manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Festo
  6. •
  7. Accessories
  8. •
  9. Festo SPAN-B Series User manual

Festo SPAN-B Series User manual

Translation of the original instructions
© 2020 all rights reserved to Festo SE & Co. KG
1 About this document
1.1 Applicable Documents
All available documents for the product èwww.festo.com/sp.
2 Safety
2.1 General safety instructions
– Only use the product in original status without unauthorised modifications.
– Only use the product if it is in perfect technical condition.
– Only use media in accordance with the specifications è Technical data.
– Observe labelling on the product.
– Note that changes to the switching status (EDIT mode) become effective
immediately.
2.2 Intended use
The product is intended for monitoring the pressure of compressed air and inert
gases in the piping.
2.3 Training of qualified personnel
Work on the product should only be conducted by qualified personnel.
3 Service
Contact your regional Festo contact person if you have technical questions
èwww.festo.com.
4 Product overview
4.1 Function
The sensor converts pneumatic pressure values (relative pressure) into electrical
signals, which can be used for control or regulating functions. Measurements are
carried out using a piezoresistive sensor element with a downstream electronic
evaluation unit. The connection to the higher-level system is established via a
switching output.
The switching output can be configured to monitor a threshold value or a pressure
range. The PNP or NPN and the normally open (N/O) or normally closed (N/C) out-
put can be optionally set in this process.
4.1.1 Operating statuses
Operating status Function
RUN mode – Basic status after the operating voltage is switched on
– Display of the current measured value
SHOW mode – Display of the current settings
EDIT mode – Setting or modification of parameters
TEACH mode – Acceptance of the current measured value to determine
switching points
Tab. 1
4.1.2 Switching functions
Threshold value comparator for monitoring of a pressure threshold _|¯
Function N/O (normally open) N/C (normally closed)
Switching function:
– 1 switching point (SP)
TEACH mode:
– 2 teach points (TP1, TP2)
– SP = ½ (TP1+TP2)
TP1 TP2
HY
1
0
Out
p
SP
TP1 TP2
SP
HY
1
0
Out
p
Tab. 2
Window comparator for monitoring of a pressure range _|¯|_
Function N/O (normally open) N/C (normally closed)
Switching function:
– 2 switching points (SP.Lo,
SP.Hi)
TEACH mode1):
– 2 teach points (TP1, TP2)
– TP1 = SP.Lo, TP2 = SP.Hi
HY HY
TP1=SP.Lo TP2=SP.Hi
1
0
Out
p
HY HY
TP1=SP.Lo TP2=SP.Hi
1
0
Out
p
1) SP.Lo = lower pressure/vacuum value, SP.Hi = higher pressure/vacuum value, dependent on the Teach
sequence
Tab. 3
4.2 Configuration
4.2.1 Product design
1Display
2A pushbutton
3EDIT pushbutton
4B pushbutton
5Pneumatic port
6Electrical connection
Fig. 1 Product design
5 Installation
5.1 Mechanical and pneumatic
NOTICE!
An unfavourable mounting position may impair the function of the product.
• Mount the sensor so that condensation from the compressed air lines cannot
accumulate in the device.
• Install the sensor so that it cannot be heated above the maximum permissible
operating temperature (plan for convection possibilities).
– Remove all transport packaging. The material used in the packaging has been
specifically chosen for its recyclability.
– Avoid applying force to the sensor housing during mechanical and pneumatic
assembly.
SPAN-B-…-G18M/R18M
• Seal connecting thread.
Fig. 2 Example with G18M
8140082
SPAN-B
Pressure sensor
8140082
2020-06
[8140084]
Operating instructions
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
SPAN-B -...- G18FPM/M5FAL with mounting bracket
– Recommendation for the variant "SPAN-B-...-G18FPM..": use type OL-1/8
sealing ring at the pneumatic connection.
Fig. 3 Example with G18FPM
Front panel insert SAMH-PN-F
Fig. 4 Size of the front panel cut-out in mm
1Panel frame 2Clamping element
Fig. 5
1. Fasten panel frame to the sensor.
2. Guide sensor into the cut-out on the front panel from the front.
3. Attach the clamping element and press until the clamping element clicks into
