiver, photocells, etc.). To avoid any electrical noise, use
separate sheaths or a screened cable (with the screen earthed).
CONTROL UNIT 624 BLD
3. LAYOUT AND COMPONENTS OF 624 BLD
Power supply voltage
230 Vac (+6% -10%) - 50 Hz
Absorbed power
7 W
Motor max. load
300 W
Power supply for
accessories
24 Vdc
Accessories max.
current
500 mA
Operating amb ien t
temperature
-20°C - +55°C
Fuses
F1 = F 5A - 250V F2 = T 0.8A - 250V
Function logics
Automatic, Automatic 1, Semiautomatic,
Parking, Parking-Automatic,
Condo, Condo-automatic
FAAC-CITY, Dead-man, Remote, Custom
Work time
Programmable (from 0 to 4 minutes)
Pause time
Programmable (from 0 to 4 minutes)
Motor power
Programmable on 50 levels
Terminal board inputs
Loop1, Loop2, Open, Close,
Closing safety devices, Stop, Emergency,
Power supply 230Vac + Earth
Connector inputs
Opening and closing limit-switch, Detector
Motor capacitor, Beam detachment sensor
Terminal board
outputs
Flashing light, Fan, Motor,
Power supply 24 Vdc, Fail-safe, Status output,
Indicator light 24 Vdc, BUS
Rapid connector
5-pin Minidec board coupling, Decoder,
Receiver RP/RP2
Programming
No. 3 keys (+, -, F) and display
Programmable
functions
Logics, Pause Time, Power, Loop 1 and 2, Thrust
torque, Pre-flashing, Slow closure, Deceleration
time, Work time, Indicator light output, Fail-safe
output, Status output, BUS output, Assistance
request
2. TECHNICAL SPECIFICATIONS
3.1 DESCRIPTION OF COMPONENTS
DL SIGNALS AND PROGRAMMING DISPLAY
LED INPUT STATUS CONTROL LEDs
J1 LOW-VOLTAGE TERMINAL BOARD
J2 TERMINAL BOARD FOR CONNECTION OF MOTOR,
FLASHING LIGHT AND FAN
J3 OPENING LIMIT-SWITCH CONNECTOR
J4 CONNECTOR: DECODER MINIDEC / RP RECEIVER
J5 CLOSING LIMIT-SWITCH CONNECTOR
J6 CONNECTOR FOR ROD BREAKING SENSOR
J8 CONNECTOR FOR MOTOR THRUST CAPACITOR
J9 TERMINAL-BOARD FOR 230 VAC POWER SUPPLY
J11 CONNECTOR FOR EXTERNAL LOOP DETECTOR
F1 FUSE FOR MOTORS AND TRANSFORMER PRIMARY
WINDING (F 5A)
F2
FUSE FOR LOW VOLTAGE AND ACCESSORIES (T 800mA)
FPROGRAMMING PUSH-BUTTON ”F”
+PROGRAMMING PUSH-BUTTON ”+”
-PROGRAMMING PUSH-BUTTON ”-”
TF1 TRANSFORMER
Fig. 1
ENGLISH

4
252321
LNPE
26242220
191816 17151412 1310 118 96 74 52 31
MOT1
COM
MOT2
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
230Vac
50Hz
COM
COM
LAMP
FAN
Loop 1
Loop 2
J1
J2
J8 J9
OPEN
CLOSE
STOP
EMERGENCY
230Vac
max 60W
24Vdc
3W
J6
J3
J5
FCC FCA
RX CL1
Altre sicurezze
Other safeties
Autres sécurités
Andere Sicherheiten
Otros disp. Seg.
De andere veiligheid
1
2
3
4
5
1
2
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
TX CL1
-
+
-
+
GND
+
-
GND
-
+
-
+
RX CL1
Altre sicurezze
Other safeties
Autres sécurités
Andere Sicherheiten
Otros disp. Seg.
De andere veiligheid
1
2
3
4
5
1
2
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
TX CL1
-
+
+
+
-
GND
-
+
-
+
Altre sicurezze
Other safeties
Autres sécurités
Andere Sicherheiten
Otros disp. Seg.
De andere veiligheid
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
1
2
5
4
3
1
2
RX CL
TX CL
1
2
5
4
3
1
2
RX CL
TX CL
-
+
-
+
-
+
-
+
+
+
-
-
GND
GND
GND
GND
-
+
-
+
-
+
-
+
4. ELECTRICAL CONNECTIONS
To connect the
photocells and
safety devices,
consult paragraph
4.1.
BLUE
Before you connect the photocells (or other devices) we advise you to select
the type of operation according to the movement zonethey have to protect.
Closing safety devices:
they are tripped only during the
barrier closing movement, and, therefore, are suitable for
protecting the closing zone against the risk of impact.
If two or more safety devices (NC contacts) have
to be connected, put them in series with each
other (see fig.3).
