Nibe VVM 320 User guide

Installer manual
APH
NIBE™ VVM 320
Indoor module
IHB GB 1613-5
231357

Quick guide
Navigation
Ok button (confirm/select)
Back button (back/undo/exit)
Control knob (move/increase/reduce)
A detailed explanation of the button functions can be found on page 40.
How to scroll through menus and make different settings is described on page 41.
Set the indoor climate
2X
MY INSTALLATION
INDOOR CLIMATE HOT WATER
INFO
The mode for setting the indoor temperature is accessed by pressing the OK button twice, when in the start mode
in the main menu.
Increase hot water volume
2X
1X INDOOR CLIMATE HOT WATER
MY INSTALLATION INFO
To temporarily increase the amount of hot water, first turn the control knob to mark menu 2 (water droplet) and
then press the OK button twice.
In event of disturbances in comfort
If a disturbance in comfort of any type occurs there are some measures that can be taken before you need to
contact your installer. See page 59 for instructions.

Table of Contents
41 Important information
4Safety information
72 Delivery and handling
7Transport
7Assembly
7Supplied components
8Removing the covers
93 Indoor module's design
114 Pipe connections
11General pipe connections
12Dimensions and pipe connections
14Installation alternative
235 Electrical connections
23General
26Connections
28Settings
31Optional connections
34Connecting accessories
356 Commissioning and adjusting
35Preparations
35Filling and venting
36Start-up and inspection
37Setting the cooling/heating curve
38Setting hot water circulation
39Pool
39SG Ready
407 Control - Introduction
40Display unit
41Menu system
448 Control - Menus
44Menu 1 - INDOOR CLIMATE
45Menu 2 - HOT WATER
45Menu 3 - INFO
46Menu 4 - MY SYSTEM
47Menu 5 - SERVICE
559 Service
55Service actions
5910 Disturbances in comfort
59Info menu indoor module
59Manage alarm
59Troubleshooting
6111 Accessories
6312 Technical data
63Dimensions and setting-out coordinates
64Technical specifications
67Electrical circuit diagram, 3 x 400V
72Electrical circuit diagram, 3 x 230V
77Electrical circuit diagram, 1 x 230V
82Index
3Table of Contents |NIBE™ VVM 320

Safety information
This manual describes installation and service proced-
ures for implementation by specialists.
This appliance can be used by children
aged from 8 years and above and per-
sons with reduced physical, sensory or
mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning
use of the appliance in a safe way and
understand the hazards involved. Chil-
dren shall not play with the appliance.
Cleaning and user maintenance shall
not be made by children without super-
vision.
Rights to make any design or technical
modifications are reserved.
©NIBE 2016.
Symbols
NOTE
This symbol indicates danger to machine or
person.
Caution
This symbol indicates important information
about what you should observe when main-
taining your installation.
TIP
This symbol indicates tips on how to facilitate
using the product.
Marking
VVM 320 is CE marked and fulfils IP21.
The CE marking means that NIBE ensures that the
product meets all regulations that are placed on it
based on relevant EU directives. The CE mark is obligat-
ory for most products sold in the EU, regardless where
they are made.
IP21 means that objects with a diameter larger than
or equivalent to 12.5 mm cannot penetrate and cause
damage and that the product is protected against
vertically falling drops of water.
Serial number
The serial number can be found to the left, on top of
VVM 320.
Serial number
Caution
Always give the product's serial number (14
digits) when contacting your installer.
Recovery
Leave the disposal of the packaging to the in-
staller who installed the product or to special
waste stations.
Do not dispose of used products with normal
household waste. It must be disposed of at a
special waste station or dealer who provides this type
of service.
Improper disposal of the product by the user results in
administrative penalties in accordance with current
legislation.
Country specific information
Installer manual
This installer manual must be left with the customer.
NIBE™ VVM 320Chapter 1 | Important information4
1 Important information

Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must
be carried out by a suitably qualified person. Fill in the page for information about installation data in the User
manual.
DateSignatureNotesDescription
✔
Heating medium (page 17)
System flushed
System vented
Expansion vessel
Particle filter
Safety valve
Shut off valves
Boiler pressure
Connected according to outline diagram
Hot water (page 17)
Shut off valves
Mixing valve
Safety valve
Electricity (page 23)
Connected communication
Circuit fuses
Fuses, indoor module
Fuses property
Outside sensor
Room sensor
Current sensor
Safety breaker
Earth circuit-breaker
Setting of emergency mode thermostat
Miscellaneous
Docked to
5Chapter 1 | Important informationNIBE™ VVM 320

Contact information
KNV Energietechnik GmbH, Gahberggasse 11, 4861 SchörflingAT
Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: mail@knv.at www.knv.at
NIBE Wärmetechnik c/o ait Schweiz AG, Industriepark, CH-6246 AltishofenCH
Druzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad JizerouCZ
NIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleDE
Vølund Varmeteknik A/S, Member of the Nibe Group, Brogårdsvej 7, 6920 VidebækDK
NIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaFI
NIBE Energy Systems France Sarl, Zone industrielle RD 28, Rue du Pou du Ciel, 01600 ReyrieuxFR
NIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QGGB
NIBE Energietechniek B.V., Postbus 634, NL 4900 AP OosterhoutNL
ABK AS, Brobekkveien 80, 0582 Oslo, Postadresse: Postboks 64 Vollebekk, 0516 OsloNO
NIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKPL
Tel: 085 662 84 90 Fax: 085 662 84 14 E-mail: sekretariat@biawar.com.pl www.biawar.com.pl
© "EVAN" 17, per. Boynovskiy, Nizhny NovgorodRU
NIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydSE
For countries not mention in this list, please contact Nibe Sweden or check www.nibe.eu for more information.
NIBE™ VVM 320Chapter 1 | Important information6

Transport
VVM 320 should be transported and stored vertically
in a dry place. However, the VVM 320 may be carefully
laid on its back when being moved into a building.
Assembly
■Position VVM 320 on a solid foundation that tolerates
water and the weight of the heat pump. Use the
product's adjustable feet to obtain a horizontal and
stable set-up.
30 - 50 mm
30 - 50 mm
15 - 40 mm
■Because water comes from VVM 320, the area where
the heating pump is located must be equipped with
floor drainage.
Installation area
Leave a free space of 800 mm in front of the product.
All service on VVM 320 can be carried out from the
front.
800
NOTE
Leave 10 – 25 mm free space between the in-
door module and the wall behind for routing
of cables and pipes.
Supplied components
Room sensorOutside sensor
LEK
LEK
LEK
Current sensor*
*Only to 3X400V
Location
The kit of supplied items is placed on top of the
product.
7Chapter 2 | Delivery and handlingNIBE™ VVM 320
2 Delivery and handling

Removing the covers
Front cover
1
2
LEK
LEK
LEK
LEK
LEK
1. Remove the screws from the lower edge of the
front cover.
2. Lift the cover out at the bottom edge and up.
LEK
LEK
LEK
The side covers can be removed to facilitate the install-
ation.
NOTE
50 mm space required to remove the side
panels.
1. Remove the screws from the upper and lower
edges.
2. Twist the cover slightly outward.
3. Move the hatch backwards and slightly to the side.
4. Pull the cover to one side.
5. Pull the hatch forwards.
NIBE™ VVM 320Chapter 2 | Delivery and handling8

VVM 320
Wilo
VVM320
Wilo
VVM320
PF1
PF3
XL4 XL3 XL9 XL8 XL1 XL2
BT63
GP6
EB1
PF1
GP1
AA4
AA4-XJ4
AA4-XJ3
SF1
FL2
FL1
QM20
BT30
FD1
AA1
AA1-S2
FA1
AA2
W130
QM11
BT6
QN10
BT7
BP5
QM22
AA3
9Chapter 3 | Indoor module's designNIBE™ VVM 320
3 Indoor module's design

