iNels SA3-06M User manual

SA3-06M
1/2
+
-
BUS
BUS
AC 230V L
N
2
28
26
3
38
36
4
48
46
1
18
16
COM 1
6
68
66
5
58
COM 2
56
1
2
3
4
5
4
Switching actuator 6-channel
EN
Characteristics
- The actuator is designed for switching up to six various appliances and loads with potentialless
contact.
- SA3-06M is a switching actuator contains 6 independent relays with changeover potentialless
contacts.
- Maximum load per contact is 8 A/2000 VA/AC1.
- Each of six output contacts are individually controllable and addressable.
-
The relays are divided into two groups, the group of four relays on the bottom terminal switches
the common potential, a pair of relays on top of the terminal switches second common potential.
- The actuator is suitable for operating discontinuously controlled thermo drivesin the distributor
underfloor heating.
- LEDs on the front panel signal the status of each output.
- Contact status of each relay can be changed separately and manually by control buttons on a
front panel.
- SA3-06M is normally supplied in the option AgSnO2contact material.
- SA3-06M in 3-MODULE version is designed for mounting into a switchboard /DIN rail EN60715.
General instrucions
Connection
Description of device
1. Data BUS
2. LED inditaction of unit´s state
3. LED output indication
4. Relay contacts
5. Control buttons
CONNECTION TO THE SYSTEM, INSTALLATION BUS
iNELS3 peripheral units are connected to the system through the BUS installation. Installation
BUS conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be
interchanged. For installation of BUS it is necessary to use a cable with a twisted pair of wires with
a diameter of at least 0.8 mm, the recommended cable is iNELS BUS Cable, whose features best
meet the requirements of the BUS installation. Bearing in mind that in terms of all the properties
is it is possible in most cases also use the cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it
is not recommended as the best option. In the case of a cable with two pairs of twisted wires
it is not possible to use the second pair of the other for modulated signal due to the speed of
communications; it is not possible within one cable to use one pair for one segment BUS and the
second pair for the second segment BUS. For installation of BUS it is vital to ensure that it is kept
at a distance from the power lines of at least 30 cm and must be installed in accordance with its
mechanical properties. To increase mechanical resistance of cables we recommend installation
into a conduit of suitable diameter. BUS topology installation is free except for the ring, wherein
each end of the bus must terminate at the terminals BUS + and BUS- peripheral unit. While
maintaining all the above requirements, the maximum length of one segment of the installation
BUS can reach up to 550 m. Due to the data communication and supply of units in one pair of wires,
it is necessary to keep in mind the diameter of wires with regards to voltage loss on the lead and
the maximum current drawn. The maximum length of the BUS applies provided that they comply
with the tolerance of the supply voltage.
CAPACITY AND CENTRAL UNIT
It is possible to connect to the central unit CU3-01M or CU3-02M two independent BUSes by means
of terminals BUS1+, BUS1- and BUS2+, BUS2-. It is possible to connect to each BUS up to 32 units,
so it is possible to connect directly to the central unit a total of 64 units. It is necessary to comply
with the requirement of a maximum load of one BUS line - maximum up to 1000 mA current. When
connecting units which draw greater than 1A, BPS3-01M with 3A sampling can be used. It is the
sum of the rated currents of the units connected to the BUS line, other units can be connected
using the units MI3-02M, which generate further BUSes. These are connected to the CU3 unit via
the system BUS EBM and you can connect a total of 8 units via EBM BUS to the central unit MI3-02M.
SUPPLYING THE SYSTEM
For supplying power to system units, it is recommended to use the power source of ELKO EP titled
PS3-100/iNELS. We recommend backing up the system with backup batteries connected to the
source of PS3-100/iNELS (see sample diagram of connecting the control system).
GENERAL INFORMATION
To operate the unit, it is necessary that the unit is connected to a central unit CU3 series, connected
to the central unit of the system CU3, or to a system that already contains this unit as its expansion
to include further system.
All unit parameters are set through the central unit CU3-01M in the software iDM3.
There is LED diode on the PCB for indication of supply voltage and communication with the
central unit series CU3. In case that the RUN diode flashes at regular intervals, so there is standard
communication between the unit and BUS. If the RUN diode lights permanently, so the unit is
supplied from BUS, but there is no communication between BUS and unit. In case that RUN diode
is OFF, so there is no supply voltage on the terminals BUS+ and BUS-.
02-97/2017
Rev.1
Made in Czech Republic
SA3-06M
2/2
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: [email protected]
TECHNICAL SUPPORT | E-mail: [email protected] | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Technical parameters Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualification, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting,
servicing, executing any changes, and repairing it is essential to observe safety regulations, norms,
directives and special regulations for working with electrical equipment. Before you start working
with the device, it is essential to have all wires, connected parts, and terminals de-energized. This
instruction manual contains only general directions which need to be applied in a particular
installation. In the course of inspections and maintenance, always check (while de-energized) if
terminals are tightened.
Outputs
Output:
Switching voltage:
Switching output:
Surge current:
Output relays separated
from all internal circuits:
Isolation between relay
inputs COM1 and COM2:
Isolation between individual
relay outputs:
Isolates. voltage open
relay contact:
Max. current terminals
COM1 and COM2:
Min. switched current:
Switching frequency /
no load:
Switching frequency /
rated load:
Mechanical life:
Electrical life AC1:
Output indication:
Communication
Installation BUS:
Power supply
Supply voltage / tolerance:
Dissipated power:
Rated current:
Status indication unit:
Connection
Terminal:
Operating conditions
Air humidity:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Design:
Dimensions and weight
Dimensions:
Weight:
6x changeover 8 A/AC1
250 V AC1, 24 V DC
2000 VA/AC1, 192 W/DC
10 A
reinforced Insulation
(Cat. II surges by EN 60664-1)
reinforced Insulation
(Cat. II surges by EN 60664-1)
basic insulated.
(Cat. II surges by EN 60664-1)
1 kV
16 A
100 mA / 5 V DC
300 min-1
15 min-1
2x 107
5x 104
6x yellow LED
BUS
27 V DC, -20 / +10 %
9 W
60 mA (at 27 V DC), from BUS
green LED RUN
max. 2.5 mm2/ 1.5 mm2with sleeve
max. 80 %
-20 .. +55 °C
-30 .. +70 °C
IP20 device, IP40 mounting in the switchboard
II.
2
any
switchboard on DIN rail EN 60715
3-MODUL
90 x 52 x 65 mm
175 g

