Roger MCT86M-IO-CH-HR User manual

1/2
Roger Access Control System
MCT86M-IO-CH-HR Installation Manual
Firmware version: 1.1.30.266 and newer
Document version: Rev. B
This document contains minimum information that is necessary for initial setup
and installation of the device. The detailed description of configuration
parameters and functionalities is specified in respective Operating Manual
available at www.roger.pl.
INTRODUCTION
The reader is designed for operation with MC16 access controller (RACS 5
system) mainly as hotel automation device. Factory new reader is configured
with default settings including ID=100 address.
DEVICE CONFIGURATION
The reader can be configured in regard of various parameters (including
address) in order to adapt it to the requirements of specific installation. Device
can be configured from VISO v2 management software or RogerVDM utility
software.
Note: Remote configuration of device from VISO v2 software is possible only if
jumper is placed on MEM contacts (fig. 4). If the jumper is removed then such
configuration is blocked. In case of factory new device, jumper is placed on MEM
contacts.
CONFIGURATION WITH VISO V2PROGRAM
In RACS 5 v2 system the reader can be installed at site without previous
configuration. According to AN006 application note, its address and other
settings can be configured from VISO v2 management software and during such
configuration the access to its service contacts (fig. 4) is not required.
CONFIGURATION WITH ROGERVDM PROGRAM
Fig. 1 Connection of MCT device to RUD-1 interface (configuration)
Programming procedure:
1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to
computer’s USB port.
2. Remove jumper from MEM contacts (fig. 4) if it is placed there.
3. Restart the device (switch power supply off and on or short RST contacts for
a moment) and orange LED SYSTEM will pulsate. Then within 5 seconds
place jumper on MEM contacts.
4. Start RogerVDM program, select MCT device, firmware version, RS485
communication channel and serial port with RUD-1 interface.
5. Click Connect, the program will establish connection and will automatically
display Configuration tab.
6. Enter unoccupied RS485 address in range of 100-115 and other settings
according to requirements of specific installation.
7. Click Send to Device to update the configuration of device.
8. Optionally make a backup by clicking Send to File… and saving settings to
file on disk.
9. Disconnect from RUD-1 interface and leave jumper on MEM contacts to
enable further configuration of device from VISO v2 software or remove
jumper from MEM contacts to block such remote configuration.
Note: Do not read any cards when reader is configured with RogerVDM.
MANUAL ADDRESSING
Manual addressing procedure enables configuration of new RS485 address with
all other settings unchanged.
Manual addressing procedure:
1. Remove all connections from A and B lines.
2. Remove jumper from MEM contacts (fig. 4) if it is placed there.
3. Restart the device (switch power supply off and on or short RST contacts for
a moment) and orange LED SYSTEM will pulsate. Then within 5 seconds
place jumper on MEM contacts.
4. Enter 3 digits of RS485 address in range of 100-115 with any MIFARE card.
5. Leave jumper on MEM contacts to enable further configuration of device from
VISO v2 software or remove jumper from MEM contacts to block such remote
configuration.
6. Restart the device.
Terminals without keypad can be addressed with multiple card readings where
the N number of readings emulates digit of the address. Three series of readings
with any MIFARE proximity card are necessary to set the address. After each
series wait for two beeps and proceed with the next digit. Zero digit is emulated
with 10 readings.
Example:
Programming of ID=101 address with card readings:
1. Read card 1 time and wait for two beeps.
2. Read card 10 times and wait for two beeps.
3. Read card 1 time and wait for two beeps.
4. Wait till reader is restarted with the new address.
MEMORY RESET
Memory reset procedure resets all settings to factory default ones including
ID=100 address.
Memory reset procedure:
1. Remove all connections from A and B lines.
2. Remove jumper from MEM contacts (fig. 4) if it is placed there.
3. Restart the device (switch power supply off and on or short RST contacts for