4.1 CONNECTION OF PHOTOCELLS AND SAFETY DEVICES
MOTOR THRUST
CAPACITOR
Connection of 2 N.O. contacts in parallel
(E.g.: Open A, Open B)
Connection of 2 NC contacts in series
(E.g.: Photocells, Stop)
If two or more safety devices with N.O. contacts
have to be connected, put them in parallel with
each other (see fig.4).
FAN
MOTOR
BEAM BREAKING
Fig. 2
Fig. 5 Fig. 6b
Fig. 4
Fig. 3
Connection of two pairs of closure photocells
Connection of 1 pair of closure photocells
with FAIL SAFE facility. Connection of 1 pair of closure photocells
Fig. 6a
To be set in the 2nd programming level: FS =Y and o 1 =00
ENGLISH

5
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
191816 17151412 1310 118 96 74 52 31
OPEN A
STOP
LOOP 1
LOOP 2
LOOP 2
LOOP 1
CLOSE
FSW
EMERGENCY
OUT 1
OUT 2
OUT 4
OUT 3
GND
GND
GND
+24 V
+24 V
OUT 3
J1
4.2. J1 TERMINAL-BOARD - ACCESSORIES (FIG.2)
LOOP 1 - Power supply to loop1 (OPEN - terminals 1-2): use these
terminals to connect the loop you wish to use as an OPEN pulse
generator.
LOOP 2 - Power supply to loop2 (SAFETY/CLOSE - terminals 3-4):
connect between these terminals the loop you wish to use as a
SAFETY/CLOSE pulse generator.
OPEN - “Opening” Command (N.O. - terminal 5): this refers to any
pulse generator (e.g.: push-button) which, by closing a contact,
commands the barrier to open and/or close.
To install several total opening pulse generators,
connect the N.O. contacts in parallel (see fig. 4).
CLOSE - “Closing” Command (N.O. - terminal 6): this refers to any
pulse generator (e.g.: push-button) which, by closing a contact,
commands the barrier to close.
To install several total opening pulse generators,
connect the N.O. contacts in parallel (see fig. 4).
FSW - Closing safety-devices contact (N.C. - terminal 7) The purpose
of the closing safety devices is to protect the barrier movement
area during closure, by reversing motion. They are never tripped
during the opening cycle. If the closing safety devices are
engaged when the automated system is in open status, they
prevent the closing movement.
To install several closing safety devices, connect the
N.C. contacts in series (fig. 3).
If closing safety devices are not connected, jumper
connect the FSW and OUT1 terminals (fig. 8).
STOP - STOP contact (N.C. - terminal 8): this refers to any device
(e.g.: push-button ) which, by opening a contact, can stop the
motion of the automated system.
To install several STOP devices, connect the N.C.
contacts in series (fig. 3).
If stop safety devices are not connected, jumper
connect the STOP and GND terminals (fig. 8).
EMERGENCY - EMERGENCY contact (N.C. - terminal 9) this refers to
any switch which, by being activated in emergency state, opens
the barrier and stops its movement until the contact is restored.
If emergency safety devices are not connected,
jumper connect the EMERGENCY and GND
terminals (fig. 8).
GND (teminals 10-11-19) - Negative contact for feeding
accessories
24 Vdc (terminals 12-13) - Positive contact for feeding
accessories
Max. load of accessories: 500 mA. To calculate
absorption values, refer to the instructions for
individual accessories.
OUT 1 - Outout 1 (terminal 14):The output can be set in one of the
functions described in 2nd level programming (see par.5.2.).
Default value is FAILSAFE.
Maximum applicable load: 24 Vdc with 100 mA.
OUT 2 - Output 2 (terminal 15): The output can be set in one of the
functions described in 2nd level programming (see par.5.2.).
Default value is CLOSED beam.
Maximum applicable load: 24 Vdc with 100 mA.
OUT 3 - Output 3 (terminal 16-17): The output can be set in one of
the functions described in 2nd level programming (see par.5.2.).
Default value is INDICATOR LIGHT.
Connect a 24 Vdc - 3 W max. indicator light, if any, to these
terminals, following the instructions in fig. 2.
Maximum applicable load: 24 Vdc or Vac with 500 mA.
To avoid endangering correct operation of the
system, do not exceed the indicated power.
OUT 4 - Output 4 (terminal 18): The output can be set in one of
the functions described in 2nd level programming (see par.5.2.).
Default value is BEAM LIGHTING.
Maximum applicable load: 24 Vdc with 100 mA.
Connection of one safety device
Connection of no device with NC contact
Fig. 7
Fig. 8
M (COM-MOT1-MOT2): Motor connection
LAMP (LAMP-COM): Flashing light output ( 230 V ~)
FAN (FAN-COM): Fan output ( 230 V ~)
PE : Earth connection
N : Power supply 230 V~ ( Neutral )
L : Power supply 230 V~ ( Line )
To ensure correct operation, the board must be
connected to the earth conductor in the system.
