Geco GH20SB User manual

P.P.U.H. „Geco” spółka z o. o.
32-060 Liszki, Cholerzyn 376
tel. 012 6369811, 6361290
fax. 012 6362002
____________________________________________________
USER MANUAL
FOR SOLAR COLLECTOR
SYSTEM CONTROLLER
GH20SB
Software release 02A

GH20SB – User Manual PAGE 2
PPUH “GECO” Sp. z o.o. Release I FROM 05/01/2015
CONTENTS
1.
Controller Description..............................................................................................................4
2.
Connecting External Devices....................................................................................................5
3.
Controller Usage........................................................................................................................6
3.1.
Enabling the Controller............................................................................................................6
3.2.
Standby Mode. .........................................................................................................................6
3.3.
Operation..................................................................................................................................6
3.3.1.
Main Screen........................................................................................................................6
3.3.2.
Main Menu Screen.............................................................................................................7
3.3.3.
System Scheme Selection...................................................................................................8
3.3.4.
Settings Configuration Menu Screen .................................................................................8
3.3.5.
Controller Configuration Menu Screen............................................................................15
3.3.6.
Manual Control ................................................................................................................18
3.3.7.
Cooling.............................................................................................................................19
3.3.8.
Energy and Collector Power Counters.............................................................................19
3.3.9.
Holiday function...............................................................................................................21
4.
Settings .....................................................................................................................................23
4.1.
Control Settings......................................................................................................................23
4.2.
Controller Settings..................................................................................................................25
5.
Additional Functions...............................................................................................................26
5.1.
Collector Freezing Prevention Function ................................................................................26
5.2.
Anti-Legionella Function.......................................................................................................26
5.3.
Holiday Function....................................................................................................................26
5.4.
Manual Cooling Function.......................................................................................................26
6.
Controller Operation Scheme................................................................................................27
6.1.
Scheme 1 – the basic scheme.................................................................................................27
6.2.
Scheme 2 – the basic scheme with a circulation pump..........................................................27
6.3.
Scheme 3 – the basic scheme with a circulation pump and a gas boiler................................28
6.4.
Scheme 4 – the basic scheme with a circulation pump and an electric heater.......................28
6.5.
Scheme 5 – the basic scheme with a circulation pump and a heat pump...............................29
6.6.
Scheme 6 – the basic scheme with a circulation pump, activating domestic hot water heating
after the boiler achieves the required temperature..........................................................................29
6.7.
Scheme 7 – a system of two heaters allows additional heating of the boiler heater with solar
energy..............................................................................................................................................30
6.8.
Scheme 8 – a system of two heaters allows additional heating of the circulation return with
solar energy. ....................................................................................................................................30
6.9.
Scheme 9 – a system with a three-way valve for domestic hot water heating and pool water
heating. Additional control of the pool water filtering system pump. ............................................31
6.10.
Scheme 10 – a system with two collector pumps for domestic hot water heating and pool
water heating. Additional control of the pool water filtering system pump. ..................................31
6.11.
Scheme 11 – a system with a three-way valve for domestic hot water heating in two solar
heaters with additional control of a circulation pump.....................................................................32
6.12.
Scheme 12 – a system with two collector pumps for domestic hot water heating in two solar
heaters with additional control of a circulation pump.....................................................................32
6.13.
Scheme 13 – a system allowing the cooperation of collectors with the buffer container used
for cooperation with the SH............................................................................................................33

GH20SB – User Manual PAGE 3
PPUH “GECO” Sp. z o.o. Release I FROM 05/01/2015
6.14.
Scheme 14 – a domestic hot water heating system with solar collectors. Additionally the
system controls a gas boiler and activates domestic hot water heating after the boiler achieves the
required temperature. ......................................................................................................................33
6.15.
Scheme 15 – a system allowing control of pumps cooperating with collector batteries placed
in various directions; additionally the system controls a circulation pump....................................34
6.16.
Scheme 16 – a system allowing control of pumps cooperating with collector batteries placed
in various directions. The system allows domestic hot water heating in two heaters.....................34
6.17.
Scheme 17 – the basic scheme with a circulation pump, allowing emergency water dump
from the heater. ...............................................................................................................................35
7.
Sensor Error Alarm................................................................................................................35
8.
Information on Marking and Collection of Waste Electric and Electronic Equipment ..35

