
16
4) When the UPS is overload, please remove some loads immediately.
It is recommended to have the total loads connected to the UPS less than
80% of its nominal power capacity to prevent overload for system safety.
5) If the overload me is over acceptable me listed in spec in AC
mode, the UPS will automacally transfer to Bypass mode. Aer the
overload is resolved, it will return back to AC mode. If the overload me
is over acceptable me listed in spec in Baery mode, the UPS will enter
fault status. At this me, if bypass is enabled, the UPS will power to the
load via bypass. If bypass funcon is disabled or the input power is not
within bypass acceptable range, it will cut o output enrely.
4. Charge the baeries
1) Aer the UPS is connected to the mains and turned on in AC
mode, the charger will charge the baeries automacally except in baery
mode, during baery self-test, overload or when baery voltage is high.
2) It’s recommended to charge baeries for at least 10 hours before
operaon. Otherwise, the backup me may be shorter than expectaon.
5. Baery mode operaon
1) When the UPS is in Baery mode, the buzzer will sound according
to dierent baery capacity. If the baery capacity is more than 25%,
the buzzer will beep once every 4 seconds. If the baery voltage drops
to the alarm level, the buzzer will beep once every sec to remind users
that the baery is at low level and the UPS will shut down immediately.
Users could switch o some non-crical loads to disable the shutdown
alarm and prolong the backup me. If there is no more load to be switched
o, you have to prepare shutdown procedure to protect working data or
devices. Otherwise, there is a risk of data loss or load failure.
2) In Baery mode, users can press the Mute buon to disable the
buzzer.
3) The backup me of the long-run model depends on the external
baery capacity.
4) The backup me may vary from dierent operang temperature
and load type.
5) When seng backup me for 16.5 hours (default value from LCD