User Notices
◆The power supply for all indoor units must be unified.
◆Prohibit installing the wired controller at wet or sunshine places.
◆Do not knock, throw or frequently disassemble the wired controller.
◆Do not operate the wired controller with wet hands.
◆In one system network, you must set one indoor unit as the master indoor unit,
Other indoor units are slave indoor units .
◆The operation mode of the system is basing on that of master indoor unit.
Master indoor unit can switch to any modes, while slave unit can’t switch to the
mode that is conflicting with master indoor unit.
◆When master indoor unit changes mode which cause operation mode of
slave indoor unit conflicts with that of system, the operation mode of slave unit
will switch to the operate mode of system automatically.
◆When two wired controllers control one (or more) indoor unit(s), the address of
wired controller should be different.
◆Functions with “*”are optional for indoor units. If a function is not included in an
indoor unit, wired controller can’t set the function, or setting of this function is
invalid to the indoor unit.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

CONTENTS
1 DISPLAY ..........................................................................................................1
1.1 LCD OFWIRED CONTROLLER............................................................1
1.2 LCD DISPLAYINSTRUCTION...............................................................2
2 BUTTONS........................................................................................................5
2.1 BUTTON GRAPHICS..............................................................................5
2.2 FUNCTION INSTRUCTION OF BUTTONS.........................................6
3 INSTALLATION AND COMMISSIONING...................................................7
3.1 INSTALLATION OF WIRED CONTROLLER........................................8
3.1.1 Communication Line Selection.......................................................8
3.1.2 Installation requirements.................................................................9
3.1.3 Wiring Requirements .....................................................................10
3.1.4 Installation .......................................................................................14
3.1.5 Disassembly....................................................................................15
3.2 COMMISSIONING.................................................................................15
3.2.1 Set Master Indoor Unit...................................................................15
3.2.2 Parameter Enquiry.........................................................................16
3.2.3 Parameter Setting ..........................................................................21
4 OPERATION INSTRUCTIONS...................................................................26
4.1 ON/OFF...................................................................................................26
4.2 MODE SETTING....................................................................................27
4.3 TEMPERATURE SETTING..................................................................28
4.4 FAN SETTING........................................................................................29
4.5 TIMER SETTING....................................................................................30
4.5.1 General Timer.................................................................................30
4.5.2 Clock Setting...................................................................................33
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

4.5.3 Clock Timer .....................................................................................33
4.6 SWING SETTING...................................................................................37
4.7 QUIET SETTING....................................................................................38
4.8 SLEEP SETTING...................................................................................41
4.9AIR SETTING*........................................................................................41
4.10 LIGHT ON/OFF SETTING..................................................................45
4.11 SAVE SETTING....................................................................................45
4.12 FILTER CLEAN REMINDER SETTING............................................52
4.13 X-FAN SETTING..................................................................................55
4.14ABSENCE SETTING...........................................................................56
4.15 REMOTE SHIELD FUNCTION..........................................................56
4.16 CHILD LOCK FUNCTION...................................................................57
4.17 GATE-CONTROL FUNCTION ...........................................................57
5 ERROR DISPLAY.........................................................................................58
5.1 TABLE OF ERROR CODES FOR OUTDOOR UNIT.........................59
5.2 TABLE OF ERROR CODES FOR INDOOR UNIT.............................61
5.3 TABLE OF DEBUGGING CODES.......................................................62
5.4 TABLE OF STATUS CODES ................................................................64
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
1
1 DISPLAY
Fig. 1.1 Appearance of wired controller
1.1 LCD OF WIRED CONTROLLER
Fig. 1.2 LCD graphics of wired controller
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
2
1.2 LCD DISPLAY INSTRUCTION
Table 1.1 LCD display instruction
No.
Symbols
Instructions
1
Up and down swing function
2
*
Left and right swing function
3
It's valid under Save mode and displays during setting process.
Temperature lower limit for Cooling: Limit the minimum
temperature value under Cooling or Dry mode.
Temperature upper limit for Heating: Limit the maximum
temperature value under Heating, Space Heating or 3D Heating
mode.
4
*
Auto mode (Under Auto mode, the indoor units will
automatically select their operating mode as per the
temperature
change so as to make the ambient comfortable.)
5
It shows the setting temperature value(In case the wired
controller is controlling a Fresh Air Indoor Unit, then the
temperature zone will display FAP)
6
Cooling mode
7
Dry mode
8
Fan mode
9
Heating mode
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
3
10
When inquiring or setting project number of indoor unit, it
displays "NO." icon
11
*
Floor Heating mode (When Heating and Floor Heating
simultaneously shows up, it indicates 3D Heating is activated.)
