Geco GH10PD User manual

MANUAL
FOR CONTROLLER
GH10PD
FOR CONTROLLING CENTRAL
HEATING BOILERS FIRED WITH
PELLETS AND OATS
Program versio 01c
USER MANUAL
We request that users carefully study applicable I structio s before co ecti g a d starti g up a y
of our products.
Should a y doubts arise, please co tact our Compa y betwee 8 a.m. a d 4 p.m.
Atte tio !!! At the bottom of each page you will fi d last docume t’s update date. Please, always use the
most rece t versio of the I structio s, which is available free of charge a d will be mailed to you if ordered.

TABLE OF CONTENTS
1. INTRODUCTION ................................................................................................................................. 3
1.1. G
RAPHIC SYMBOLS
................................................................................................................................ 3
1.2. K
EYBOARD AND FUNCTION
..................................................................................................................... 3
1.3.
D
EVICE OPERATION INDICATORS
................................................................................................................. 3
2. GENERAL FEATURES ...................................................................................................................... 4
3. TECHNICAL DATA .......................................................................................................................... 4
4. ELECTRICAL SYSTEM AND CONNECTION RULES .............................................................................. 5
5. QUICK START ................................................................................................................................ 5
6. OPERATION OF THE GH10PD ......................................................................................................... 7
6.1. S
YSTEM CONFIGURATION
....................................................................................................................... 7
6.2. A
UTOMATIC OPERATION MODE
............................................................................................................... 7
6.3. M
ANUAL OPERATION MODE
................................................................................................................. 10
6.4. V
IEWING FLAME TEMPERATURES
........................................................................................................... 10
6. . A
LARMS
............................................................................................................................................ 10
6.6. P
OWER FAILURE
................................................................................................................................. 11
6.7. B
OILER BURNOUT DETECTION
................................................................................................................ 11
7. USER SETTINGS ........................................................................................................................... 11
7.1. B
OILER PRESET TEMPERATURE
(U0) ....................................................................................................... 11
7.2. F
EEDER WORKING TIME
(U1) ................................................................................................................ 12
7.3. F
EEDER STOP TIME
(U2) ...................................................................................................................... 12
7.4. M
AINTAIN TIME
(U3) .......................................................................................................................... 12
7. . F
AN SPEED
(U4) ................................................................................................................................. 12
7.6. T
HE NUMBER OF GRATE ROTATION IN HEATING MODE AND SUSTAIN MODE
(U ) ........................................... 12
. TEMPERATURE LIMITER (STB) ...................................................................................................... 13
9. ROOM THERMOSTAT .................................................................................................................. 13
10. CONNECTING DEVICES TO THE GH10PD CONTROLLER .................................................................. 14
11. INFORMATION ON LABELLING AND COLLECTION OF WORN OUT ELECTRICAL AND ELECTRONIC
EQUIPMENT ................................................................................................................................ 15

GH10PD USER MANUAL PAGE 3
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
1. INTRODUCTION
1.1. Graphic symbols
Symbols intended to indicate and at the same time emphasize the importance of text containing
information that warns against dangerous situation have the following graphic forms:
Warning
This symbo
l is used when it is necessary in described instructions to follow the
sequence of carried out operations. The unit may be damaged or destroyed in case of
any error or proceeding in discord with the description.
Important!
This symbol indicates infor
mation of particular importance.
⇒
Reference
This symbol indicates occurrence of additional information in a chapter.
1.2. Keyboard and function
1.3. Device operation indicators
The operation of particular devices is indicated by means of LED lights placed next to the keys (⇒
section 1.2 page 3) and by the first segment of the display. Individual lines on the display, when lit up,
indicate the operation of: the CH pump, the heater and the grate– see the figure below:
– CH pump operation,
– heater operation,
PROGRAM
ON
/
OFF
MANUAL
MODE
SIGNALING
AUTOMATIC MODE
FAN MANUAL SWITCHING
/
UP
WARD VALUE CHANGE
AUTOMATIC MODE
SIGNALING
MAINTAIN MODE
FEEDER
M
ANUAL SWITCHING
/
DOWNWARD VALUE CHANGE

