Gree XK46 User manual

Change for life
Wired Controller XK46
Commercial Air Conditioners
Owner's Manual
Thank you for choosing Commercial Air Conditioners ,please read this owner’s manual
carefully before operation and retain it for future reference.
GREE reserves the right to interpret this manual which will be subject to any change due
to product improvement without further notice.
GREE Electric Appliances, Inc. of Zhuhai reserves the nal right to interpret this manual.

User Notices
◆The power supply for all indoor units must be unied.
◆Prohibit installing the wired controller at wet or sunshine places.
◆Do not knock, throw or frequently disassemble the wired controller.
◆Do not operate the wired controller with wet hands.
◆In one system network, you must set one indoor unit as the master indoor
unit.
◆When two wired controllers control one (or more) indoor unit(s), the
address of wired controller should be different.

CONTENTS
1 DISPLAY...............................................................................................1
1.1 LCD of Wired Controller ............................................................................. 1
1.2 LCD Display Instruction.............................................................................. 2
2. BUTTONS ...........................................................................................4
2.1 Button Graphics.......................................................................................... 4
2.1 Function Instruction of Buttons .................................................................. 4
3. INSTALLATION AND COMMISSIONING ...........................................5
3.1 Installation of Wired Controller ................................................................... 5
3.2 Commissioning........................................................................................... 9
4. OPERATION INSTRUCTIONS..........................................................12
4.1 On/Off....................................................................................................... 12
4.2 Mode Setting ............................................................................................ 12
4.3 Temperature Setting ................................................................................. 13
4.4 Fan Setting ............................................................................................... 13
4.5 Timer Setting ............................................................................................ 13
4.6 Swing Setting ........................................................................................... 16
4.7 Quiet Setting............................................................................................. 16
4.8 Sleep Setting ............................................................................................ 17
4.9 Air Setting ................................................................................................. 18
4.10 Light On/Off Setting................................................................................ 19
4.11 Save Setting ........................................................................................... 19

4.12 Filter Clean Reminder Setting ................................................................ 21
4.13 X-fan Setting........................................................................................... 22
4.14 Out Setting ............................................................................................. 22
4.15 Remote Shield Function ......................................................................... 22
4.16 Child Lock Function................................................................................ 23
4.17 Gate-control Function............................................................................. 23
5. ERROR DISPLAY..............................................................................23
5.1 Table of Error Codes for Outdoor Unit...................................................... 24
5.2 Table of Error Codes for Indoor Unit......................................................... 25
5.3 Table of Status Codes .............................................................................. 25
5.4 Table of Debugging Codes ....................................................................... 26

Wired Controller XK46
1
1 DISPLAY
Fig. 1.1 Appearance of wired controller
1.1 LCD of Wired Controller
Fig. 1.2 LCD graphics of wired controller

Wired Controller XK46
2
1.2 LCD Display Instruction
Table 1.1 LCD display instruction
No. Symbols Instructions
1 Up and down swing function
2 Left and right swing function
3
It's valid under Save mode and displays during setting process.
Temperature lower limit for Cooling: Limit the minimum temperature value under
Cooling or Dry mode.
Temperature upper limit for Heating: Limit the maximum temperature value
under Heating, Floor Heating, Space Heating or 3D Heating mode.
4
Auto mode (Under Auto mode, the indoor units will automatically select their
operating mode as per the temperature change so as to make the ambient
comfortable.)
5 It shows the setting temperature value
6 Cooling mode
7 Dry mode
8 Fan mode
9 Heating mode
10 When inquiring or setting project number of indoor unit, it displays "NO." icon
11 Floor Heating mode (When Heating and Floor Heating simultaneously shows
up, it indicates 3D Heating is activated.)
12 Display "SET" icon under parameter setting interface
13 Space Heating mode
14 Display "CHECK" icon under parameter view interface
15 Outdoor unit operates under Save mode/upper limit of system capacitor less
100%/remote Save status
16 Sleep status
17 Current set fan speed (including auto, low speed, medium-low speed, medium
speed, medium-high speed, high speed and turbo seven status)
18 Air status
19 Remind to clean the lter
20 Quiet status (including Quiet and Auto Quiet two status)
21 Allow auxiliary electric heating On icon