place.
5.2 Electrical
WARNING!
Risk of injury due to electric shock.
• For the electric power supply, use only PELV circuits that ensure a reliable
electric disconnection from the mains network.
• Observe IEC60204-1/EN60204-1.
• Connect sensor.
– Take the maximum permissible line length into account: 30m.
Pin Colour1) Allocation Plug L1
1 Brown (BN) Operating voltage +24 V DC
2 Black (BK) Switching output OutA
3 White (WH) NC (not connected)
4 Blue (BU) 0V
1) Colours apply for connecting cables NEBS-L1… or electrical adapter SASC-P4… with NEBU-M8…
Tab. 4
Circuit diagram SPAN-B-PN
Fig. 6 SPAN-B-PN
6 Commissioning
6.1 LCD display
1Switching status indication
2Main display (e.g.measurement
value)
3Pressure units
4Status information
Fig. 7 LCD display
Example for LCD display Meaning
Output display
[OutA] Switching output OutA selected
[OutA] Switching output OutA set
Status information/signal indicator
[Lock] Security code activated
[SPEC] Special menu selected
Tab. 5
Example for
LCD display
Main display
Example for
LCD display
Alternating
display
Meaning
Measured value indicator and unit in the RUN mode
[– 0.53] [bar] Measured value indicator (here: negative value) and unit
Menu for switching output OutA
_|¯ [Fctn] Threshold value comparator
_|¯|_ [Fctn] Window comparator
[1.80] [SP] Switching point value
[2.45] [SP.Lo] Value of lower switching point
[6.45] [SP.Hi] Value of upper switching point
[0.50] [HY] Hysteresis value
[NO] [LOGC] Switching behaviour:
[N/O] = normally open, [N/C] = normally closed
[PNP] [Out] Shift of the switching outputs (binary) between PNP and
NPN
[bLUE] [COLR] Display colour:
[bLUE] = blue, colour change function is deactivated
[R.ON] = red when switching output set
[R.OFF] = red when the switching output is not set
Note: independent of the settings [COLR], the red colour
change appears with some malfunctions.
Extreme values (only SHOW mode)
[1.64] [MIN] Minimum measured pressure since switch-on or the last
reset
[8.50] [MAX] Maximum measured pressure since switch-on or the last
reset
Menu for device settings (SPEC)
[16] [Filt]/[ms] Value of the filter time constant for the pressure measure-
ment signal
[bar] [Unit] Unit for the pressure indicator
[OFF] [Z.AdJ] [OFF] = zero point synchronisation (zero adjust) deactiv-
ated
[ON] = offset correction for measured value indicator and
switching points possible
[40] [Eco]/[s] Economy mode: period after which the display background
lighting is switched off
[OFF] [Code]/[Lock] Activation and determination of the security code
[OFF] [MASt] Activation of the IO-Link master function for replication of
parameters
Tab. 6
6.2 Switching on the sensor (RUN mode)
• Switch on the operating voltage.
ÄCurrent measured value is displayed. The sensor is in the basic status
(RUN mode).
The basic status can be reached from other modes by:
– Press and hold Edit pushbutton for 3 seconds
– Expiration of a monitoring time (time-out)
6.3 Displaying parameters (SHOW mode)
Requirement: the sensor is ready for operation (RUN mode).
Switching output OutA
1. Press the A pushbutton.
ÄThe first parameter set is displayed. [Fctn] flashes.
2. Press the A pushbutton to display each of the following parameters.
SPEC menu parameters
1. Press B pushbutton.
ÄThe first parameter set is displayed. [Filt] flashes.
2. Press the B pushbutton to display each of the following parameters.
3. The minimum and maximum values are displayed at the end. To reset the val-
ues, press the EDIT key.
Fig. 8 SHOW mode
Legend Meaning
MIN, MAX Parameter is displayed without time-out
EDIT pushbutton
A pushbutton, B pushbutton
1) This menu item is not applicable for SPAN-B-B2 and SPAN-B-B11. With these
variants the Zero Adjust function is always switched on.
Tab. 7
6.4 Setting parameters (EDIT mode)
Fig. 9 EDIT mode
Legend Meaning
EDIT pushbutton
A pushbutton, B pushbutton
1) The values refer to the relevant measuring range and the selected unit.
2) This menu item is not applicable for SPAN-B-B2 and SPAN-B-B11. With these
variants the Zero Adjust function is always switched on.
Tab. 8
6.4.1 Entering the security code