GH20SB – User Manual PAGE 4
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
1. Controller Description
The GH20SB Controller is a device designed and manufactured to support systems with solar
collectors. The product was base on a reliable state-of-the-art microprocessor technology. The
Controller is modern in its design and very easy to use as it is equipped with a user panel with a
transparent keyboard and an LCD graphic display.
Its advantage is an extensive package of basic options greatly enhancing its functionality. These are:
A selection of 17 various system configurations,
System scheme display,
Device operation animation in the system scheme,
Collector pump rotation speed adjustment,
External device manual control option,
Calculation of collector instantaneous power,
Inbuilt real-time clock,
Controller status memory after disconnecting power supply,
Extensive average collector power statistics menu,
Extensive energy counters menu,
Holiday function,
Anti-legionella function,
Collector overheating prevention function,
Anti-freeze function,
Collector type selection function (flat plate / tube).
Additionally the Controller has been equipped with a number of features facilitating its use:
Transparent menu,
Graphic presentation of time intervals,
Selection of many language versions,
Easy and quick control settings configuration.

GH20SB – User Manual PAGE 5
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
2. Connecting External Devices
The GH20SB Controller is equipped with 4 inputs enabling connection of NTC10K
temperature sensors and three outputs enabling connection of external devices, pumps or three-way
valves, depending on the system scheme chosen. A drawing contains a graphic presentation of the
input and output marking. The description of the Controller inputs and outputs is provided in the
table.
Marking of Controller inputs and outputs
Input/Output Description
Un Mains connection (230VAC~/ 50Hz)
O1 Main pump output
Maximum current rating: 3.15A
O2 Relay output – dry, switch relay
Maximum current rating: 8A
- S1-S2 – NC (normally closed),
- S2-S3 – NO (normally open).
O3 Relay output – live, 230VAC~
Maximum current rating: 8A
O4 Mains power outlet 230VAC~ bridged within the Controller. This output
may be bridged outside with the switch relay output, thus providing
switching power supply for controlling e.g. a three-way valve.
T1,T2,T3,T4 Temperature sensor inputs – NTC10k
Description of Controller inputs and outputs
When connecting devices to the Controller outputs it must be remembered that outputs
marked as O1 and O3 are live outputs to which an external device may be connected directly. The
O2 output is dry and to be placed in series between the power source and the external device.

GH20SB – User Manual PAGE 6
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
3. Controller Usage
The GH20SB controller can’t be connection with electronic flow meter. Before
you start using controller make sure that “Measurmem” parameter is adjust to
“Rotameter”. (pkt. 3.3.4.5.)
3.1. Enabling the Controller
After connecting the Controller to the power supply, controller for about 5 second make
touch-pad keyboard calibration, and inform user about this fact by inscription on the display:
“Keyboard calibration, Do not touch sensors”
After connecting the Controller to power supply the Collector will be activated in the
standby mode (if before deactivation it was in the standby mode) or in the operation mode (if before
deactivation it was in the operation mode).
If touch sensors display doesn’t work correct please make calibration process again.
Before you start next calibration Please turn of the controller from the power supply for a moment.
3.2. Standby Mode.
In this mode the LCD display is slightly backlit and the Controller name and the current
software release are shown on the screen.
In the standby mode all outputs remain disabled and the alarm sounds are inactive.
Press to cause the Controller to exit the standby mode and switch to the operation mode.
3.3. Operation.
3.3.1. Main Screen.
In the upper line of the LCD display, on the left, the number of the currently supported
system scheme is shown. In the middle and on the right the time and date are shown. Below the
time and date line, on the left, the system scheme and the collector pump control level are
displayed. The digits in the scheme represent the numbering of the temperature sensors. You need
to ensure that the sensors are properly installed, as described in the scheme. Sensor substitution may
result in control system malfunction.
On the right of the system scheme the temperatures measured by sensors are shown. T1
corresponds to the temperature measured by sensor 1, T2 corresponds to the temperature measured