GH10PD USER MANUAL PAGE 4
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
– grate.
2. GENERAL FEATURES
The GH10PD Controller is a microprocessor-based device manufactured using the Surface Mount
Technology (SMT).
It is designed to control the main Central Heating (CH) water circuit. Control parameters can be
adjusted to the current operating conditions and boiler type. The Controller includes a system protecting it
from power outages and various other disturbances.
The GH10PD Controller is fitted with:
•Inputs analog:
1. for boiler output water temperature measurement (NTC sensor),
•a digital input:
2. for check position of grates (Reed Relay),
3. for Room thermostat
It also contains five outputs allowing direct connection of 230 V AC devices, i.e.: the fan, the burner feeder,
the grate, the CH circulation pump and the ignition heater.
IT IS ABSOLUTELY NECESSARY TO DISCONNECT THE
CONTROLLER FROM THE MAIN DURING STORMS
3. TECHNICAL DATA
Working voltage 230V AC +10% -1 %
Resistance characteristics
for NTC sensors
Working temperature from + °C to +40°C
Humidity from 20% to 80% RH
Temperature
°C
Re
si
stanc
e
Ω
Fan and Feeder protection 3,1 A
0 7174,89
Sensor type NTC 2,2kΩ
10 4374,83
Temp. sensor operating range 0°C÷100°C
20 2747,10
30 1774,91
Output Maximum
continuous load
40 1172,09
0 79 ,08
CH pump 1A 2 0W
60 47,9
Grate 1A 2 0W
70 384,62
Burner feeder* 1A 2 0W
80 27 ,86
Fan* 1A 2 0W
90 202,37
Heater 3A 7 0W
100 149,16

GH10PD USER MANUAL PAGE 5
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
*I case of co ectio co trollers with co tactor or i termediary
relay. User should apply dedicated to the outputs que cher
co structio (for example: varistor co structio ).
If this ki d of protectio will be omit, This ca cause i correct worki g
or damage outputs i co troller.
4. ELECTRICAL SYSTEM AND CONNECTION RULES
Boiler room should be equipped with 230V/ 0Hz electrical system according to applicable regulations.
Electrical system (regardless of its type) should end with a plug-in socket equipped with protective contact.
Using a socket without connected protective contact may result in electric shock !!!
The controller needs to be connected to a separate power supply line protected with a properly selected
quick fuse and differential current switch (anti-electric shock). It is forbidden to connect any other
equipment to this line !!!
THE CONTROLLER IS POWERED FROM 230V/50HZ MAINS
ANY REPAIRS MAY BE CARRIED OUT ONLY WITH POWER SUPPLY
CUT OFF AT THE FUSE
5. QUICK START
Carry out the following operations in order to activate the GH10PD controller quickly:
1. Connect the unit to the mains (plug in power supply cable).
⇒

GH10PD USER MANUAL PAGE 6
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
Switch on the controller using push-button . The following screen will appear:
Press push-button . The following screen will appear:
and the controller will start automatic operation based on preset factory parameters.
Table 1. Factory settings chart.
User
parameter Description
Factory
settings
U0 Boiler preset temperature* 60
0
C
U1 Feeder working time 1 s
U2 Feeder stop time 4 s
U3 Maintain time** 1 min
U4 Fan speed
U
The number of grate rotation in heating
mode and sustain mode 3
* When there is no lock on the room thermostat.
** When U3 = 0 in sustain mode the feeder and fan do not operate, and return to automatic initiates the
firing up process.