Install an adequate differential thermal breaker
upstream of the system.
Rapid connector for connecting the motor thrust capacitor.
Quick-fit connector for connection of the opening (J3) and closing (J5)
limit-switches.
4.3. J2 TERMINAL-BOARD - MOTOR - FLASHING LIGHT AND
FAN (FIG.2)
4.4. J8 CONNECTOR - MOTOR CAPACITOR (FIG.2)
4.5. J9 TERMINAL-BOARD - POWER SUPPLY (FIG.2)
4.6. J3, J5 RAPID CONNECTORS - FOR OPENING AND
CLOSING LIMIT-SWITCHES (FIG.2)
ENGLISH

6
RP / RP2
624BLD
J4
4.9 J4 QUICK FIT CONNECTOR - FOR MINIDEC, DECODER AND RP
It is used for rapid connection of Minidec, Decoder and RP/RP2
Receivers.
If you are using an RP2 twin-channel receiver, you will be able to directly
command the automated system’s OPEN and CLOSE from a twin-channel
radio control.
If using a single-channel RP type receiver, only OPEN can be
commanded.
Fit the accessory with the components side directed toward the board
interior.
Insert and remove the boards ONLY after cutting
power.
Quick-fit connector for connecting the beam breaking sensor (where
present). If this sensor is absent, leave the supplied jumper in place.
Quick-fit connector for connecting the external loop-detector. For
adjustment and programming consult the relevant instruction.
An example of a radio accessory connection
modification of the programming parameters
is immediately effective, whereas definitive
memory-storage occurs only on exiting programming
and returning to the view of the automation status. If
you cut power to the unit before returning to view the
status, all the modifications made will be lost.
You can return to viewing the status from any point
of programming at any level, by pressing keys Fand
-simultaneously.
To restore the programming default settings,
simultaneously press keys +,-and Fand hold them
down for 5 seconds.
The following table indicates the sequence of functions accessible in 1ST
LEVEL PROGRAMMING:
5. PROGRAMMING
To program the operation of the automated system, you must access
the “PROGRAMMING” mode.
Programming is in three parts: 1st LEVEL, 2nd LEVEL and 3rd LEVEL.
Fig. 9
1ST LEVEL PROGRAMMING
Display Function Default
dF
LOADING PARAMETERS:
00
Neutral condition
0 1
Default FAAC 1 loaded
02
Default FAAC 2 loaded
03
Default FAAC CITY loaded
04
Default FAAC CITY K loaded
For an explanation of the dFparameter,
refer to page 10 chapter 5.5.
00
LO
FUNCTION LOGICS:
A
Automatic
A1
Automatic 1
E
Semi-automatic
P
Parking
PA
Parking Automatic
Cn
Condo
CA
Condo Automatic
rb
Faac-City (traffic bollard logic)
C
Dead-man
r
Remote
Cu
Custom
E
PA
PAUSE TIME:
This operates only if an automatic logic
was selected. Can be adjusted from
0
to
59
in one second steps.
Next, the viewing changes in minutes and
tenths of a second (separated by a dot)
and time is adjusted in 10 second steps,
up to the maximum value of
4.1
minutes.
E.g. if the display shows
2.5
, the pause
time will be 2 min and 50 sec.
20
FO
POWER:
adjusts motor power.
0 1 = minimum power
5 0 = maximum power
50
L 1
LOOP 1:
If this function is activated, the loop
connected to the Loop1 input will have the
OPEN function.
Y
= loop1 active
n o
= loop1 not active
Attention: if the function is not activated, loop1
status will nevertheless be available on one of
the outputs, if appropriately set (see second
level programming).
no
To access 1ST LEVEL PROGRAMMING, use push-button F:
• if you press it (and hold it down), the display shows the name
of the first function.
• if you release the push-button, the display shows the value of
the function, which can be changed with keys +and -.
• if you press Fagain (and hold it down), the display shows
the name of the next function, etc.
• when you reach the last function, press the Fpush-button
to exit programming, and the display resumes showing
the inputs status.
4.7 J6 CONNECTOR - BEAM BREAKING SENSOR (FIG. 2)
4.8. J11A,B,C CONNECTOR - QUICK-FIT CONNECTOR FOR
EXTERNAL LOOP DETECTOR (FIG.2)
5.1. 1ST LEVEL PROGRAMMING
ENGLISH

7
Display Function Default
L 2
LOOP 2:
If you activate this function, the loop
connected to Loop2 input will have the
SAFETY /CLOSE function, i.e. it will operate
as SAFETY during the closing stage, and will
command CLOSE to the board at release.