GH20SB – User Manual PAGE 7
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
by sensor 2 etc. The Controller is designed to ensure that it is not necessary to install all four
temperature sensors. You need to install only those sensors which are necessary for control. If a
sensor necessary for control is not installed or damaged, next to the sensor symbol on the screen the
word ”Err” will appear, indicating that there is no sensor or it is damaged. In this case all external
devices will be deactivated and the Controller will raise alarm indicated by an intermittent audio
signal. If a sensor not required for control is not connected to the controller or is damaged, the
Controller will not raise alarm, and on the screen the temperature will be replaced with the symbol
“-----”.
Below the displayed temperatures, in the lower right-hand corner of the screen, the
collectors’ instantaneous power is displayed as calculated by the Controller. When the collector
pump is deactivated or the sensor on the collector return (as a rule it is sensor T3) is disconnected,
the power indication is replaced with the symbol “-----”. For systems numbered 6, 10, 12, 14, 15
and 16 the power calculation option is not available.
Depending on the control status, additional symbols may appear on the screen, such as:
“L” – active anti-legionella function.
Holiday symbol – active holiday function.
Cooling symbol – active cooling function.
Press to cause the Controller to switch to the standby mode.
Press to cause the Controller to switch to the main menu screen.
3.3.2. Main Menu Screen
On the main menu screen you can choose the following Controller functions:
Scheme selection,
Settings configuration,
Controller settings configuration,
Manual control,
Cooling settings configuration,
Energy counters view,
Holiday function.
Press and to switch between options.
To confirm the selection of an option press .
Press to return to the main screen.
Press to cause the Controller to switch to the standby mode.

GH20SB – User Manual PAGE 8
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
3.3.3. System Scheme Selection
The Controller allows controlling 17 different configurations of solar collector systems. To
choose the desired configuration of the collector system, choose “Scheme Selection” on the main
menu screen.
When you go to the system scheme selection screen, on the display screen a figure appears
representing the system scheme and accompanied by its number.
Press and to change the system scheme.
Press to save changes and return to the main menu screen.
Press to cancel changes and return to the main menu screen.
Press to cancel changes and cause the Controller to switch to the standby mode.
3.3.4. Settings Configuration Menu Screen
To go to the settings configuration menu choose “Parameters settings” on the main menu
screen.
In the settings configuration menu you can:
Choose control settings edition option,
Choose circulation pump C time programme editing option,
Choose boiler/heater K time programme editing option,
Choose heating medium freezing point editing option,
Choose rated and minimum flow editing option,
Choose maximum and minimum collector pump rotation speed editing option,
Enter factory values of control settings.

GH20SB – User Manual PAGE 9
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
Depending on the currently selected system scheme some of the above options may be hidden (they
will not appear in the menu).
Press and to switch between options.
To confirm the selection of an option press .
Press to return to the main menu screen.
Press to cause the Controller to switch to the standby mode.
3.3.4.1. Control Settings Editing
To edit control settings choose “Control parameters” on the main menu screen and then
“Parameters settings” on the settings configuration menu screen.
On this screen you can change the configuration of the following settings:
Solar collector type (Flat /Tube) ,
T1, T2 temperatures difference for deactivating collector pump (2…15ºC),
Temperatures difference for activating additional pump, valve (2…15ºC),
Max. temp. T2 OFF collectors pump (10…85ºC)
Min. temp. T3 ON boiler pump (10…85ºC
Min. temp. T4 ON circulation pump (10…85ºC)
Max. temp. T4 OFF source of heat (10…85ºC)
Max. temp. of water heated in boiler C (10…85ºC)),
Regulation of collectors pump (No / Yes)),
Circulation pump mode (Discon / Continuous)),
Coll. Power OFF boiler heater, heat source (100…3000W)),
Overheat protection of collectors ON (No / Yes)),
MaxTemp. T2 overheat protection OFF (60…85ºC)),
Freezing protection of collectors ON (No / Yes)),
Selection of heating priority (A / B)),
Protection against Legionella (No / Yes)),
Disabling boiler K operation by activating boiler C (No / Yes).