GH10PD USER MANUAL PAGE 7
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from APRIL 2013
6. OPERATION OF THE GH10PD
6.1. System configuration
Fig. 1. Central Heating circuit
INPUT
OUTPUT
T1 – Boiler temperature
P1 – Burner feeder
Tp – Room thermostat
P2 – Fan
C1 – Reed relay grate P3 – Heater
P4 – CH pump
P – Grate
6.2. Automatic operation mode
By pressing , you can enable the automatic operation mode – the Controller lights up the upper
indicator on ( ).
6.2.1. Firing up
The condition for FIRING UP mode is U3=0 and:
1. Exiting room panel lock and returning to automatic mode
2. Exiting sustain mode and returning the controller to automatic mode
This mode of operation is indicated by the blinking of the upper indicator on ( ). Firing up
consists in controlling the burner feeder, the fan and the ignition heater so as to switch to the Automatic
Operation Mode (if F34=0, then the ignition heater cycle is skipped – Controller without ignition heater
support) without the need to enable it manually.

GH10PD USER MANUAL PAGE 8
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
The fan operates continuously providing the output indicated in the F36 service setting and the
Controller additionally indicates whether it activates the feeder, the fan or the heater.
The heater activation and operation are indicated by means of a horizontal line on the left side of
the display, in the lower sign segment, on the Controller main display screen (⇒ section 1.3 page 4). During
the firing up operation the grate is all time off.
The firing up process follows the scheme below:
Start Firing up
Fuel container
+
Fan
Heater
+
Fan
F35
FUEL
FEEDING
FIRING UP
PHASE 1
F34
1
2
FIRING UP
MODE 2
F37
3
1
2
AUTOMATIC
MODE
3
N
O
Flame detection
?
1
-Cycle
1
2
-Cycle
2
3
-Cycle
3
LEGEND:
3
1
2
N
O
2
YES
Flame detection
?
AUTOMATIC
MODE
YES
AUTOMATIC
MODE
Flame detection
?
N
O
TAK
YES
Fan
4
GOING OUT
ALARM 14
1
2
3
Increase number
of cycle
Fig. 2. Diagram showing firing up process.
6.2.2. Burner feeder
The burner feeder operates according to the values set in the user settings U1 – “Feeder work time”
and U2 – “Feeder stop time”. Activation and operation of the burner feeder is indicated by the lower
indicator on .
6.2.3. Grate
The burner feeder operates according to the values set in the user settings U5 – “The number of rate
rotation in heatin mode and in sustain mode” .
a) In sustain mode when U3>0 :
In SUSTAIN mode, the fuel feeder operates according to the value set by the user in parameter U . The
grate activation and operation are indicated by means of a horizontally line on the left side of the display,
in the lower sign segment, on the Controller main display screen (⇒ section 1.3 page 4).

GH10PD USER MANUAL PAGE 9
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
In the firing up mode of operation the grate is off. It stats working when firing up process is finish.
The Grate start its work from the U parameter - “The number of rate rotation in heatin mode and in
sustain mode” .
The Grate start its work o ly whe the bur er feeder stops, a d worki g accordi g to the values set i
the user setti gs U5 – “The umber of grate rotatio i heati g mode a d i sustai mode” .
b) In sustain mode when U3=0:
The fuel grate does not operate in sustain mode
6.2.4. CH pump
In the AUTO mode, the CH pump is activated when the temperature of the boiler water is higher or
equal to the value set in the F06 service setting (factory setting is 40°C).
The CH pump activation and operation are indicated by means of a vertical line on the left side of
the display, in the upper sign segment, on the Controller main display screen (⇒ section 1.3 page 4).
The Controller deactivates the pump when the water temperature drops to the activation
temperature - 4°C. (If the CH pump activation temperature is 40°C, then the CH pump deactivation
temperature is 36°C).
6.2. . Fan
In the AUTO mode, the fan operates continuously until the boiler temperature reaches the value set by
the user in the U0 setting. During that period the fan operates at the speed set in the U4 setting. Fan
activation and operation are indicated by the upper indicator on .
6.2.6. Maintain operation mode
The Controller switches into this mode when the boiler temperature reaches the value set by the
user in the U0 setting.
This mode of boiler operation is indicated by the lower indicator on ( ).
If U3>0
The fuel feeder and the fan remain inactive in this mode for the period set by the user in the U3
settings.When the period ends, the Controller activates the feeder and fan for the period set by the
manufacturer in the F20 service setting.
The fan operates for a period appropriately longer than the feeder for the time set in the F1 service
setting in order to fire up the added fuel.
The Controller exits the MAINTAIN mode and return to the AUTO mode if the boiler temperature drops to
the value equal to: U0 - F05.
The CH pump operates in the same manner as in the AUTO mode.
If U3=0
The fan, feeder and heater remain off until SUSTAIN mode is exited and automatic mode in initiated.