Y
= loop2 active
n o
= loop2 not active
Attention: if the function is not activated, loop2
status will nevertheless be available on one of the
outputs, if appropriately set.
no
S 1
NO EFFECT
05
S2
NO EFFECT
05
S t
AUTOMATED SYSTEM STATUS:
Exit from programming, storage of set data
and return to automated system status
view.
00
Closed
0 1
Opening pre-flashing
02
Opening
03
Open
04
On pause
05
Closing pre-flashing
06
Closing
07
Stopped ready to close
08
Stopped ready to open
09
Emergency opening
10
Closing safety device in operation
To access 2ND LEVEL PROGRAMMING, press push-button Fand, while
holding it down, press push-button +.
• if you release the push-button +, the display shows the name
of the first function.
• if you also release the Fpush-button, the display shows the
value of the function, which can be changed with keys +
and -.
• if you press the Fkey (and hold it down), the display shows
the name of the next function; if you release it, the value is
shown and can be modified with keys +and -.
• when you reach the last function, press the Fpush-button
to exit programming, and the display resumes showing the
inputs status.
The following table indicates the sequence of functions accessible in
2nd LEVEL PROGRAMMING:
2
nd
LEVEL PROGRAMMING
Display Function Default
bo MAXIMUM TORQUE AT THRUST:
the motor works at maximum torque
(ignoring the torque adjustment) during
the initial time of the movement.
Y
= Active
no
= Excluded
Y
PF PRE-FLASHING:
to activate the flashing light for 5 sec
before the start of the movement
no
excluded
OC
before every movement
PA
at end of pause only
CL
before closing
no
Display Function Default
SC SLOW CLOSING:
for setting the entire closing stage at slow
speed.
Y
= Active
no
= Excluded
no
tr DECELERATION TIME AFTER LIMIT-SWITCHES:
for setting deceleration time (in seconds)
after the opening and closing limit-switches
have operated.
Can be adjusted from
0
to
10
sec. in one
second steps.
00
= deceleration excluded
10
=
maximum deceleration
03
tWORK TIME (time-out):
We advise you to set a value from 5 to 10 se-
conds longer than the required by the au-
tomated system to move from the closing
to the opening position and vice versa.
Can be adjusted from
0
to
59
sec. in one
second steps.
Next, the viewing changes in minutes and ten-
ths of a second (separated by a dot) and time is
adjusted in 10 second steps, up to the maximum
value of
4.1
minutes.
20
FS FAIL SAFE:
If this function is activated, it enables a
function test of the photocells before any
automated system movement, indepen-
dently from the output used . If the test fai-
ls , the automated system does not start
the movement.
Y
= Active
no
= Excluded
no
o 1 OUTPUT 1:
The output can be set to one of the fol-
lowing functions:
00
FAILSAFE
01
INDICATOR LIGHT (lighted at ope-
ning and pause, flashing at closing, and
off when automated system closed)
02
BEAMLIGHTING
LIGHTE
(outputactivewith
beam closed
and on pause, inactive with
beam open, flashing during movement)
03
Beam CLOSED
04
Beam OPEN or in PAUSE, it goes
OFF during closing pre-flashing.
05
Beam MOVING AT OPENING,
pre-flashing included.
06
Beam MOVING AT CLOSING,
pre-flashing included.
07
Beam STILL
08
Beam in EMERGENCY status
09
LOOP1 engaged
10
LOOP2 engaged
1 1
OPEN for 624 SLAVE
12
CLOSE for 624 SLAVE
13
Beam DETACHED
14
FAAC - CITY lights
15
FAAC - CITY buzzer
16
FCA engaged
17
FCC engaged
18
interlock
00
P1 OUTPUT 1 POLARITY:
for configuring the output polarity status.
Y
= N.C. polarity
n o
= N.O. polarity
Note: if the output is set to FAIL-SAFE (
00
)
leave the default value.
no
o2 OUTPUT 2:
See output 1 03
P2 OUTPUT 2 POLARITY:
See output 1 polarity no
o3 OUTPUT 3:
See output 1 01
P3 OUTPUT 3 POLARITY:
See output 1 polarity no
5.2. 2nd LEVEL PROGRAMMING
ENGLISH

8
Display Function Default
o4 OUTPUT 4:
See output 1
, except to functions 00, 11 ,
12
that in this case have not effect.
02
P4
OUTPUT 4 POLARITY:
for configuring the output polarity status.
Y
= N.C. polarity
n o
= N.O. polarity
no
AS
ASSISTANCE REQUEST (coupled to the
next two functions):
If activated at the end of the count-down
(settable with the next two functions under
“Cycle programming”), it activates LAMP
output for 4 sec every 30 sec. (assistan-
ce request). Can be useful for setting
scheduled maintenance
Y= Active
no = Excluded
no
nc
CYCLE PROGRAMMING IN THOUSANDS:
For setting a count-down of the system
operating cycles. Settable value from 0to 99
(thousands of cycles). The displayed value is
reset as the cycles progress, interacting with
the n C value (99 n c decrementing steps
correspond to one n C decrement).