GH20SB – User Manual PAGE 10
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
Depending on the currently selected system scheme some of the above settings may be hidden.
Press and to switch between settings.
Press to edit the current setting. During edition the setting value flashes. Press and
to define a new value. Press to save the new value and exit the setting edition option. Press
to cancel the change and exit the setting edition option.
Press (when setting edition is not active) to return to the settings configuration menu screen.
Press to cause the Controller to switch to the standby mode.
3.3.4.2. Editing Circulation Pump C Time Programme
To edit the circulation pump C time programme choose “Parameters settings” on the main
menu screen and then “Time program C” on the settings configuration menu screen.
The external devices operating hours setting mode allows setting time separately for week
days (Monday-Friday) and for Saturday and Sunday. The horizontal arrow shown above the scale at
the top of the screen indicates the hour range active for edition.
The edition of the time programme begins with defining the device operation on weekdays
(Monday-Friday). To change the hour displayed use and . After setting the last hour in
this range the Controller will switch to editing the time programme for Saturday, and after setting
the last hour for Sunday it will switch to editing the time programme for Sunday.
To activate or deactivate an external device at a selected hour, press . If the device is
set to operate during the selected hour, it will be indicated by a white field on the hour scale. To
deactivate the device for the selected hour, use the key to put out the white field above the
hour scale.
Press to save new settings and return to the settings configuration menu screen.
Press to cancel changes and cause the Controller to switch to the standby mode.
3.3.4.3. Editing Boiler/Heater K Time Programme
To edit the boiler / heater K time programme choose “Parameters settings” on the main
menu screen and then “Time program K” on the settings configuration menu screen.

GH20SB – User Manual PAGE 11
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
To set the time zones for the device marked with “K” on the scheme follow the same
procedure as when selecting working hours for circulation pump C.
3.3.4.4. Editing Heating Medium Freezing Point
To edit heating medium freezing point choose “Parameters settings” on the main menu
screen and then “Heat transfer fluid” on the settings configuration menu screen.
When you go to this screen the setting value flashes. Press and to define a new
heating medium freezing point temperature in the range from -35 to 0ºC.
Press to save the new value and return to the settings configuration menu.
Press to cancel changes and return to the settings configuration menu.
Press to cancel changes and cause the Controller to switch to the standby mode.
3.3.4.5. Editing Rated and Minimum Flow
To edit rated and minimum flow choose “Parameters settings” on the main menu screen and
then “Flow rate” on the settings configuration menu screen.

GH20SB – User Manual PAGE 12
PPUH “GECO” Sp. z o.o. FROM 05/01/2015
On this screen you can edit:
Speed (1...3)
Measurem: (Rotameter/Electr.916)
The nominal flow (0.5…30.0l/min),
the minimum flow (0…rated flow–0.5l/min).
The GH20SB controller can’t be connection with electronic flow meter. Before
you start using controller make sure that “Measurmem” parameter is adjust to
“Rotameter”. (pkt. 3.3.4.5.)
If the “Regulation of collectors pump” is set to “No” the minimum flow will be hidden (it cannot
be edited).
If the “Regulation of collectors pump” is set to “Yes” the minimum flow will be hidden (it can be
edited).
Press and to switch between these settings and press to edit the highlighted
setting.
During active edition the setting value flashes. Use and to set a new value. Press
to save the new value and exit the setting edition option. Press to cancel the change and
exit the setting edition option.
Press (when setting edition is not active) to return to the settings configuration menu screen.
Press to cause the Controller to switch to the standby mode.
3.3.4.6. Factory Control Settings
To restore factory control settings choose “Ustaw. parametrów” (Settings Config.) on the
main menu screen and then “Nastawy fabryczne” (Factory Settings) on the settings configuration
menu screen.
When you choose this option the Controller will ask for confirmation of factory settings
restoration. Press to restore factory control settings and return to the settings configuration
menu screen. Press to return to the settings configuration menu, the control settings will
remain unchanged.
The values of the factory control settings depend on the currently set system scheme

