1 Safety instructions
Electrical devices may be mounted and connected only by electrically skilled
persons.
Serious injuries, fire or property damage are possible. Please read and follow the
manual fully.
2 Intended use
– External sensor for measuring ambient temperature
– Connection to a suitable room temperature controller
3 Mounting and electrical connection
DANGER!
Electric shock when live parts are touched.
Electric shocks can be fatal.
Always disconnect before carrying out work on the device or installation. For this,
switch off all the corresponding circuit breakers, secure against being switched on
again, and check that there is no voltage. Cover up adjacent live parts.
The remote sensor must be mounted in an empty tube so that the sensor is mechan-
ically protected and can be exchanged if necessary.
The supplied device connection terminal is used for connection to Pushbutton
sensor 4 Komfort.
4 Technical data
Dimensions Ø×H 7.8 × 27 mm
Sensor cable S03VV-F 2 x 0.5 mm²
Length connecting cable 4 m
Degree of protection IP 67
Remote sensor resistance values
Temperature
(°C)
Resistance
(kΩ)
Temperature
(°C)
Resistance
(kΩ)
5 89.5 30 26.2
10 68.8 35 20.9
15 53.5 40 16.7
20 41.9 45 13.5
25 33.0 50 11.0
3 / 4
32406912 10870484 25.05.2023
Remote sensor