Requirement: the sensor is ready for operation (RUN mode).
1. Press Edit pushbutton.
ÄThe EDIT mode is active. If the security code is activated, the parameter
entry option is blocked: [Lock] flashes.
2. Enter security code set with A or B pushbutton.
3. Briefly press Edit pushbutton.
Ä[OutA] flashes. The parameter entry option is unblocked.
6.4.2 Configuring switching output
Requirement: the sensor is ready for operation (RUN mode).
Set threshold value comparator _I¯ and window comparator _I¯I_
1. Briefly press Edit pushbutton.
Ä[OutA] flashes.
2. Briefly press Edit pushbutton.
Ä[Fctn] flashes.
3. Select _I¯ or _I¯I_ with A or B pushbutton.
4. Briefly press Edit pushbutton.
Ä– The set value is saved.
– The next adjustable parameter is shown.
5. Set the parameter with A or B pushbutton.
6. Repeat points 4 and 5 until all parameters are set.
7. Press Edit pushbutton.
ÄSwitch to the RUN mode.
6.4.3 Changing device settings
Requirement: the sensor is ready for operation (RUN mode).
1. Briefly press Edit pushbutton.
Ä[OutA] flashes.
2. Select special menu [SPEC] with A or B pushbutton.
Ä[SPEC] flashes.
3. Briefly press Edit pushbutton.
Ä[Filt] flashes.
4. Set the parameter with A or B pushbutton.
5. Briefly press Edit pushbutton.
Ä– The set value is saved.
– The next adjustable parameter is shown.
6. Repeat points 4 and 5 until all parameters are set.
7. Press Edit pushbutton.
ÄSwitch to the RUN mode.
6.4.4 Replicating parameters
Requirements:
– The pre-configured sensor (master sensor) is ready for operation (RUN mode).
– Master sensor and device sensor have the same design with reference to the
parameters (same device ID).
– The master sensor is connected with the device sensor è Fig.10.
– The device sensor is in an unswitched status (switching output PNP, display
OutA off).
Fig. 10 Pin allocation
Replicating parameters
1. Select the special menu [SPEC] from the device settings on the master sensor.
2. Press Edit pushbutton repeatedly until [MASt] appears.
3. Select [ON] using the A or B pushbutton.
4. Press Edit pushbutton.
Ä[REPL]/[RedY] appears.
5. Press A or B pushbutton.
Ä[REPL]/[RUN] appears briefly. The parameters are transmitted to the
device sensor. [REPL]/[RedY] appears. If an error occurs, an error mes-
sage appears è 9.1 Fault clearance.
6. If an additional sensor is to be parameterised, connect the additional sensor
to "è Fig.10" and repeat step 5.
7. Press Edit pushbutton.
ÄRUN mode is active.
6.5 Zero point synchronisation (zero adjust)
Requirement:
– The sensor is ready for operation (RUN mode).
– [Z.AdJ] [ON] is set (factory setting for bipolar variants).
– The measured value lies in the range 0 bar ± 3% FS.
Perform zero point synchronisation
1. Hold down the A and B pushbutton.
2. Also press the Edit key.
Ä– [OK] appears. The zero point synchronisation was successful.
– If [FAIL] appears: the zero point synchronisation was not successful.
Check requirements.
If [Z.AdJ] [OFF] is set for a later time, the device accepts the factory-set calibration
values.
6.6 Teaching the switching points (TEACH mode)
There is no time-out in the TEACH mode. The sensor changes to the RUN mode
only after the entire teach process is ended.
If the security code is activated, the parameter entry option is blocked: [Lock]
flashes.
• Enter the security code è 6.4.1 Entering the security code.
Requirement:
– The sensor is ready for operation (RUN mode).
Teach-in switching points
1. Establish the switching function in EDIT mode
è 6.4.2 Configuring switching output.
2. Create pressure value 1.
3. Press A pushbutton and Edit pushbutton simultaneously.
ÄThe current pressure value will then be adopted as the first teaching
point (TP1).
[t-IN] flashes.
4. Create pressure value 2.
5. Press A pushbutton and Edit pushbutton.
ÄThe current pressure value is adopted as the second teaching point (TP2).
Switch to the RUN mode.
7 Operation and use
NOTICE!
Property damage due to high temperatures.
Extreme pneumatic conditions (high switching frequency with high pressure amp-
litude) can heat the product above 80°C.
• Select the operating conditions (in particular the ambient temperature, pres-