GH20SB – User Manual PAGE 13
Setting
System scheme number
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Typ kolektora
słonecznego (Solar
collector type)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Płaski
(Flat
plate)
Różnica temp. T1,T2
włącz. Pompy kolektorów
(T1, T2 temperatures
differences for activating
collector pump)
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
6ºC
Różnica temp. włączenia
dod. pompy, zaworu
(Temperatures differences
for activating additional
pump, valve)
- - - - - 5ºC
5ºC
5ºC
5ºC
5ºC
5ºC
5ºC
5ºC
5ºC
- - -
Max. temp. T2
wyłączenia pompy
kolektorów (Max. T2
temperature for
deactivating collector
pump)
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
65ºC
Min. temp. T3
uruchomienia pompy
kotła (Min. T3
temperature for activating
boiler pump)
- - - - - 41ºC
- - - - - - - 41ºC
- - -
Min. temp. T4 włączenia
pompy cyrkulacyjnej
(Min. T4 temperature for
activating circulation
pump)
- 35ºC
35ºC
35ºC
35ºC
35ºC
35ºC
- - - 35ºC
35ºC
- - 35ºC
- 35ºC
Max. temp. T4
wyłączenia źródła ciepła
(Max. T4 temperature for
deactivating heat source)
- - 50ºC
50ºC
50ºC
50ºC
50ºC
- 30ºC
30ºC
65ºC
65ºC
- 50ºC
- 65ºC
80ºC
Max. temp. wody grzana
z kotła C (Max.
temperature of water
heated in boiler C)
- - - - - - - - - - - - - 65ºC
- - -
Regulacja obrotów pompy
kolektorów (Collector
pump rotation speed
adjustment)
Tak
(Yes)
Tak
(Yes)
Tak
(Yes)
Tak
(Yes)
Tak
(Yes)
- Tak
(Yes)
Tak
(Yes)
Tak
(Yes)
- Tak
(Yes)
- Tak
(Yes)
- - - Tak
(Yes)

GH20SB – User Manual PAGE 14
Tryb pracy pompy
cyrkulacyjnej (Circulation
pump operation mode)
- Przer.
(Interm
.)
Przer.
(Interm
.)
Przer.
(Interm
.)
Przer.
(Interm
.)
Przer.
(Interm
.)
Przer.
(Interm
.)
Przer.
(Interm
.)
- - Przer.
(Interm
.)
Przer.
(Interm
.)
- Przer.
(Interm
.)
Przer.
(Interm
.)
- Przer.
(Inter
m.)
Moc kolekt. wyłącz.
kotła, grzałki, pompy
ciepła (Collector power
for deactivated boiler,
heater, heat pump)
- - 1500W
1500W
1500W
- - - - - - - - - - - -
Ochrona przed
przegrzaniem kolektorów
(Collector overheating
prevention)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Max. temp. T2 wył.
ochrony przegrz.
kolektorów (Max. T2
temperature for
deactivating collector
overheating prevention)
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
80ºC
Ochrona przed
zamrożeniem kolektorów
(Collector freezing
prevention)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Nie
(No)
Wybór priorytetu grzania
(Heating priority
selection)
- - - - - - - - B
B
B
B
- - - B
-
Ochrona przed bakteriami
Legionella (Protection
from Legionella)
- - Nie
(No)
Nie
(No)
- - - - - - - - - Nie
(No)
- - -
Blokada pracy kotła K
uruchomieniem kotła C
(Blocking boiler K
operation by activating
boiler C)
- - - - - - - - - - - - - Nie
(No)
- - -
Factory control settings

GH20SB – User Manual PAGE 15
3.3.5.Controller Configuration Menu Screen
To go to the Controller configuration menu choose “Controller settings” on the main menu
screen.
In the Controller configuration menu you can:
Choose date and time edition option,
Choose display settings edition option,
Choose sound edition option,
Choose language selection option.
Press and to switch between options.
To confirm the selection of an option press .
Press to return to the main menu screen.
Press to cause the Controller to switch to the standby mode.
3.3.5.1. Editing Date and Time
To go to date and time edition screen choose “Controller settings” on the main menu screen
and then “Date and Time” on the Controller configuration menu screen.

GH20SB – User Manual PAGE 16
Press and to change to flashing (edited) value.
Press to edit the next value. If you press it when editing the year then the new time and date
will be saved and you will return to the Controller configuration menu screen.
Press to cancel changes and return to the Controller configuration menu.
Press to cancel changes and cause the Controller to switch to the standby mode.
3.3.5.2. Display Settings Editing
To edit display settings choose “Controller settings” on the main menu screen and then
“Display” on the Controller configuration menu screen.
On this screen you can edit:
Display backlight intensity (1…10),
Inactivity time after which the backlight will be automatically turned off (1…10min).
Press and to switch between these settings and press to edit the currently
highlighted setting.
During active edition the setting value flashes. Use and to set a new value. Press
to save the new value and exit the setting edition option. Press to cancel the change and
exit the setting edition option.
Press (when setting edition is not active) to return to the Controller configuration menu
screen.
Press to cause the Controller to switch to the standby mode.