The function can be used combined with
n C , to check the use of the system and to
make use of the “Assistance request”.
00
n C
CYCLE PROGRAMMING IN HUNDREDS OF
THOUSANDS:
For setting a count-down of the system
operating cycles. Settable value from 0
to 99 (hundreds of thousands of cycles).
The displayed value is reset as the cycles
progress, interacting with the n c value
(1 decrement of n C corresponds to 99
decrements of n c ).
The function can be used combined with
n c to check the use of the system and to
make use of the “Assistance request”.
0 1
h 1 NO EFFECT oo
h 2 NO EFFECT oo
S t AUTOMATED SYSTEM STATUS:
Exit from programming, storage of data
and return to gate status view (see par.
5.1.).
To access 3rd LEVEL PROGRAMMING, press push-button Fand, while holding
it down, press push-button +for about 10 seconds:
• if you release the push-button +, the display shows the name
of the first function.
• if you also release the push-button F, the display shows the value
of the function, which can be changed with keys +and -.
• if you press the push-button F(and hold it down), the display
shows the name of the next function; if you release it, the
values is shown and can be modified with keys +and -.
• when you reach the last function, press the push-button F
to exit programming, and the display resumes showing the
inputs status.
The following table indicates the sequence of functions accessible in 3rd
LEVEL PROGRAMMING:
3rd LEVEL PROGRAMMING 10sec
Display Function Default
/ setting
0 1
If you enable this function, automatic closure
occurs after pause time.
.
Y
= automatic
closure
no
= disables
02
If you enable this function, operation is with
two different inputs: OPEN for opening and
CLOSE for closing
Y
= operation
on two inputs
no
= disables
03
Activation of recognition of input levels OPEN
and CLOSE (command maintained), i.e. the
board recognises the level (e.g. with OPEN
maintained and STOP pressed, when the
latter is released, the automated system
continues to open). If
03
is disabled, the
board commands a manoeuvre only if the
input is varied.
Y
= recognition
of input level
no
= recognition
of input variation
04
Activation of DEAD MAN opening (command
always pressed). If the OPEN command is
released, operation is stopped.
Y
= enables
no
= disables
05
If you enable this function, an OPEN command
during opening stops the movement.
If parameter
06
is
no
the system is ready for
opening
If parameter
06
is
Y
the system is ready for
closing
Y
= OPEN at
opening stops
movement
no
= disables
06
If you enable this function, an OPEN command
during opening reverses movement.
If parameters
05
and
06
are
no
, OPEN has no
effect during opening
Y
= OPEN
at opening
reverses
no
= disables
07
If you enable this function, an OPEN command
during the pause stops operation
If parameters
07
and
08
are
no
, OPEN
recharges pause time
Y
= OPEN during
pause stops
movement
no
= disables
08
If you enable this function, an OPEN command
during the pause causes closure
If parameters
07
and
08
are
no
, OPEN
recharges pause time.
Y
= OPEN in
pause closes
no
= disables
09
If you enable this function, an OPEN command
during closure, stops operation, otherwise it
reverses movement.
Y
= stops
movement
no
= reverses
10
DEAD MAN closing enabled (command always
pressed). If you release the CLOSE command,
operation is stopped.
Y
= enables
no
= disables
1 1
If you enable this function, a CLOSE command
has priority over OPEN, otherwise OPEN has
priority over CLOSE.
Y
= enables
no
= disables
12
If you enable this function, a CLOSE command
commands closure when it is released.
Until CLOSE is enabled, the unit remains in
closure pre-flashing.
Y
= CLOSE
closes when
released
no
= CLOSE
closes at once
13
If you enable this function, a CLOSE command
during opening stops operation, otherwise
the CLOSE command commands reversing
immediately or at end of opening (also see
parameter
14
)
Y
= CLOSE stops
movement
no
= CLOSE
reverses
14
If you enable this function, and if parameter
13
is
no
, the CLOSE command commands
immediate closure at end of opening cycle
(memory stores CLOSE)
If parameters
13
and
14
are
no
, CLOSE
commands immediate closure.
Y
= immediate
closure at end of
opening
no
= immediate
closure
15
If you enable this function, when the system
is stopped by a STOP, a subsequent OPEN
command moves in the opposite direction.
If parameter
15
is
no
it always closes.
Y
= OPEN moves
in opposite
direction
no
= OPEN
always closes
16
If you enable this function, during closing, the
CLOSING SAFETY DEVICES stop movement
and allow resumption of movement when
disengaged, otherwise they immediately
reverse at opening.