sure amplitude, switching frequency, current consumption) such that the
product does not heat up above the maximum permitted operating temperat-
ure.
7.1 Restoring Factory Settings (Restore)
By resetting to the factory settings, the current settings are lost. Note down cur-
rent settings before resetting.
1. Switch off operating voltage.
2. Hold down the A and B pushbutton.
3. Switch on the operating voltage.
4. Additionally, press the Edit button.
Ä[RSto PArM] appears. All parameters are reset to the factory settings.
8 Maintenance and Care
1. Switch off the energy sources (operating voltage, compressed air).
2. Clean sensor with non-abrasive cleaning agents.
9 Malfunctions
9.1 Fault clearance
Malfunction Possible cause Remedy
No operating voltage or impermissible
operating voltage
Apply permissible operating voltage
Electrical connections swapped Connect the device in accordance with
the circuit diagram
No display
Device faulty Replace device
Short circuit or overload at the output Eliminate short circuit/overload
Incorrect switching point taught
(e.g.at 0kPa)
Repeat teach-in
Device faulty Replace device
Indicator or
switching output
does not react in
accordance with
the settings
Parameter incorrect Reset to factory settings
[Er01]/[FAIL] 1) Device faulty Replace device
[Err10]/[OVER] Measuring range exceeded Hold measuring range
[Er21]/[SHRt] 2) Short circuit at OutA Eliminate short circuit
[Err]/[BUSY] OutA is switched active Check device settings
è 6.4.4 Replicating parameters.
[Err]/[ID] DeviceID error, replication function
failed
Use sensors with the same type when
replicating (same DeviceID)
[Err]/[COMM] Communication errors Check wiring
1) Display flashes red
2) Display is red
Tab. 9
10 Disassembly
1. Switch off operating voltage and compressed air.
2. Disconnect pneumatic and electrical connections from the device.
3. Loosen mountings and remove device.
11 Disposal
ENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations èwww.festo.com/sp.
12 Technical data
SPAN-B-
General information
Approval RCM compliance mark
Input Signal/Measuring Element
Operating medium Compressed air in accordance with ISO 8573-1:2010
[7:4:4]; inert gases, operation with lubricated medium
possible
Temperature of medium [°C] 0…+50
Ambient temperature [°C] 0…+50
Output, general
Accuracy
[%FS] ± 1.5 at room temperature
[%FS] ± 3 over complete temperature range
Repetition accuracy [%FS] ± 0.3, at [Filt] = [OFF]
Temperature coefficient [%FS/K] typ. 0.1
Switching output
Switching output 1x PNP or 1x NPN, switchable
Switching function Threshold value comparator, window comparator
Switch-on/switch-off time [ms] Max.1
Max. output current [mA] 80
Capacitive load maximum DC [nF] 100
Voltage drop [V] max. 2
Pull-down resistor integrated (PNP)
Pull-up resistor not integrated (NPN)
Inductive protective circuit present
Output, additional data
Short circuit current rating yes
Overload protection present
Electronics
Operating voltage range DC [V] 10.8…30 (nominal voltage 12…24)
No-load supply current [mA] max. 30
Ready-state delay [ms] typ. 30
Reverse polarity protection All connections against each other
Mechanics
Housing material PA-reinforced
Inspection window material PC
Keypad material TPE-O
Materials in contact with the medium 1) FPM, NBR, PA reinforced, brass (nickel-plated)
Display/operation
Displayable units 2) bar, kPa, MPa, psi, mmHg, inchHg
Setting range threshold values [%FS] 1…99
Hysteresis setting range [%FS] 0…90
Immissions/emissions
Storage temperature [°C] –20…+80
Max. permissible relative
humidity
[%RH] 85
Degree of protection in accord-
ance with EN 60529
IP40
Protection class in accordance with
DIN VDE 0106-1
III
Shock resistance in accordance with
EN 60068-2
30g acceleration with 11 ms duration (half-sine)
Vibration resistance in accordance with
EN 60068-2
10…60 Hz: 0.35mm/60…150 HZ: 5g
1) depending on the variant
2) depending on the variant
Tab. 10
SPAN-B -B2 -B11 -V1
Pressure measuring
range
[bar]
[MPa]
–1…1
–0.1…0.1
–1…10
–0.1…1
0…–1
0…–0.1
Overload range [bar]
[MPa]
–1…5
–0.1…0.5
–1…15
–0.1…1.5
–1…5
–0.1…0.5
Tab. 11