Other iNels Controllers manuals

iNels RF KEY User manual

iNels

iNels RF KEY User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels RF KEY-40 User manual

iNels

iNels RF KEY-40 User manual

iNels IDRT3-1 User manual

iNels

iNels IDRT3-1 User manual

iNels RFDA-73M/RGB User manual

iNels

iNels RFDA-73M/RGB User manual

iNels SA3-01B User manual

iNels

iNels SA3-01B User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels SA3-02M User manual

iNels

iNels SA3-02M User manual

iNels RF KEY - 40 User manual

iNels

iNels RF KEY - 40 User manual

iNels RFOWB-20 User manual

iNels

iNels RFOWB-20 User manual

iNels RFDEL-76M User manual

iNels

iNels RFDEL-76M User manual

iNels RF KEY User manual

iNels

iNels RF KEY User manual

iNels SOPHY2 User manual

iNels

iNels SOPHY2 User manual

iNels DA3-22M User manual

iNels

iNels DA3-22M User manual

iNels SA3-012M User manual

iNels

iNels SA3-012M User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels KEY2-01 Simple manual

iNels

iNels KEY2-01 Simple manual

iNels IM2-140M Simple manual

iNels

iNels IM2-140M Simple manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels PS-30/24 Quick guide

iNels

iNels PS-30/24 Quick guide

iNels GSB3-40 User manual

iNels

iNels GSB3-40 User manual

iNels RF KEY User manual

iNels

iNels RF KEY User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

Popular Controllers manuals by other brands

Sunricher SR-ZG9001T-RGBW manual

Sunricher

Sunricher SR-ZG9001T-RGBW manual

Hubbell LXi-2300 Specification sheet

Hubbell

Hubbell LXi-2300 Specification sheet

GF SIGNET 5600 instructions

GF

GF SIGNET 5600 instructions

AGS Merlin 500S user guide

AGS

AGS Merlin 500S user guide

HIMA HIMatrix F3 AIO 8/4 01 manual

HIMA

HIMA HIMatrix F3 AIO 8/4 01 manual

Lucent Technologies Lineage 2000 ECS-6U product manual

Lucent Technologies

Lucent Technologies Lineage 2000 ECS-6U product manual

AKCP SECIO 64 user manual

AKCP

AKCP SECIO 64 user manual

Norac UC5 Topcon X30 installation manual

Norac

Norac UC5 Topcon X30 installation manual

WAREMA LONMSE 2M230 User and installation guide

WAREMA

WAREMA LONMSE 2M230 User and installation guide

Festo VPPM C1 Series operating instructions

Festo

Festo VPPM C1 Series operating instructions

SMC Networks ITV1000-CC Series Operation manual

SMC Networks

SMC Networks ITV1000-CC Series Operation manual

Emulex Fibre Channel user manual

Emulex

Emulex Fibre Channel user manual

Rain AMICO PRO instructions

Rain

Rain AMICO PRO instructions

Deif AGC 200 Series General guidelines for commissioning

Deif

Deif AGC 200 Series General guidelines for commissioning

Norac UC4 Plus Rogator 64 Series installation manual

Norac

Norac UC4 Plus Rogator 64 Series installation manual

Hanna Instruments BL 983317-0 instruction manual

Hanna Instruments

Hanna Instruments BL 983317-0 instruction manual

Madas RG/2MCS manual

Madas

Madas RG/2MCS manual

Pulsar ULTRA 5 Quick start manual

Pulsar

Pulsar ULTRA 5 Quick start manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.