Y
= closure at
disengagement
no
= immediate
reversing
5.3. 3rd LEVEL PROGRAMMING
ENGLISH

9
A A1 E P PA Cn CA rb C
0 1
Y Y N N Y N Y Y N
02
N N N Y Y Y Y Y Y
03
NNNNNNNYN
04
NNNNNNNNY
05
NNY NNNNNN
06
NNY NNNNNN
07
NNNNNNNNN
08
NNNNNNNNN
09
NNNNNNNNN
10
NNNNNNNNY
1 1
NNNNNNNNN
12
N N N Y Y N N N N
13
NNNNNNNNN
14
N N N Y Y Y Y N N
15
NNNNNNNNN
16
N N N Y Y N N N N
17
NY NNNNNNN
18
NY NNNNNNN
19
N N N Y Y N N N N
20
N Y N Y Y Y Y N N
21
N Y N Y Y Y Y N N
22
N N N N N Y Y N N
23
N N N Y Y N N N N
24
NNNNNNNNN
Display Function Default
/ setting
17
If you enable this function, the CLOSING
SAFETY DEVICES command closure when
disengaged (also see parameter
18
).
Y
=
closure when
FSW disengaged
no
= disables
18
If you enable this function, and if parameter
17 is Y, the unit waits for the opening cycle to
end before executing the closing command
supplied by the CLOSING SAFETY DEVICES.
Y
= closing at
end of opening
no
= disables
19
If you enable this function, during closing,
LOOP2 stops movement and allows it to
resume at disengagement, otherwise it
immediately reverses at opening.
Y
= closure at
disengagement
no
= immediate
reversing
20
If you enable this function, LOOP2 commands
closing when disengaged (also see
parameter
21
).
Y
= closure
when LOOP2
disengaged
no
= disables
2 1
If you enable this function, and if parameter
20
is
Y
, the unit waits for the opening cycle to
end before executing the closing command
supplied by LOOP2.
Y
= closure at
end of opening
no
= disables
22
NOT USED
/
23
LOOP 1 commands opening and, at end of
opening, closes if released (useful if a vehicle
reverses with consecutive loops). If disabled at
release of LOOP 1, no closure is performed.
Y
=closure
at release of
LOOP1
no
= disables
24
NOT USED
/
25
A.D.M.A.P. function
If you enable this function, the safety devices
operate according to French standards: in
closed status, the CLOSING SAFETY DEVICES
prevent opening. The unit memory stores
OPEN and opens when the CLOSING SAFETY
DEVICES are disengaged.
Y
= enables
no
= disables
26
If you enable this function, during closure, the
CLOSING SAFETY DEVICES stop movement
and, when disengaged, reverse movement,
otherwise they reverse immediately.
Y
= stops
movement and
reverses when
disengaged
no
= reverses
immediately
27
NO EFFECT
/
A 1
PRE-FLASHING
Used for adjusting - in 1 sec steps - the duration
of required pre-flashing, from a minimum of
0
to a maximum of
10
seconds
05
A2
TIMEOUT FOR REVERSING AT CLOSURE:
If you enable this function, during closing, you
can decide whether to reverse or stop the
movement when time out elapses (closing
stroke limit not reached).
Y
= reversing
no
= stop
no
A3
OPENING AT POWER UP
In case of a power cut, when power is
restored, an opening operation can be
commanded by enabling this function (only
if the automated system is not closed, FCC
free).
Y
= opening
no
= stays still
no
A4
CLOSING SAFETY DEVICES ENABLEMENT TIME:
The time after which the unit ignores
enablement of the CLOSING SAFETY DEVICES,
continuing to close (useful for use with the
pressure switch of FAAC CITY).
Can be adjusted from
0
to
59
sec. in 1 second
steps. Subsequently, the display changes
to show minutes and tenths of a second
(separated by a dot), up to a maximum value
of
4,1
minutes.
4.0
A5
DISABLING CLOSING SAFETY DEVICES AT START
OF MOVEMENT:
The CLOSING SAFETY DEVICES can be disabled
at start of the closing operation (useful for use
with the FAAC CITY pressure switch.
no
A6
FAAC CITY SOLENOID VALVE CONTROL:
Y
= FAAC CITY K
no
= FAAC CITY standard
no
Procedure for implementing the modification of one or more 3rd level
programming parameters,
Select one of the basic logics most suitable for your requirements.
Enter the 3rd programming level and modify the required
parameters.
Exit the 3rd programming level, memory storing the modifications
and, from the 1st level select logic Cu.
The Cu logic enables you to maintain all the settings you had made in
1st and 2nd level programming and enables the modifications made
at 3rd level.
The following table contains the default parameters affecting the function
logics.
1.
2.
3.