GH20SB – User Manual PAGE 17
3.3.5.3. Sound Settings Editing
To edit sound settings choose “Controller settings” on the main menu screen and then
“Sound settings” on the Controller configuration menu screen.
On this screen you can edit:
Alarm sounds (Yes / No),
Keys (Yes / No).
Press and to switch between these settings and press to edit the currently
highlighted setting.
During active edition the setting value flashes. Use and to set a new value. Press
to save the new value and exit the setting edition option. Press to cancel the change and
exit the setting edition option.
Press (when setting edition is not active) to return to the Controller configuration menu
screen.
Press to cause the Controller to switch to the standby mode.
3.3.5.4. Language Selection
To go to the language selection screen choose “Controller settings” on the main menu screen
and then “Language” on the Controller configuration menu screen.

GH20SB – User Manual PAGE 18
Use and to select the desired language.
Press to save the new language settings and return to the Controller configuration menu
screen.
Press to cancel changes and return to the Controller configuration menu screen.
Press to cancel changes and cause the Controller to switch to the standby mode.
3.3.6. Manual Control
To go to the manual control screen choose “Manual control” on the main menu screen.
»The LCD display will show the system scheme screen and (on the right side of the screen)
letters will appear that correspond to the devices in the scheme together with a description of the
external device status (ON / OFF).
NOTE!!!
After switching to manual operation the control algorithm is wholly suspended and the user has full
control over the status of the outputs (external devices).
Depending on the selected system configuration, the Controller can operate from 1 to 3
external devices. Each device can be separately activated and deactivated, and its current status is
always shown in the system scheme and on the right side of the display, next to the letter describing
the device. To switch between devices use and Press to unlock the possibility of
changing the status of the currently highlighted output, which is indicated by the flashing of the
output status symbol (ON / OFF). Press and to change the device status and then press
to lock the current output status.
Press to restore control and return to the main menu screen.
Press to cause the Controller to switch to the standby mode.

GH20SB – User Manual PAGE 19
3.3.7. Cooling
To choose the cooling settings editing option choose “Cooling” on the main menu screen.
On this screen you can activate cooling and set the temperature of cooling activation and
deactivation.
Press and to switch between settings.
Press to choose current setting editing option. During edition the setting value flashes. Press
and to set a new value. Press to save the new value and exit the setting edition
option. Press to cancel the change and exit the setting edition option.
Press (when setting edition is not active) to return to the main menu screen.
Press to cause the Controller to switch to the standby mode.
3.3.8. Energy and Collector Power Counters
The energy and collector power counters function is not available for schemes 6, 10, 12, 14,
15, 16.
The Controller has an inbuilt module for recording average collector power and the energy
generated by the collectors. The Controller enables recording and readout of power and energy
statistics for the following time intervals:

GH20SB – User Manual PAGE 20
Last 60 recorded days,
Last 20 recorded weeks,
Last 12 recorded months,
Last 10 recorded years,
Additionally, for days, weeks, months and years statistics there is possibility to present the time
intervals graphically, by means of bar charts:
For daily statistics it is possible to graphically present the hourly distribution of the average
collector power and energy,
For weekly statistics it is possible to graphically present the distribution of average power
and energy for individual days in the interval from Monday to Sunday,
For monthly statistics it is possible to graphically present the distribution of the average
power and energy for individual days, The interval depends on the number of days in the
month viewed,
For annual statistics it is possible to graphically present the distribution of average power
and energy for individual months in the year in intervals from January to December.
When the graphical presentation in the form of bar charts is displayed, in the left upper-corner of
the screen the highest value in the given interval appears, to which the height of each bar is scaled.
Additionally, in the right-hand upper corner the series recording date appears.
The energy counters menu includes also the total energy counter. This counter counts, on a
continuous basis, the energy generated since the Controller activation.
The statistics and the total counter may be reset anytime. The reset options are to be found in
the energy counters menu and available separately for the total counter and for the statistics.
A change of date may disturb the sequence of the recorder data.
To view the energy counters or reset the counters, choose “Energy statistics” on the main menu
screen.
3.3.8.1. Average Collector Power Counters
To view average collector power counters choose “Energy statistic” on the main menu
screen and then “Collector Power” on the energy counters menu screen.
Report type selection option will appear on the screen:
Day Report,
Week Report,
Month Report,
Year Report,
Table of contents
Other Geco Controllers manuals