
Installation alternative
SAM 42 can be installed in several different ways, some
of which are shown here.
Further option information is available at nibe.eu/ODM
and in the respective assembly instructions for the ac-
cessories used. See page 21 for a list of the accessories
that can be used with SAM 42.
VOLUME VESSEL
During hot water production, and when F750 is defrost-
ing, no energy is supplied to the climate system. For
this reason, to achieve satisfactory function of the supply
air module, stored energy must be available in the cli-
mate system during these operating cases. If there are
thermostat valves that can block the flow through the
radiators/underfloor heating coils, the volume in these
cannot be included in the system volume.
If the total volume in the climate system (excluding the
heat pump volume) is less than 40 litres, extra system
volume, e.g. volume vessel UKV, has to be connected
to the supply line after the heat pump.
EXTRA CLIMATE SYSTEM
In buildings with several climate systems that require
different supply temperatures, the accessory
ECS 40/ECS 41 can be connected.
SAM 42 is connected to the climate system that has
the lowest supply temperature.
-EP21-RM1
-EP21-GP10-EP21-BT2
-EP21-AA25
-EP21-BT3
-EP21-QN25
-EP21
General ventilation
connection
• Ventilation installation must be carried out in accord-
ance with current norms and directives.
• Connections must be made via flexible hoses, which
should be installed so that they are easy to replace.
• Provision must be made for inspection and cleaning
of the duct.
• Make sure that there are no reductions of cross-sec-
tional area in the form of creases, tight bends, etc.,
since this will reduce the ventilation capacity.
• The air duct system must be a minimum of air tight-
ness class B.
• To prevent fan noise being transferred to the ventila-
tion devices, install silencers in the ducts.
• The outdoor air duct is insulated using diffusion-proof
material (at least PE30 or equivalent) along its entire
length.
• Ensure that the condensation insulation is fully sealed
at any joints and/or at lead-in nipples, silencers, roof
cowls or similar.
• The air must be routed to the outdoor air duct through
an outer wall grille in the facade. The outer wall grille
must be installed so that it is protected from the
weather and must be designed so that no rainwater
and/or snow can penetrate the facade or follow the
air into the duct.
• When positioning the outdoor air and extract air
hood/grille, bear in mind that the two air flows must
not short circuit to prevent the extract air from being
drawn into SAM 42 again.
• When external devices that affect the ventilation are
used, for example kitchen fans and stoves, the heat
pump must be in operation. There is a risk of freezing
at low outdoor temperatures.
• It is not permitted to use a duct in a masonry chimney
stack for outdoor air.
Ventilation flow
The supply air flow must be lower than the exhaust air
flow to prevent over pressure in the house.
The ventilation capacity is set in the heat pump’s menu
system (menu 5.1.6).
13Chapter 4 | Pipe and ventilation connectionsSAM 42