Wired Controller XK46
3
22 Light On/Off function
23 X-fan function
24 Health function
25 When Fresh Air is on, this unit is the fresh air unit
26 Out function
27 Outdoor unit defrosting status
28 Gate-control function
29 Shielding status
30 Child Lock status
31 One wired controller controls multiple indoor units
32 Save status of indoor unit
33 It indicates the current wired controller is the slave wired controller (address of
wired controller is 02)
34 Memory status (The indoor unit resumes the original setting state after power
failure and then power recovery)
35 Invalid operation
36 Current wired controller connects master indoor unit
37 Timer zone:Display system clock and timer status
Note: When wired controller is connected with different indoor units, some functions will be different

Wired Controller XK46
4
2. BUTTONS
2.1 Button Graphics
Fig. 2.1 Button graphics
2.1 Function Instruction of Buttons
Table 2.1 Function instruction of buttons
No. Buttons Instructions
1ENTER/
CANCEL Select and cancel function
2(1) Set operating temperature of indoor unit
(2) Set Timer
(3) Switch Quiet mode, Air grade, Clean grade, set upper and lower
temperature limit under Save mode
(4) Set and inquiry parameter
5
3 SLEEP Set Sleep mode
4FAN Switch among auto, low speed, low-medium speed, medium speed,
medium-high speed, high speed and turbo status
6 MODE
Switch Auto,Cooling, Dry, Fan, Heating, Floor Heating, 3D Heating and
Space Heating modes for indoor unit. (Note: The Floor Heating, 3D
Heating and Space Heating function icon will show up when the unit has
those functions.)
7 FUNCTION Switch among Air, Quiet, Light, Health, Out, Save, Clean, E-heater and
X-fan functions.
8 TIMER Timer setting
9 SWING Set up and down swing , left and right swing status
10 ON/OFF Indoor unit On/Off
2+5 +Simultaneously press “ ” and “ ” for 5s to enter or cancel the Child
Lock function.

Wired Controller XK46
5
3. INSTALLATION AND COMMISSIONING
112 22
5
3
82.5
40
112
42.5
R3.3
6-R2.7
22
Unit:mm
Fig. 3.1.1 Dimension of wired controller
31 2
Fig. 3.1.2 Parts of wired controller
No. 1 2 3
Name Panel of wired controller Screw M4*25 Soleplate of wired controller
Q'ty 1 3 1
3.1 Installation of Wired Controller
3.1.1 Communication Line Selection
L=L01+L02+L1+L2+......+L(n-1)(n≤16)
L1
L0
Indoor unit 1
Indoor unit 2 Indoor unit 3 Indoor unit n
Master wired
controller
Slave wired
controller
1L02
L2 L(n-1)
Fig. 3.2 Length of communication line
Wire material type
Total length of
communication line
between indoor unit and
wired controller L (m)
Wire size (mm2)Material
standard Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤250 2×0.75~2×1.25 IEC 60227-
5:2007
Total length of
communication line
can't exceed 250m
Note:
① If the air conditioner is installed at the strong electromagnetic interference place,
communication line of the wired controller must use shielding twisted pair.
② Materials of communication line for wired controller must be selected according to this
instruction manual strictly.

