
You can use VVM 500 to cool the house during hot periods
of the year.
Caution
Certain setting options only appear if their function
is installed and activated in VVM 500.
delta at +20 °C
Set the desired temperature on the temperature difference
between supply and return lines to the climate system during
cooling operation when the outdoor temperature is +20 °C.
VVM 500 then attempts to get as close to the set temperat-
ure as possible.
delta at +40 °C
Set the desired temperature on the temperature difference
between supply and return lines to the climate system during
cooling operation when the outdoor temperature is +40 °C.
VVM 500 then attempts to get as close to the set temperat-
ure as possible.
use room sensor
Here you can set whether room temperature sensors are to
be used in cooling mode.
cool/heat sensor
An extra temperature sensor can be connected to VVM 500
in order to determine when it is time to switch between
heating and cooling operation.
When several heating/cooling sensors are installed, you can
select which one of them should be in control.
Caution
When the heating/cooling sensors BT74 have been
connected and activated in menu 5.4, no other
sensor can be selected in menu 1.9.5.
set pt value cool/heat sensor
Caution
This setting option only appears if a room sensor
for cooling/heating is installed and activated in
VVM 500.
Here you can set at which indoor temperature VVM 500 is
to shift between heating respectively cooling operation.
heat at room under temp.
Caution
This setting option only appears if a room temper-
ature sensor is connected to VVM 500 and has
been activated.
Here you can set how far the room temperature can drop
below the desired temperature before VVM 500 switches
to heating operation.
cool at room over temp.
Caution
This setting option only appears if a room temper-
ature sensor is connected to VVM 500 and has
been activated.
Here you can set how high the room temperature can in-
crease above the desired temperature before VVM 500
switches to cooling operation.
larm rumsgivare kyla
This is where you set whether VVM 500 is to initiate an alarm
if the room sensor is disconnected or breaks during cooling
operation.
start active cooling
Caution
This setting option only appears if "active cooling"
is activated in menu 5.2.4.
Here you can set when active cooling is to start.
Degree minutes are a measurement of the current heating
demand in the house and determine when the compressor,
cooling operation respectively additional heat will start/stop.
degree minutes cooling
This selection is only available when the connected access-
ory itself counts cooling degree minutes.
After a min or max value has been set, the system will
automatically set the actual value if the air/water heat pump
is running cooling.
time betw. switch heat/cool
This selection is only available when cooling in 2-pipe sys-
tems.
Here you can set how long VVM 500 is to wait before it re-
turns to heating mode when the cooling demand has ceased
or vice versa.
MENU 1.9.6 - FAN RETURN TIME (ACCESSORY
REQUIRED)
fan return time 1.9.6
speed 1
speed 2
speed 3
speed 4
hrs
hrs
hrs
hrs
speed 1-4
Setting range: 1 –
99 h
Default value: 4 h
Here you select the return time for temporary speed change
(speed 1-4) on the ventilation in menu 1.2.
Return time is the time it takes before ventilation speed re-
turns to normal.
NIBE VVM 500Chapter 3 | VVM 500 – at your service20