BF1
XL5
RM1
BT2
BT3
CM1
UB1
UB2
WM1
Pipe connections
Connection, heating medium supply line Ø22
mm
XL1
Connection, heating medium return line Ø22
mm
XL2
Connection, cold water Ø22 mmXL3
Connection, hot water Ø22 mmXL4
Connection, hot water circulation Ø15 mm
(does not apply to copper)
XL5
Connection, docking from heat pump Ø22 mmXL8
Connection, docking to heat pump Ø22 mmXL9
HVAC components
Expansion vessel, closed, heating mediumCM1
Safety valve, water heaterFL1
Safety valve, heating mediumFL2
Circulation pumpGP1
Circulation pump, heating mediumGP6
Venting, climate systemQM20
Venting valve, coilQM22
Reversing valve, climate system/water heating,
flow line
QN10
Filler valve, heating mediumQM11
Check valve, cold waterRM1 1)
TundishWM1
Sensors etc.
Manometer, heating systemBP5
Temperature sensors, heating medium flowBT2
Temperature sensors, heating medium returnBT3
Temperature sensor, hot water, chargingBT6
Temperature sensor, hot water, topBT7
Thermostat, standby modeBT30
Temperature sensor, heating medium supply
after immersion heater
BT63
Electrical components
Immersion heater cardAA1
AA1-S2 Switch (DIP switch) on circuit board
Base cardAA2
Input circuit boardAA3
Display unitAA4
AA4-XJ3 USB socket
AA4-XJ4 Service socket
Energy meterBF12)
Immersion heaterEB1
Miniature circuit-breakerFA1
Temperature limiterFD1
SwitchSF1
Network cable for NIBE UplinkTM
W130
Miscellaneous
Rating platePF1
Serial number platePF3
Cable glandUB1
Cable glandUB2
Designations in component locations according to
standard IEC 81346-1 and 81346-2.
1) Not Denmark and Germany.
2) Applies to VVM 320 R, VVM 320 3x230V R and VVM 320 E EM. Available as accessory EMK 300 for other markets.
NIBE™ VVM 320Chapter 3 | Indoor module's design10

General pipe connections
Pipe installation must be carried out in accordance with
current norms and directives.
VVM 320 together with air/water heat pumps F2030-
7 / F2030-9 or F2040-8 / F2040-12, F2120-8 / F2120-
12 / F2120-16 make up a complete installation for
heating and hot water.
The system requires the radiator circuit to be designed
for a low temperature heating medium. At lowest di-
mensioned outdoor temperature, the highest recom-
mended temperatures are 55 °C on the supply line and
45 °C on the return line, but VVM 320 can handle up
to 65 °C.
Overflow water from the safety valve goes via overflow
cups to a drain so that hot water splashes cannot cause
injury. The entire length of the overflow water pipe
must be inclined to prevent water pockets and must
also be frost proof.
NIBE recommends installing VVM 320 as close to the
heat pump as possible for optimum comfort. For further
information about the location of different compon-
ents, see section "Installation alternatives" in this
manual.
NOTE
Any high points in the climate system, must
be equipped with air vents.
NOTE
The pipe systems need to be flushed out be-
fore the indoor module is connected so that
any debris cannot damage component parts.
NOTE
Switch (SF1) must not be moved to "" or " "
until VVM 320 has been filled with water.
Otherwise the temperature limiter, thermostat
and the immersion heater etc can be dam-
aged.
Boiler and radiator volumes
H
VVM 320 is equipped with a
pressure expansion vessel of
10 litres.
The pre-pressure of the pres-
sure expansion vessel must
be dimensioned according to
the maximum height (H)
between the vessel and the
highest positioned radiator,
see figure. A pre-pressure of
0.5 bar (5 mvp) means a
maximum permitted height
difference of 5 m.
The maximum system volume
excluding the boiler is 220
litres at the above pre-pres-
sure.
11Chapter 4 | Pipe connectionsNIBE™ VVM 320
4 Pipe connections