Display Function Default
/ setting
A7
POLARITY OF OPENING TRAVEL-LIMIT STOP:
Configuration of the travel-limit stop contact
Y
= polarity NO
no
= polarity NC
no
A8
POLARITY OF CLOSING TRAVEL-LIMIT STOP:
Configuration of the travel-limit stop contact
Y
= polarity NO
no
= polarity NC
no
A9
FAAC CITY PRESSURE SWITCH ENABLED:
Recognition of PRESSURE SWITCH contact as
a safety device and travel-limit stop for FAAC
CITY:
Y
= Operation for FAAC CITY
no
= Standard operation
no
b 1
SAFETY ONLY PRESSURE SWITCH FOR FAAC CITY:
Recognition of PHOTOCELL contact as a safety
PRESSURE SWITCH but not as TL for FAAC CITY
Y
= Operation with dedicated mechanical tra-
vel-limit stop and safety only pressure switch.
no
= Standard operation
no
b2
DO NOT MODIFY
30
St
AUTOMATED SYSTEM STATUS:
Exit from programming, memory storage of
data and return to gate status display (see
par.5.1.).
5.4. MODIFICATION OF FUNCTION LOGIC
Step
ENGLISH

10
Fig. 10
LED Description ON (closed contact) OFF (Open contact)
DL1 OPEN Command enabled Command disabled
DL2 CLOSE Command enabled Command disabled
DL3 FSW Safety devices released Safety devices engaged
DL4 STOP Command disabled Command enabled
DL5 EMERGENCY Command disabled Command enabled
DL6 FCA Opening limit switch free Opening limit switch engaged
DL7 FCC Closing limit switch free Closing limit switch engaged
DL8 PIVOT Beam attached Beam detached
7. AUTOMATED SYSTEM TEST
When you have finished programming, check if the system is operating
correctly.
Above all, check if power is adequately adjusted and if the safety
devices operate correctly.
6.1. LEDS CHECK
The following table shows the status of the LEDs in relation to the status
of the inputs (the closed at rest automated system condition is shown
in bold).
Check the status of the signalling LEDs as per table below:
Note that: Led on = closed contact
Led off = open contact
Operation of status signalling LEDs
5.5. MODIFICATION OF PRE-SETTING OF LOGICAL PARAMETERS
The modification of dF parameter enables to automatically load 4
different configurations modifying all programming values on every
level with preset values.
This possibility is a starting point for subsequent ‘fine tuning’ of other
parameters depending on the application and its context.
For example, if you choose 01 and exiting from 1st level programming,
all the FAAC default values which can be found in tables of 1st, 2nd and
3rd level in the “Default” column are loaded.
In this way, all the parameters in the memory are returned to a known
standard condition (see table under).
To implement the loading of the values of one of the 4 pre-settings,
select the required number and exit 1st level programming.
If you do not wish to load or modify a pre-setting, leave the dF step
on value 00.
The table below shows the main default values which are loaded on
selecting each of the 4 pre-settings:
Parameters dF=0 1 d F =02 d F =03 d F =04
1st level
Lo logic E A 1 rb rb
PA pause 20 30 30
OF force 50
L 1 loop 1 no
L2 loop 2 no
S 1 not used 5
S2 not used 5
2nd level
bo boost Y
PF pre-flashing no CL
SC slow closing no
tr slow-down 3
t time out 20 12 12
FS fail safe no
o 1 output 1 00 16 15 15
P 1 polarity 1 no
o2 output 2 03 17 14 14
P2 polarity 2 no
o3 output 3 0 1 0 1
P3 polarity 3 no
o4 output 4 02
P4 polarity 4 no
A5 assistance no
nc cycles 1. 00
nC cycles 2. 0 1
h 1 not used no
h2 not used no
3rd level
25 no
26 no
27 no
A 1 5 4
A2 no
A3 no
A4 4 4 4
A5 no Y Y
A6 no Y
A7 no
A8 no
A9 no Y Y
b 1 no
b2 30
Attention: The selection of a default and subsequent exit
from 1st level programming entails the deletion of all the
modifications made previously.
Make sure that you carry out the required default
loading and exit 1st level programming BEFORE modifying
other steps.