GH10PD USER MANUAL PAGE 10
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from APRIL 2013
6.3. Manual operation mode
Pressing causes the Controller to switch from automatic to manual mode, and immediately
deactivates the fan, the feeder and the pump.
In this mode, you can manually and independently activate and deactivate the fuel feeder , grate, pump
CH and the fan. To do this, follow the scheme below:
To activate or inactivate the CH pump, press the following keys simultaneously: + . The CH
pump activation and operation are indicated by means of a vertical line on the left side of the display, in the
upper sign segment, on the Controller main display screen (⇒ section 1.3 page 4). The grate is inactivate after
inputs reed relay change from open to close. To activate or inactivate the grate, press the following keys
simultaneously: + . The grate activation and operation are indicated by means of a horizontal line on
the left side of the display, in the lower sign segment, on the Controller main display screen (⇒ section 1.3
page 4).
6.4. Viewing flame temperatures
After pressing , the display shows water temperature at the boiler outlet. Flame sensor
measurement is available in the AUTO and MAINTAIN modes, but only if the flame sensor are properly
enabled. Press to view the flame sensor measurement. Press the key again to exit the view. You can
also wait for automatic exit 10s from pressing the key.
6.5. Alarms
The Controller uses different alarms. In each alarm condition, the Controller displays the alarm number
and activates the alarm sound output. In case of several alarm conditions occurring simultaneously, their
numbers are displayed in sequence. You can exit an alarm condition only by pressing , except the AL12
alarm. Alarms:
• AL1 → STB activated or fuse blown
• AL2 → Boiler water outlet temperature sensor failure
• AL9 → No grate rotation / reed relay failure
• AL12 → Boiler overheating
• AL13 → Boiler burnout
STEP 1 STEP 2
→
Controller
indicates water
temperature
measured on the
boiler
Burner feeder
Lower key indicator lights
up. Press the key again to
deactivate the feeder and the
indicator.
Fan
Upper key indicator lights
up. Press the key again to
deactivate the feeder and the
indicator.

GH10PD USER MANUAL PAGE 11
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
6.6. Power failure
After power failure the Controller resumes operation according to the condition it was in before the power
failure. The Controller waits 1 minute for the mains power parameters to stabilise, and then resumes
operation with the previously entered settings.
During the waiting period, the display shows time in seconds remaining until the end of the period,
together with indication of its condition before the power outage:
•blinking “A” for AUTO mode,
•blinking “P” for MAINTAIN mode,
•blinking “r” for MANUAL mode.
Respective indicators (AUTO or MAINTAIN ) are blinking together with the letters.
6.7. Boiler burnout detection
6.7.1. No fuel
If during automatic operation the boiler outlet water temperature remains below the F0 setting for a
period of time set in the F09 setting, then the Controller considers the boiler as “burned out” and enters the
AL13 alarm condition.
6.7.2. Sudden Drop of Outlet Water Temperature
If during automatic operation the boiler outlet water temperature drops by 10°C, and during that
dropping period the temperature does not rise by 4°C, then the CH pump is switched off, and the Controller
goes into the burnout detection mode.
The Controller waits for the period of time set in the F10 setting, during which it checks whether a rise
of 4°C occurs. If YES, then the burnout detection condition is stopped, and the CH pump (if necessary) is
started. If NOT, this means that the furnace is burned out – the Controller enters the AL13 alarm condition.
7. USER SETTINGS
7.1. Boiler preset temperature (U0)
You can change the boiler temperature setting applying the following procedure:
STEP 1 STEP 2 STEP 3
→ or →
The green LED lights up
on the key.
The display shows
current temperature
setting.
Set the new desired
temperature within the
range permitted by the
boiler manufacturer.
Save the new
temperature setting.
Move to the U1
setting.
If duri g setti g the ew temperature o e of the followi g
keys , , is pressed for 15 s, the ew temperature will
ot be saved a d the Co troller will exit the programmi g mode.