Wired Controller XK46
6
3.1.2 Installation requirements
(1) Prohibit installing the wired controller at wet places.
(2) Prohibit installing the wired controller at direct sunshine places.
(3) Prohibit installing the wired controller at the place near high temperature objects or water-
splashing places.
(4) Prohibit installing the wired controller at the place where faces forward to the window.
Prevent abnormal work due to the interference from the other wired controller around.
3.1.3 Wiring Requirements
There are four network wiring methods between wired controller and indoor unit:
D1D2H1H2
D1 D2
Indoor unit
Outdoor unit
D1D2H1H2
D1 D2
Outdoor unit
Indoor unit
Fig. 3.3 One wired controller
controls one indoor unit Fig. 3.4 Two wired controllers
control one indoor unit

Wired Controller XK46
7
D1D2 H1H2
D1 D2H1 H2
D1D2H1H2
D1 D2
Indoor unit 1 Indoor unit 2 Indoor unit 16
Outdoor unit
Fig. 3.5 One wired controller controls multiple indoor units simultaneously
D1D2H1H2
D1D2H1H2
D1D2 H1H2
D1 D2
Indoor unit 1 Indoor unit 2 Indoor unit 16
Outdoor unit
Fig. 3.6 Two wired controllers control multiple indoor units simultaneously
Wiring instructions:
(1) When one wired controller controls multiple indoor units simultaneously, the wired controller
can connect to any one indoor unit, but the connected indoor unit must be the same series
indoor unit. The total quantity of indoor unit controlled by wired controller can't exceed 16
sets, and the connected indoor unit must be within the same indoor unit's network.
(2) When two wired controllers control one indoor unit, the addresses of those two wired
controllers should be different. Please refer to 3.2.3 parameter setting.

Wired Controller XK46
8
(3) When two wired controllers control multiple indoor units, wired controller can connected
to any one indoor unit, while the connected indoor unit should be the same series indoor
unit. The addresses of those two wired controllers should be different. Please refer to
3.2.3 parameter setting. The total quantity of indoor unit controlled by wired controller can't
be more than 16 sets and all connected indoor units must be within the same indoor unit
network.
(4) When one (or two) wired controller(s) control(s) multiple indoor units at the same time, the
controlled indoor unit's setting should be the same.
(5) Wiring of wired controller and indoor unit network must be according to one of the four
wiring method as shown in g 3.3-3.6. As for the connection method shown in g 3.4 and
3.6, there should be only one master wired controller (address is 01) and one slave wired
controller (address 02). The quantity of wired controller can't exceed two.
3.1.4 Installation
10
1 2 3 4
67
8 9
H1H2
H1H2
H1H2
5
Fig. 3.7 Installation diagram for wired controller
Fig. 3.7 is the simple installation process of wired controller; please pay attention to the
following items:
(1) Before installation, please cut off the power for indoor unit.
(2) Pull out the two-core twisted pair from the installation hole on wall, and then pull this wire
through the " ” shape hole at the rear side of Soleplate of wired controller.
(3) Stick the bottom plate of wired controller on the wall and then use screw M4×25 to fix
Soleplate and installation hole on wall together.
(4) Connect two-core twisted pair to H1 and H2 wiring column and then x the screws.
(5) Set two-core into the groove at left side of wiring column, and then bundle panel and
Soleplate of wired controller together.

Wired Controller XK46
9
Note: If the wire size of the selected communication line is too large, you can peel some sheath
layer of communication wire to satisfy installation requirements.
3.1.5 Disassembly
1 2 3 4
H1H2
H1H2
Fig. 3.8 Disassembly diagram of wired controller
3.2 Commissioning
3.2.1 Set Master Indoor Unit
Under Off status, long press MODE button for 5s to set the corresponding indoor unit of wired
controller as master indoor unit. “MASTER” icon will be light after nishing setting.
3.2.2 Parameter Enquiry
Unit parameters can be checked in unit On or Off status.
(1) Long press “FUNCTION” button for 5s to enter the interface of viewing unit parameters. “C00”
is displayed in temperature zone and “CHECK” icon is light;
(2) Press “ ” or “ ” button to select parameter code;
(3) Press “ENTER/CANCEL” button to return to last step until exits viewing parameters.
The parameter enquiry list is as following:
Table 3.1 Parameters viewing list
Parameter
code Parameter name Parameter
range Viewing method
C00 Entrance of adjustable
parameter - -
C01
View the project
number of indoor unit
in the case that one
wired controller controls
several indoor units at
the same time
1-255:
project
number on-
line indoor
unit
Operation method:
Enter viewing: press MODE button in “C01” status
to enter the interface of viewing indoor unit project
number. Press “ ” or “ ” button to select indoor unit.
Display method:
Temperature zone: displays current indoor unit
number;
Timer zone: displays C5 malfunction of project number
conict/present indoor unit project number.
If master indoor unit exists in current indoor unit
network, “MASTER” icon will be bright under “C01”
interface. After entering the interface of viewing indoor
unit project number, “MASTER” icon will be bright
only when the project number of master indoor unit is
selected.