12
Display "SET" icon under parameter setting interface
13
-*
Space Heating mode
14
Display "CHECK" icon under parameter view interface
15
Outdoor unit operates under Save mode/upper limit of system
capacitor less 100%/remote Save status
16
Sleep status
17
Current set fan speed (including auto, low speed, medium-low
speed, medium speed, medium-high speed, high speed
and turbo seven status)
18
*
Air status, Indoor unit optional function
19
Remind to clean the filter
20
Quiet status (including Quiet and Auto Quiet two status)
21
*
Allow auxiliary electric heating On icon
22
Light On/Off function
23
X-fan function
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
4
24
*
Health function, Indoor unit optional function
25
*
Reserved function
26
Absence function
27
Outdoor unit defrosting status
28
Gate-control function
29
Shielding status
30
Child Lock status
31
One wired controller controls multiple indoor units
32
Save status of indoor unit
33
It indicates the current wired controller is the slave wired
controller (address of wired controller is 02)
34
Memory status (The indoor unit resumes the original setting
state after power failure and then power recovery)
35
Invalid operation
36
Current wired controller connects master indoor unit
37
Timer zone:Display system clock and timer status
Note: When wired controller is connected with different indoor units, some functions will be
different
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
5
2 BUTTONS
2.1 BUTTON GRAPHICS
Fig. 2.1 Button graphics
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
6
2.2 FUNCTION INSTRUCTION OF BUTTONS
Table 2.1 Function instruction of buttons
No.
Buttons
Instructions
1
ENTER/CANCEL
Select and cancel function
2
(1) Set operating temperature of indoor unit
(2) Set Timer
(3) Switch Quiet mode, Air grade, Clean grade, set upper
and lower temperature limit under Save mode
(4) Set and inquiry parameter
5
3
SLEEP
Set Sleep mode
4
FAN
Switch among auto, low speed, low-medium speed,
medium speed, medium-high speed, high speed and
turbo status
6
MODE
Switch Auto,Cooling, Dry, Fan, Heating, Floor Heating,
3D Heating and Space Heating modes for indoor unit.
(Note: The Floor Heating, 3D Heating and Space Heating
function icon will show up when the unit has those
functions.)
7
FUNCTION
Switch among Air, Quiet, Light, Health, Absence, Save,
Clean, E-heater and X-fan functions.
8
TIMER
Timer setting
9
SWING
Set up and down swing status
10
ON/OFF
Indoor unit On/Off
2+5
+
Simultaneously press “ ” and “ ” for 5s to enter or
cancel the Child Lock function.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
7
3 INSTALLATION AND COMMISSIONING
Fig. 3.1 Parts of wired controller
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
8
No.
1
2
3
Name
Panel of wired
controller
Self-tapping Screw ST3.9X25
MA
Soleplate of wired
controller
Q'ty
1
3
1
3.1 INSTALLATION OF WIRED CONTROLLER
3.1.1 Communication Line Selection
Fig. 3.2 Length of communication line
Wire material
type
Total length of
communication line
between indoor unit
and wired controller
L (m/feet)
Wire size
(mm2/AW
G)
Material
standard
Remarks
Light/Ordinary
Polyvinyl
chloride
sheathed
cord.
(60227 IEC 52
/60227 IEC
53)
L≤250m
(L≤820-1/5feet)
2×0.75
mm2~2×
1.25 mm2
(2×AWG1
8~2×AWG
16)
IEC
60227-5:2
007
(1)Total length of
communication line can't
exceed 250m (820-1/5feet).
(2)The cord shall be Circular
cord (the cores shall be
twisted together).
(3)If unit is installed in
places with intense
magnetic field or strong
interference, it is necessary
to use shielded wire.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
9
Note:
①If the air conditioner is installed at the strong electromagnetic interference
place, communication line of the wired controller must use shielding
twisted pair.
②Materials of communication line for wired controller must be selected
according to this instruction manual strictly
3.1.2 Installation requirements
(1) Prohibit installing the wired controller at wet places.
(2) Prohibit installing the wired controller at direct sunshine places.
(3) Prohibit installing the wired controller at the place near high temperature
objects or water-splashing places.