GH10PD USER MANUAL PAGE 12
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
7.2. Feeder working time (U1)
This setting informs the user about the time for which the fuel feeder will be activated in the AUTO mode.
Settings are within range of 2s to 2 0s.
You can change the setting using the following procedure:
STEP 1 STEP 2 STEP 3
STEP 4
→
→
or →
The green LED lights
up on the key.
The display shows
U0 parameter
current setting.
Go to U1
Set the new desired
value.
Save the new
temperature
setting.
Move to the U2
setting.
7.3. Feeder stop time (U2)
This is the period of time between two consecutive fuel feeds in the AUTO mode. Settings are within the
range from s to 2 0s.
You can modify this setting applying a procedure similar to the one described in section 7.2.
7.4. Maintain time (U3)
This is the period of time after which the Controller activates the feeder and fan for the period set by the
manufacturer for the MAINTAIN mode to prevent burning out of the boiler. Settings range is from 1 min. to
2 0 min. When U3=0 in SUSTAIN mode, the fan, feeder and heater do not turn on, and each return to
AUTOMATIC mode starts FIRING UP mode. You can modify this setting in a manner similar to the one
described in section 7.2.
7.5. Fan speed (U4)
This setting determines the fan rotation speed, and thus the amount of air delivered. It allows adjusting
the fan speed according to the type and quality of the fuel used.
This setting can be set within the range of 1÷10, where “1” denotes the minimum speed, and “10” the
maximum speed. You can modify this setting in a manner similar to the one described in section 7.2.
7.6. The number of grate rotation in heating mode and sustain mode (U5)
This setting determines the number of grate rotation in heating mode and sustain mode, thus the amount
of ash throw out. It allows adjusting the number of grate rotation according to the type and quality of the fuel
used. This setting can be set within the range of 1÷10. You can modify this setting in a manner similar to the
one described in section 7.2.

GH10PD USER MANUAL PAGE 13
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
. TEMPERATURE LIMITER (STB)
The GH10PD Controller can be equipped with an additional independent temperature limiter STB via
terminals 1 and 16.
WHEN THE TEMPERATURE LIMITER IS NOT USED, TERMINALS 15
AND 16 SHOULD BE SHORTED.
If due to boiler temperature rise the temperature limiter is activated and opens its terminals, it will disable
feeder and fan power supply in order to stop fuel and air delivery do the boiler. After approximately s from
limiter activation the Controller indicates the AL1 alarm.
Return to normal boiler operation is possible when the boiler temperature drops to a level enabling limiter
reset (temperature level depends on the limiter model used).
For safety reasons the Controller does not resume automatic operation on its own.
For the Controller to resume operation you have to, after resetting the limiter, press twice:
– pressing for the first time cancels the alarm and disables the Controller,
– pressing for the second time reactivates the Controller,
– pressing causes the Controller to switch to automatic operation mode.
CAPILLARY TUBE PUNCTURE OR BREAKAGE INDICATES THAT
TEMPERATURE LIMITER FILLED WITH LIQUID LEAKS, WHICH RESULTS IN
ABNORMAL OPERATION OF THE GH10PD CONTROLLER.
IN CASE IF THE ABOVE-MENTIONED DEFECT IS FOUND, IT WILL BE
NECESSARY TO DISCONNECT TEMPERATURE LIMITER FROM THE
GH10PD CONTROLLER, REMOVE IT AND REPLACE WITH A NEW DEVICE.
9. ROOM THERMOSTAT
The GH10PD controller can cooperate with external room thermostat ( Fig.1), which can put coal
boiler in blockade position when temperature is reached in room.
During blockade position C.H. pump stay off after 4 minutes, for the moment when temperature in room is
reached (short circuit contact). The boiler start working in maintain operation mode.
The controller GH10TA passing from automatic operation to maintain operation mode just from time
to time, when the boiler temperature is higher than minimum temperature adjust in F03 service parameter.
When room thermostat put controller in blockade position, the boiler is in maintain operation mode and boiler
temperature fall down less than F03 service parameter than the controller come back to automatic operation
mode until both conditions will be accomplish.
The controller supports the room panel of our manufacture. The controller responses to the panel orders
if the controller is under the automatic operation mode. Where the malfunction occurs to the connection with
the panel, the controller will resume the operation with the user programmed settings.
The illuminated dot
on the segment on the left-hand side of the display shows that the communication link is operable.