Wired Controller XK46
10
C03
View the indoor unit
quantity of the system
network
1-80 Timer zone: display indoor unit quantity of the system
C06 View priority operation
00: normal
operation
01: priority
operation
Operation method:
Enter viewing: press MODE button in “C06” status to
enter the interface of viewing priority operation. Press
“ ” or “ ” button to select indoor unit.
Display method:
Temperature zone: displays current indoor unit project
number;
Timer zone: displays current priority operation setting
value of indoor unit.
C07 View indoor ambient
temperature -
Operation method:
Enter viewing: press MODE button in “C07” status
to enter the interface of viewing indoor ambient
temperature. Press “ ” or “ ” button to select indoor
unit.
Display method:
Temperature zone: displays current indoor unit project
number;
Timer zone: displays indoor ambient temperature.
C08 View Filter Clean
Reminder time 4-416: days Timer zone: displays Filter Clean Reminder time
C09 View address of wired
controller 01, 02 Timer zone: displays the address of wired controller
C11
View the indoor unit
quantity in the case that
one wired controller
controls several indoor
units at the same time
1-16 Timer zone: displays the indoor unit quantity controlled
by the wired controller
C12 View outdoor ambient
temperature - Timer zone: displays outdoor ambient temperature
Note:
① Under parameter viewing status, FAN, TIMER, SLEEP and SWING buttons are invalid.
Press “ON/OFF” button to go back to the home page, while not to turn on/off the unit.
② Under parameter viewing status, the signal from remote controller is invalid.
3.2.3 Parameter Setting
Unit parameters can be set in unit On or Off status.
(1) Long press FUNCTION button for 5s and the temperature zone displays “C00”; long
press FUNCTION button for another 5s to enter the interface of setting wired controller
parameters. “P00” is displayed in temperature zone;
(2) Press “ ” or “ ” button to select parameter code. Press MODE button to enter parameter
setting. At that time, parameter value is blinking. Press “ ” or “ ” button to adjust the
parameter value and press ENTER/CANCEL button to nish setting.
(3) Press ENTER/CANCEL button to return to last step until exists setting parameters.

Wired Controller XK46
11
The parameter setting list is as following:
Table 3.2 Parameter setting list
Parameter
code Parameter name Parameter range Default
value Note
P10 Set master
indoor unit
00: do not change
current master/slave
state of indoor unit
01: set current indoor
unit as master indoor
unit
00
When set the corresponding indoor
unit of wired controller as master
indoor unit, MASTER” icon will be
bright after nishing setting.
P11
Set infrared
receiver of wired
controller
00: forbidden
01: activated 01
It can be set only through master
wired controller.
When infrared receiver of wired
controller is forbidden, the wired
controller can’t receive the signal from
remote controller and it is operated
through buttons.
P13 Set address of
wired controller
01: master wired
controller
02: slave wired
controller
01
When two wired controllers control
one indoor unit (or several indoor
units), the addresses of the two
wired controllers should be different.
Assistant wired controller (02)
is without unit parameter setting
function except setting its address.
P14 Set group control
indoor units
00: forbid this function
01-16: indoor unit
quantity
01
Set the corresponding value
according to the connected indoor
unit quantity.
P16 Set unit of
temperature
00:Celsius
01:Fahrenheit 00
P30
Set static
pressure of
indoor fan motor
01-09: static pressure
level of indoor fan motor 05
There are two kinds of static pressure
level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05, 06, 07,
08, 09
Static pressure level range is different
for different models; the wired
controller will automatically select
static pressure level range of indoor
fan motor according to the model of
indoor unit.
P31 High ceiling
installation
00: installation height of
standard ceiling
01: installation height of
high ceiling
00
P33 Set Timer 00: general timer
01: clock timer 00
P34 Clock Timer
repetition is valid
00: once
01: repeat everyday 00 Available only when timer is set to
clock timer.