This manual suits for next models

118

Other Festo Accessories manuals

Festo AS-i Series Parts list manual

Festo

Festo AS-i Series Parts list manual

Festo SDE1 Series User manual

Festo

Festo SDE1 Series User manual

Festo SFAB Parts list manual

Festo

Festo SFAB Parts list manual

Festo MPS 8034566 User manual

Festo

Festo MPS 8034566 User manual

Festo SFAB-PNLK Series User manual

Festo

Festo SFAB-PNLK Series User manual

Festo SFAM-62-***-T User manual

Festo

Festo SFAM-62-***-T User manual

Festo SOPA User manual

Festo

Festo SOPA User manual

Festo NEBU-M12W8-K N-LE8 Series User manual

Festo

Festo NEBU-M12W8-K N-LE8 Series User manual

Festo SOEG-S-Q20 series User manual

Festo

Festo SOEG-S-Q20 series User manual

Festo ASLR-D-L1 User manual

Festo

Festo ASLR-D-L1 User manual

Festo Sensorbox SRBG-C1-N-20N-ZC-M12-EX5 Instruction manual

Festo

Festo Sensorbox SRBG-C1-N-20N-ZC-M12-EX5 Instruction manual

Festo SFAM User manual

Festo

Festo SFAM User manual

Festo SRAP-M-CA1 Series User manual

Festo

Festo SRAP-M-CA1 Series User manual

Festo SPAW series User manual

Festo

Festo SPAW series User manual

Festo SRBG User manual

Festo

Festo SRBG User manual

Festo SOPA User manual

Festo

Festo SOPA User manual

Festo SDE5 series User manual

Festo

Festo SDE5 series User manual

Festo SDAP-...-M50-Series User manual

Festo

Festo SDAP-...-M50-Series User manual

Festo CP Lab User manual

Festo

Festo CP Lab User manual

Festo SOEL-RTD-Q50-PP-S-7L Service manual

Festo

Festo SOEL-RTD-Q50-PP-S-7L Service manual

Festo SDE5 series User manual

Festo

Festo SDE5 series User manual

Festo SDAT-MHS User manual

Festo

Festo SDAT-MHS User manual

Festo SFAM-62 User manual

Festo

Festo SFAM-62 User manual

Festo SOEC-RT-Q50-PS-S-7L User manual

Festo

Festo SOEC-RT-Q50-PS-S-7L User manual

Popular Accessories manuals by other brands

XD COLLECTION P322.14 Series manual

XD COLLECTION

XD COLLECTION P322.14 Series manual

Dometic TRIM LINE 9472 010 Series installation instructions

Dometic

Dometic TRIM LINE 9472 010 Series installation instructions

Amana Hardwire Junction Kit installation instructions

Amana

Amana Hardwire Junction Kit installation instructions

PKP DR08-40 instruction manual

PKP

PKP DR08-40 instruction manual

Datalogic S70 manual

Datalogic

Datalogic S70 manual

Bnoto K-201 instruction manual

Bnoto

Bnoto K-201 instruction manual

TP-Link KP115 user guide

TP-Link

TP-Link KP115 user guide

FIBARO FGBHMS-001 operating manual

FIBARO

FIBARO FGBHMS-001 operating manual

COMPX Stock Locks C7022 Dimensional drawing

COMPX

COMPX Stock Locks C7022 Dimensional drawing

Dahua DB11 user manual

Dahua

Dahua DB11 user manual

Craftsman 486.246211 owner's manual

Craftsman

Craftsman 486.246211 owner's manual

Philips CRP149 brochure

Philips

Philips CRP149 brochure

Lionelo FantasyPen 3D manual

Lionelo

Lionelo FantasyPen 3D manual

Venstar ACC0435 installation instructions

Venstar

Venstar ACC0435 installation instructions

Soluzione Solare ENVMETER-485 Pro installation manual

Soluzione Solare

Soluzione Solare ENVMETER-485 Pro installation manual

Raindrip WeatherSmart RS 100 user manual

Raindrip

Raindrip WeatherSmart RS 100 user manual

Koden KBG-3 quick start guide

Koden

Koden KBG-3 quick start guide

Southern Telecom MAHLI Plant MDB-96 Instruction guide

Southern Telecom

Southern Telecom MAHLI Plant MDB-96 Instruction guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.