System diagram
VVM 320 consists of water heater with charge coil, ex-
pansion vessel, safety valve, filler valve, immersion
heater, circulation pumps, buffer vessel and control
system. VVM 320 is connected to the climate system.
VVM 320 is designed for connection and communica-
tion with F2030 / F2040 / F2120, which together make
up a complete heating installation.
When it is cold outdoors F2030 / F2040 / F2120 works
with VVM 320 and if the outdoor air temperature falls
below the heat pump stop temperature, all heating is
carried out by VVM 320.
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-EB15
Symbol key
MeaningSymbol
Venting valve
Shut-off valve
Tapping valve
Non-return valve
Trim valve
Shunt / shuttle valve
Safety valve
Thermometer
T
Temperature sensor
Expansion vessel
Pressure gauge
P
Circulation pump
Particle filter
Particle filter
Fan
Compressor
Heat exchanger
Radiator system
Domestic hot water
MeaningSymbol
Under floor heating systems
Dimensions and pipe
connections
70
1775
560
30-50
600
7575 757560 60
610
25
Wilo
VVM320
XL3XL4 XL8XL9 XL1 XL2
QM20
NIBE™ VVM 320Chapter 4 | Pipe connections12

70
1775
560
30-50
600
7575 757560 60
610
25
Pipe connections
Connection, heating medium supply line Ø22
mm
XL1
Connection, heating medium return line Ø22
mm
XL2
Connection, cold water Ø22 mmXL3
Connection, hot water Ø22 mmXL4
Connection, hot water circulation Ø15 mm
(does not apply to copper)
XL5
Connection, docking in heating medium Ø22
mm
XL8
Connection, docking out heating medium Ø22
mm
XL9
13Chapter 4 | Pipe connectionsNIBE™ VVM 320

Installation alternative
Compatible NIBE air/water heat pumps
Compatible NIBE air/water heat pumps must be
equipped with a control card with display that has the
software version given in the following list as a minim-
um. The control card version is displayed in the heat
pump's display upon start-up.
Software versionProduct
all versionsF2030-7
all versionsF2030-9
all versionsF2040-8
all versionsF2040-12
all versionsF2120-8
all versionsF2120-12
all versionsF2120-16
VVM 320 can be connected to extra water heater, see
below.
Further option information is available at www.nibe.eu
and in the respective assembly instructions for the ac-
cessories used. See page 61 for a list of the accessories
that can be used with VVM 320.
The indoor module can be supplemented with an
electric water heater, if a hot tub or other significant
consumer of hot water is installed. A mixing valve is
then installed on outgoing hot water from the heater.
Water heater with immersion heater
If the valve connector is to be installed externally,
moved out or separated, it must be replaced with a
separable connector Ø 22 mm.
HW fromVVM 320
NIBE™ VVM 320Chapter 4 | Pipe connections14

Explanation
Exhaust air heat pump F135AZ10
Particle filterHQ1
Shut-off valveQM42
Shut-off valveQM43
Shut-off valveQM44
Non-return valveRM1
Pool packageCL11
Unit box with accessory cardAA25
Temperature sensor, poolBT51
Exchanger, poolEP5
Pool, pumpGP9
Charge pumpGP12
Particle filterHQ4
Three way valve, poolQN19
VVM 320EB15
Temperature sensor, heating medium, external
supply
BT25
Connection, heating medium, flow 1XL1
Connection, heating medium, return 1XL2
Connection, cold waterXL3
Connection, hot waterXL4
Connection, docking, from heat pumpXL8
Connection, docking, to heat pumpXL9
Heat pumpEB101
Safety valveFL10
Particle filterHQ1
Shut-off valveQM40
Shut-off valveQM41
External heat source (Oil, gas, pellets or wood
fired boiler with shunt valve)
EM1
Unit box with accessory cardAA25
Temperature sensor, boilerBT52
Expansion vessel, closedCM1
Safety valve, heating mediumFL2
Auxiliary relayKA1
Shunt valveQN11
Climate system 2EP21
Unit box with accessory cardAA25
Temperature sensor, heating medium, flowBT2
Temperature sensor, heating medium, returnBT3
Circulation pump, heating medium, lower shuntGP20
Shunt valveQN25
Active cooling module ACS 310EQ1
Unit box with accessory cardAA25
Temperature sensor, cooling, supply lineBT64
Single jacket accumulator tank, coolingCP10
Charge pumpGP12
Circulation pump, coolingGP13
Three way valve cooling/heatingQN12
Hot water circulation
Temperature sensor, hot water circulation returnBT82
Water heaterEB2
Circulation pump, hot waterGP11
Trim valveRN1
Non-return valveRM1
Miscel-
laneous
EMK 300BF1
External electrical additional heatEB1
1) Energy meter (BF1) is included in VVM 320 R, VVM 320 3x230V
R and VVM 320 E EM. Available as accessory EMK 300 for other
markets.
15Chapter 4 | Pipe connectionsNIBE™ VVM 320