GH10PD SERVICE MANUAL PAGE 14
10. CONNECTING DEVICES TO THE GH10PD CONTROLLER
OUTPUTS INPUTS
14
L
—
Fan (P2)
50, 51
—
Boiler temperature (T1)
1
2
N
—
Fan (P2)
52, 53
—
Room thermostat (Tp)
11
L
—
Burner feeder (P1)
56, 57
—
Grate reed relay (C1)
09
N
—
Burner feeder (P1)
06
L
—
CH pump (P4)
05
N
—
CH pump (P4)
0
L
—
Grate (P )
07
N
—
Grate (P )
04
L
—
Heater (P3)
03
N
—
Heater (P3)
02
N
—
Power AC 230V
01
L
—
Power AC 230V
Fig. 3 Diagram of connections between equipment, sensors and the GH10PD controller.
ANY ADDITIONAL EQUIPMENT MAY BE CONNECTED TO THE GH10PD
CONTROLLER ONLY BY PERSON LICENSED TO PERFORM ELECTRICAL
INSTALLATION WORKS.

GH10PD USER MANUAL PAGE 15
PPUH “GECO” Sp. z o.o. [Ltd.] Issue III Valid from April 2013
11. INFORMATION ON LABELLING AND COLLECTION OF WORN OUT ELECTRICAL
AND ELECTRONIC EQUIPMENT
CAUTION!
This symbol placed on the product or its packaging indicates the need for
selective collection of worn out electrical and electronic equipment. It
means that this product should not be disposed of with other household
wastes. Proper disposal of aged and worn out electrical and electronic
equipment will help to avoid potentially adverse effects for environment
and human health.
It is the user’s responsibility to collect worn out equipment separately,
and to return it to an authorized disposal company.

P.P.U.H. „Geco” Sp. z o.o. [Ltd.]
Cholerzyn 376, 32-060 Liszki
Poland
ph.+48 12/636-98-11, 636-12-90
fax. +48 12/636-20-02
http://www.geco.pl
e-mail: [email protected]
Table of contents
Other Geco Controllers manuals
Popular Controllers manuals by other brands

e-con Systems
e-con Systems See3CAM CX3RDK Series Application User's Manual

SpaNet
SpaNet SV Series quick start guide

Bosch
Bosch Buderus Logamatic 5000 Series Guideline

RBM
RBM RinoxPlus M Technical sheet

Victron energy
Victron energy BlueSolar PWM-Light 12/24-5 manual

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual

Siemens
Siemens SSA Series Mounting instructions

Linear Technology
Linear Technology LTC4365 Demo Manual

Dirt Devil
Dirt Devil M024 Series operating manual

Süd wind
Süd wind ambientika WallPanel manual

3One data
3One data IAP2300C Series Quick installation guide

United CoolAir
United CoolAir MARVEL MINI Installation, operation and maintenance manual