Tetra PowerStrip DS 20 ft. (6.10 m) 25 ft. (7.62 m) 35 ft. (10.67 m) 60 ft. (18.29 m) 75 ft. (22.86 m) 100 ft. (30.46 m)
Tetra Contour/Tetra Contour LS 30 ft. (9.14 m) 50 ft. (15.24 m) 80 ft. (24.38 m) 120 ft. (36.58 m) - -
NOTE: For CSA approval, a disconnect/toggle switch of appropriate rating needs to be placed within 29.5 feet (9 meters)
of primary side of the power supply. The minimum rating of the switch must be either 120 or 220 Volts AC. The
switch must also support twice the amount of input current.
NOTE: When installing power supply, connect to the appropriate sized building breaker or disconnect device for line,
neutral and ground connections, in accordance with National Electric Code (NEC) Article 600 and all local
regulations.
SIGN081-R020211
RISK OF ELECTRIC SHOCK:
• Turn power OFF before inspection, installation or removal.
• Properly ground Tetra Power Supply enclosure.
• Shut off power at fuse box or circuit breaker before installation.
RISK OF FIRE:
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
Minimum size 18 AWG (0.82 mm2)
WARNING!
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. This Class [A] RFLD complies with the Canadian standard ICES-005. Ce DEFR de la classe [ A ] est conforme à la NMB-005 du Canada.
Conforms to the following standards:
Power Supply Specifications
Loading per Power Supply Maximum load per output bank Maximum load per power supply
14 modules/14 ft. (4.27 m)
Tetra PowerStrip DS
Tetra Contour
Tetra Contour LS
27 ft. (8.23 m)
27 ft. (8.23 m)
28 modules/28 ft. (8.54 m)
54 ft. (16.46 m)
54 ft. (16.46 m)
Environmental Specifications Min Typical Max
Environmental Operating Temperature Range -40°C +25°C +60°C*
Environmental Humidity (non-condensing) 0% - 95%
Environmental Storage Temperature Range -40°C - +85°C
* Maximum case temperature is 80°C
Performance Data Min Typical Max
Input Voltage (VAC) 90 100-277 305
Input Frequency (Hz) - 50/60 -
Input Current (A) 0.7 - 2.5
Output Voltage (VDC) 23.25 24.0 24.75
Output Current (ADC) per output bank - - 3.8
Output Power (W) - - 180
Enclosure Specifications Dimensions
Damp Location Rated 1 5.5 in. x 2.5 in. x 1.6 in. (392 mm x 62 mm x 40 mm)
Maximum Remote
Mounting Distance
18AWG 16AWG 14AWG 12AWG 10AWG 8AWG
(0.82 mm2) (1.31 mm2) (2.08 mm2) (3.31 mm2) (5.27 mm2) (8.35 mm2)
NOTE: Exceeding maximum load will cause the power supply to shut down. Once the excess load is removed, cycle the input power to
restart the power supply.
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
1 - 8 8 8 - 6 9 - 4 3 - 5 3 3
GE Lighting Solutions, LLC is a subsidiary of the General Electric Company. Tetra is a trademark of GE Lighting Solutions, LLC. The GE brand and logo are trademarks of the General Electric Company.
© 2011 GE Lighting Solutions, LLC. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.