Outline diagram
-GP9 -BT51 -HQ4
-EP5
-AA25
-CL11
-CL11
-QN19
-CL11
-GP12
POOL
-BT3
-BT2
-EP21
-GP20
-QN25
-AA25
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-EB15
NIBE™ VVM 320Chapter 4 | Pipe connections16

Connecting to heat pump
All outdoor pipes must be thermally insulated with at
least 20 mm thick pipe insulation.
VVM 320 is not equipped with shut off valves; these
must be installed outside the indoor module to facilit-
ate any future servicing.
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-EB15
Connection during use without heat pump
Connect the pipe for docking in from the heat pump
(XL8) with the pipe out to the heat pump XL9.
-XL8 -XL9
-EB15
Connecting cold and hot water
The mixer valve must be installed if the factory setting
is changed so that the temperature can exceed 60 °C.
If the factory setting is changed, national regulations
must be observed. The setting is made in menu 5.1.1 (
See page 48).
-EB15
Connecting the climate system
When connecting to a system with thermostats on all
radiators/underfloor heating coils, a relief valve must
be fitted, or a thermostat must be removed to ensure
sufficient flow.
-EB15
Two or more climate systems
When more than one climate system is to be heated,
the following connection can be used.
The ECS 40/ECS 41. accessory is required for this con-
nection.
-BT3
-BT2
-EP21
-GP20
-QN25
-AA25
-EB15
17Chapter 4 | Pipe connectionsNIBE™ VVM 320

Connection of external heat source
For connection to a gas/electric/oil boiler, the AXC40
accessory is required, see "Accessories" on page 61.
-EB15
-QN11
-EM1 -BT52
-CM1
-KA1
-EM1
-FL2
-EB15 -BT25
-AA25
-XL1
-XL2
Connection of extra electrical addition
For connection of extra electrical addition, in one step,
in event of a stoppage because of cold outdoor air. The
electrical addition should not be greater than the heat
pump's power, just before being stationary.
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-EB15
-EB1
-XL8
-XL9
Connecting EMK 300
Installing energy measurement kit EMK 300 (BF1) to
VVM 320.
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-EB15
-BF1
-XL8
-XL9
Connecting hot water circulation
To reduce the risk of bacterial growth in systems with
hot water circulation, the temperature of the circulating
water should not fall below 50 °C. There should not be
any non-circulatory hot water pipes. Adjust the hot
water system so that the temperature does not fall
below 50 °C at the ends of the system.
-EB15
-GP11-BT82 -RM1
-RN1
NIBE™ VVM 320Chapter 4 | Pipe connections18

Connecting ACS 310
For connection of active cooling, ACS 310, see "Accessor-
ies" on page 61.
-CP10
-QN12
-AA25
-EQ1
-GP13
-GP12
-BT64
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-EB15
Connecting pool
Charging of the pool is controlled by the pool sensor. In the case of low pool temperatures, the reversing valve reverses
direction and opens towards the pool exchanger. The POOL 310 accessory is required for this connection.
-GP9 -BT51 -HQ4
-EP5
-AA25
-CL11
-CL11
-QN19
-CL11
-GP12
POOL
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-XL8
-XL9
-EB15
19Chapter 4 | Pipe connectionsNIBE™ VVM 320

Connecting F135
The demand on F135 is controlled by the indoor module in the system. The pump and fan speed are also controlled
from the menu in the indoor module.
-EB101
-FL10
-QM41
-QM40
-HQ1
-EB101
-XL1
-XL2
-XL8
-XL9
-AZ10
-AZ10
-RM1
-HQ1 -GP10
-QM42 -QM43
-EB15
NIBE™ VVM 320Chapter 4 | Pipe connections20
Other manuals for VVM 320
6
This manual suits for next models
1