6. START-UP
ENGLISH

11
19 1918 1816 17 16 1715 1514 1412 13 12 1310 11 10 118 9 8 96 7 6 74 5 4 52 3 2 31 1
OPEN A
OPEN A
STOP
STOP
LOOP 1
LOOP 1
LOOP 2
LOOP 2
LOOP 2
LOOP 2
LOOP 1
LOOP 1
CLOSE
CLOSE
FSW
FSW
EMERGENCY
EMERGENCY
OUT 1
OUT 1
OUT 2
OUT 2
OUT 4
OUT 4
OUT 3
OUT 3
GND
GND
GND
GND
GND
GND
+24 V
+24 V
+24 V
+24 V
OUT 3
OUT 3
J1 J1
624BLD
MASTER
624BLD
SLAVE
Logica
Logic
Logique
Nur Logik
Lógica
De logica
per il resto lasciare il default
for the rest leave the default
pour le reste laisser par défaut
programmieren die anderen werkeinstellungen lassen
por lo demas dejar el default
voor de rest default laten
OUT2: = =
OUT3: = =
o2 P2 no
o3 12 P3 no
1 1
LO C
=
Fig. 10
8. MASTER-SLAVE
ENGLISH

12
Tab. 1/b
Tab. 1/a
Tab. 1/c
LOGIC “A” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect
no effect
(opening disabled) no effect opens and closes after
pause time no effect
OPENING no effect
reverses
immediately at
closing
stops operation no effect no effect no effect
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time
recharges pause
time
(closing disabled)
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening
reverses
immediately at
opening
STOPPED closes closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
opens and closes after
pause time
no effect
(closing disabled)
LOGIC “A1” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect opens and closes after
pause time no effect
OPENING no effect
reverses
immediately at
closing
stops operation closes immediately
at end of opening no effect closes immediately
at end of opening
OPEN IN PAUSE recharges pause time closes stops operation closes recharges pause time closes
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening
reverses
immediately at
opening, closes
when opening
finished
STOPPED closes closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
opens and closes after
pause time
no effect
(closing disabled)
LOGIC “E” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect opens no effect
OPENING stops operation
reverses
immediately at
closing
stops operation no effect no effect no effect
OPEN closes closes no effect
(closing disabled)
no effect
(closing disabled) closes no effect
(closing disabled)
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening
reverses
immediately at
opening
STOPPED closes closes
no effect
(opening and
closing disabled)
no effect
(closing disabled) opens no effect
(closing disabled)
In brackets: effects on the other inputs when pulse active
ENGLISH

13
Tab. 1/d
Tab. 1/e
Tab. 1/f
LOGIC “P” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
disengaged
no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN no effect
(closing disabled) closes no effect
(closing disabled)
no effect
(closing disabled) no effect closes
CLOSING reverses immediately
at opening no effect stops operation stops and continues
to close on release
reverses immediately
at opening and closes
at end of opening if
disengaged
stops and continues
to close on release
STOPPED opens closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
disengaged
no effect
(closing disabled)
In brackets: effects on the other inputs when pulse active
LOGIC “PA” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect
opens and at end
of opening closes if
disengaged
no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time closes
CLOSING reverses immediately
at opening no effect stops operation stops and continues
to close on release
reverses immediately
at opening and closes
at end of opening if
disengaged
stops and continues
to close on release
STOPPED opens and closes after
pause time closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
opens and at end
of opening closes if
disengaged
no effect
(closing disabled)
LOGIC “Cn” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect opens no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN no effect
(closing disabled) closes no effect
(closing disabled)
no effect
(closing disabled) no effect closes
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening
reverses
immediately at
opening
STOPPED opens closes
no effect
(opening and
closing disabled)
no effect
(closing disabled) opens no effect
(closing disabled)
ENGLISH

14
Tab. 1/i
Tab. 1/g
Tab. 1/h
LOGIC “CA” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect opens and closes after
pause time no effect
OPENING no effect closes immediately
at end of opening stops operation no effect no effect closes immediately
at end of opening
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time closes
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening
reverses
immediately at
opening
STOPPED opens and closes after
pause time closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
opens and closes after
pause time
no effect
(closing disabled)
LOGIC “rb” PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens and closes after
pause time no effect no effect
(opening disabled) no effect opens and closes after
pause time no effect
OPENING no effect
reverses
immediately at
closing
stops operation no effect no effect no effect
OPEN IN PAUSE recharges pause time closes stops operation
recharges pause
time
(closing disabled)
recharges pause time
recharges pause
time
(closing disabled)
CLOSING reverses immediately
at opening no effect stops operation
reverses
immediately at
opening
reverses immediately
at opening
reverses
immediately at
opening
STOPPED opens and closes after
pause time closes
no effect
(opening and
closing disabled)
no effect
(closing disabled) opens no effect
(closing disabled)
In brackets: effects on the other inputs when pulse active
LOGIC “C” MAINTAINED COMMANDS PULSES
AUTOMATED SYSTEM
STATUS OPEN A CLOSE STOP FSW LOOP 1 LOOP 2
CLOSED opens no effect no effect
(opening disabled) no effect no effect no effect
OPENING / no effect stops operation no effect no effect no effect
OPEN no effect
(closing disabled) closes stops operation no effect no effect
(closing disabled)
no effect
(closing disabled)
CLOSING reverses immediately
at opening / stops operation Stops
operation stops operation stops operation
STOPPED opens closes
no effect
(opening and
closing disabled)
no effect
(closing disabled)
no effect
(closing inhibited)
no effect
(closing disabled)
ENGLISH
Other manuals for 624 BLD
2
Table of contents
Other FAAC Control Unit manuals