(4) Prohibit installing the wired controller at the place where faces forward to the
window. Prevent abnormal work due to the interference from the other wired
controller around.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
10
3.1.3 Wiring Requirements
There are four network wiring methods between wired controller and indoor unit:
Fig. 3.3 One wired controller controls Fig. 3.4 Two wired controllers control
one indoor unit one indoor unit
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
11
Fig. 3.5 One wired controller controls multiple indoor units simultaneously
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
12
Fig. 3.6 Two wired controllers control multiple indoor units simultaneously
Wiring instructions:
(1) When one wired controller controls multiple indoor units simultaneously, the
wired controller can connect to any one indoor unit, but the connected indoor
unit must be the same series indoor unit. The total quantity of indoor unit
controlled by wired controller can't exceed 16 sets, and the connected indoor
unit must be within the same indoor unit's network. Wire controller must set
quantity of group control indoor units. Please refer to 3.2.3 Parameters Setting.
(2) When two wired controllers control one indoor unit, the addresses of those two
wired controllers should be different. Please refer to 3.2.3 parameter setting.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
13
(3) When two wired controllers control multiple indoor units, wired controller can
connected to any one indoor unit, while the connected indoor unit should be
the same series indoor unit. The addresses of those two wired controllers
should be different. Please refer to 3.2.3 parameter setting. The total quantity
of indoor unit controlled by wired controller can't be more than 16 sets and all
connected indoor units must be within the same indoor unit network. Wire
controller must set quantity of group control indoor units. Please refer to 3.2.3
Parameters Setting.
(4) When one (or two) wired controller(s) control(s) multiple indoor units at the
same time, the controlled indoor unit's setting should be the same.
(5) Wiring of wired controller and indoor unit network must be according to one of
the four wiring method as shown in fig 3.3-3.6. As for the connection method
shown in fig 3.4 and 3.6, there should be only one master wired controller
(address is 01) and one slave wired controller (address 02). The quantity of
wired controller can't exceed two.
Note:
Series of indoor units include:①Common Multi VRF Units;②Fresh Air Units;③
Double-heat Sources Units;④Combined Units; Except for fresh air units,
double-heat sources units and combined units, the rest of indoor units belong to
common multi VRF units.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
14
3.1.4 Installation
Fig. 3.7 Installation diagram for wired controller
Fig. 3.7 is the simple installation process of wired controller; please pay
attention to the following items:
(1) Before installation, please cut off the power for indoor unit.
(2) Pull out the two-core twisted pair from the installation hole on wall, and then
pull this wire through the " ” shape hole at the rear side of Soleplate of wired
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
15
controller.
(3)Stick the bottom plate of wired controller on the wall and then use Self-tapping
Screw ST3.9X25 MA to fix Soleplate and installation hole on wall together.
(4) Connect two-core twisted pair to H1 and H2 wiring column and then fix the
screws.
(5) Set two-core into the groove at left side of wiring column, and then bundle
panel and Soleplate of wired controller together.
Note: If the wire size of the selected communication line is too large, you can peel
some sheath layer of communication wire to satisfy installation requirements.
3.1.5 Disassembly
Fig. 3.8 Disassembly diagram of wired controller
3.2 COMMISSIONING
3.2.1 Set Master Indoor Unit
Under Off status, long press MODE button for 5s to set the corresponding
indoor unit of wired controller as master indoor unit. “MASTER” icon will be light
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Wired Controller XK46
16
after finishing setting.
Note:
①There is a master indoor unit in a system, other slave indoor units can be set
as master unit, in which case, the original master unit will become a slave
unit.
②In one system, only one set of master indoor unit is allowed. If system detects
that there are several master units, it will designate the unit with the smallest
project number as a master unit.
3.2.2 Parameter Enquiry
Unit parameters can be checked in unit On or Off status.
(1) Long press “FUNCTION” button for 5s to enter the interface of viewing unit
parameters. “C00” is displayed in temperature zone and “CHECK” icon is light;
(2) Press “ ” or “ ” button to select parameter code;
(3) Press “ENTER/CANCEL” button to return to last step until exits viewing
parameters.
The parameter enquiry list is as following:
Table 3.1 Parameters viewing list
Paramet
er
code
Parameter
name
Parameter
range
Viewing method
C00
Entrance of
adjustable
parameter
--
In “C00” status, Timer zone shows the current
indoor unit project number. When one wired
controller is controlling multiple indoor units,
then only the smallest project number will be
displayed.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Other manuals for XK46
2
Table of contents
Other Gree Controllers manuals