Wired Controller XK46
12
P37
Cooling setting
temperature
under auto
mode
17°C~30°C(63°F~86°F) 25°C(77°F) When the temperature unit is°C,
cooling setting temperature minus
heating setting temperature≥1°C.
When the temperature unit is°F,
cooling setting temperature minus
heating setting temperature≥2°F.
P38
Heating setting
temperature
under auto
mode
16°C~29°C(61°F~84°F) 20°C(68°F)
P43 Set priority
operation
00: normal operation
01: priority operation 00
When power supply is insufcient, the
indoor units which are set to priority
operation can operate, while other
indoor units are forced to be turned
off.
P46
Clear Filter Clean
accumulated
time
00: do not clear
01: clear 00
Note:
① Under parameter setting status, FAN, TIMER, SLEEP and SWING button are invalid. Press
ON/OFF button to go back to home page, but not turning on/off the unit.
② Under parameter setting status, the signal from remote controller is invalid.
4. OPERATION INSTRUCTIONS
4.1 On/Off
Press ON/OFF button to turn on the unit.
Press ON/OFF button again to turn off the unit.
The interfaces of On/Off status are shown in g. 4.1 and 4.2.
Fig. 4.1 Interface of On status Fig. 4.2 Interface of Off status
4.2 Mode Setting
Under On status, pressing MODE button can set mode circularly as:

Wired Controller XK46
13
OR
Note:
①
the available modes are different for different models, the wired controller will automatically
select mode setting range according to the model of indoor unit.
②
The Auto mode can be only set at the master indoor unit.
③
Under Auto mode, if the indoor unit is running under Cooling, the icons“ ” and “ ” will
light up; if the indoor unit is running under Heating, the icons“ ” and “ ” will light up.
4.3 Temperature Setting
Pressing “ ” or “ ” button in On status increases or decreases set temperature by 1°C;
holding “ ” or “ ” button increases or decreases set temperature by 1°C every 0.3s.
In Cooling, Fan, Heating, Floor Heating, 3D Heating or Space Heating mode, temperature
setting range is 16°C~30°C.
In Dry mode, the temperature setting range is 12°C, 16°C~30°C. In Dry mode, when
temperature is 16°C, continuously press “ ” button twice to decrease temperature to 12°C (when
Save function is activated, the temperature in Dry mode can’t be adjusted to 12°C and the setting
range is “lowest temperature in Save mode” ~ 30°C).
Note: Under Auto mode or Out function is activated, the setting temperature can not be
adjusted by pressing “ ” or “ ”.
4.4 Fan Setting
Under On status, pressing FAN button can set fan speed circularly as:
Note: in Dry mode, fan speed is low and can’t be adjusted.
4.5 Timer Setting
The wired controller is equipped with two kinds of timer: general timer and clock timer. General
timer is factory defaulted setting. Please refer to Section 3.2.3 for the timer setting way.
4.5.1 General Timer
Unit On/Off after a desired hour can be set through general timer.
Set Timer: when timer is not set, press TIMER button to enter timer setting and “HOUR” icon is
blinking. Press “ ” or “ ” button to adjust timer time. Press TIMER button to save the setting and
then exit setting.
Cancel Timer: when timer is set, press TIMER button to cancel it.
Timer setting range: 0.5~24h. Pressing “ ” or “ ” button increases or decreases timer time by
0.5h; holding “ ” or “ ” button increases or decreases timer time by 0.5h every 0.3s.
In unit On status, timer Off setting is as shown in g. 4.3:

Wired Controller XK46
14
Press TIMER button to set timer
Press TIMER button to finish timer setting
Press “ ” or “ ” button to adjust timer time
Press TIMER button to set timer
Press TIMER button to finish timer setting
Press “ ” or “ ” button to adjust timer time
Fig. 4.3 Timer Off setting in unit On status
4.5.2 Clock Setting
Clock display: when the timer setting way is clock timer, timer zone displays system clock in
unit On and Off status. icon is bright and the clock can be set at this time.
Clock setting: long press TIMER button for 5s to enter clock setting and icon is blinking.
Pressing “ ” or “ ” button increases or decreases clock time by 1min; holding “ ” or “ ” button
for 5s increases or decreases clock time by 10min; Press ENTER/CANCEL button or TIMER button
to save the setting and then exit setting.
4.5.3 Clock Timer
Unit On/Off at a certain time can be set through clock timer.

Wired Controller XK46
15
Set Timer:
(1) Press TIMER button to enter timer on setting and the “ON” icon is blinking;
(2) Press “ ” or “ ” button to adjust unit On time. Press ENTER/CANCEL button to finish
setting;
(3) Before pressing ENTER/CANCEL button, pressing TIMER button can save unit On time and
then switch to unit Off time setting with “OFF” icon blinking;
(4) Press “ ” or “ ” button to adjust unit Off time. Press ENTER/CANCEL button to finish
setting;
Cancel Timer:
Press TIMER button to enter timer setting; press TIMER button again to switch to the setting of
unit ON time or unit Off time; press ENTER/CANCEL button to cancel timer.
Pressing “ ” or “ ” button increases or decreases timer time by 1min; holding “ ” or “ ”
button for 5s increases or decreases timer time by 10min.
Clock Timer setting is as shown in g. 4.4:
Press “ ” or “ ” button to adjust unit Off time
Unit is on and timer is not set Press TIMER button to set unit On time
Press TIMER button to switch to unit
Off time setting
Press ENTER/CANCEL button to finish setting
Press “ ” or “ ” button to adjust unit On time

Wired Controller XK46
16
Press “ ” or “ ” button to adjust unit Off time
Unit is on and timer is not set Press TIMER button to set unit On time
Press TIMER button to switch to unit
Off time setting
Press ENTER/CANCEL button to finish setting
Press “ ” or “ ” button to adjust unit On time
Fig. 4.3 Unit On/Off time setting in unit On status
4.6 Swing Setting
Press SWING button in unit On status to start Swing function. There are two kinds of swing
direction: up & down swing and left & right swing. Press SWING button to start swing and stop
swing. Holding SWING button for 5s to switch between up & down swing and left & right swing.
In up & down swing, “Swing” icon changes as following:
(closed)
In left & right swing, “Swing” icon changes as following:
(closed)
Note: the available Swing direction is different for different models; the wired controller will
automatically select swing setting range according to the model of indoor unit.
4.7 Quiet Setting
Quiet Function: decrease the noise of indoor unit and achieve the quiet effect. Quiet function
has two modes: Quiet mode and Auto Quiet mode. It is available only in Auto, Cooling, Dry, Fan,
Heating, 3D heating, Space heating mode.
Turn on Quiet Function: press FUNCTION button to turn to Quiet function and then Quiet icon
“” or auto quiet icon “
AT
” is blinking. At this moment, press “ ” or “ ” button to switch between
quiet and auto quiet, and then press ENTER/CANCEL button to tactivate.
Turn off Quiet Function: press FUNCTION button to turn to Quiet function and then press
ENTER/CANCEL button to cancel Quiet function.