a moment) and orange LED SYSTEM will pulsate. Then within 5 seconds
place jumper on MEM contacts.
4. Read any MIFARE card 11 times.
5. Wait till device confirms reset with long acoustic signal.
6. Leave jumper on MEM contacts to enable further configuration of device from
VISO v2 software or remove jumper from MEM contacts to block such remote
configuration.
7. Restart the device.
FIRMWARE UPDATE
The firmware of device can be changed to newer or older version. The update
requires connection to computer with RUD-1 interface (fig. 2) and starting
RogerVDM software. The latest firmware file is available at www.roger.pl.
Firmware update procedure:
1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to
computer’s USB port.
2. Place jumper on FDM contacts (fig. 4).
3. Restart the device (switch power supply off and on or short RST contacts for
a moment).
4. Start RogerVDM program and in the top menu select Tools and then Update
firmware.
5. In the opened window select device type, serial port with RUD-1 interface,
path to main firmware file (*.hex) and additional firmware file (*.cyacd).
6. Click Update to start firmware upload with progress bar in the bottom.
7. When the update is finished, remove jumper from FDM contacts and restart
the device.
Fig. 2 Connection of MCT device to RUD-1 interface (firmware update)
2/2
APPENDIX
Fig. 3 Enclosure opening
Fig. 4 Service contacts
Table 1. Screw terminals
Name
Description
12V
Supply plus
GND
Ground
A
RS485 bus, line A
B
RS485 bus, line B
IN1
IN1 input line
IN2
IN2 input line
IN3
IN3 input line
IO1
IO1 output line
IO2
IO2 output line
NC
REL1 relay output (NC)
COM
REL1 relay common terminal
NO
REL1 relay output (NO)
Table 2. Specification
Supply voltage
Nominal 12VDC, min./max. range 10-15VDC
Current consumption
(average)
~60 mA
Inputs
Three parametric inputs (IN1..IN3) internally
connected to the power supply plus through a
5.6kΩ resistor. Approx. 3.5V triggering level for
NO and NC inputs.
Relay output
Relay output (REL1) with single NO/NC contact,
30V/1.5A DC/AC max. load
Transistor outputs
Two (IO1, IO2) open collector outputs, 15VDC/1A
max. load
Tamper protection
Enclosure opening reported to access controller
Proximity cards
13.56MHz MIFARE Ultralight, Classic, DESFire
EV1 and Plus
Reading range
Up to 7 cm for MIFARE Ultralight, Classic
Up to 4 cm for MIFARE DESFire EV1, Plus
Distance
1200m maximal cable length for RS485 bus
between controller and terminal
IP Code
IP41
Environmental class
(according to EN 50133-1)
Class II, indoor general conditions, temperature: -
10°C to +50°C, relative humidity: 10 to 95% (no
condensation)
Dimensions H x W x D
155 x 85 x 22 mm
Weight
~180g
Certificates
CE
Fig. 5 Connection of terminals and expanders to MC16 access controller
Fig. 6 Typical control of 230VAC supply by terminal with card holder
This symbol placed on a product or packaging indicates that the
product should not be disposed of with other wastes as this may
have a negative impact on the environment and health. The user is
obliged to deliver equipment to the designated collection points of
electric and electronic waste. For detailed information on recycling,
contact your local authorities, waste disposal company or point of
purchase. Separate collection and recycling of this type of waste
contributes to the protection of the natural resources and is safe to
health and the environment. Weight of the equipment is specified in
the document.
Contact:
Roger Sp. z o. o. sp. k.
82-400 Sztum
Gościszewo 59
Tel.: +48 55 272 0132
Fax: +48 55 272 0133
Tech. support: +48 55 267 0126
E-mail: support@roger.pl
Web: www.roger.pl

Other Roger Control System manuals

Roger PR611 User manual

Roger

Roger PR611 User manual

Roger OSR88M-IO User manual

Roger

Roger OSR88M-IO User manual

Roger ASCD-1 User manual

Roger

Roger ASCD-1 User manual

Roger RUD-3-DES User manual

Roger

Roger RUD-3-DES User manual

Roger PSD4D User manual

Roger

Roger PSD4D User manual

Roger MCT80M-BLE User manual

Roger

Roger MCT80M-BLE User manual

Roger PRT22 User manual

Roger

Roger PRT22 User manual

Roger MCX2-BRD User manual

Roger

Roger MCX2-BRD User manual

Roger H85/TDR Product manual

Roger

Roger H85/TDR Product manual

Roger MCT88M-IO User manual

Roger

Roger MCT88M-IO User manual

Roger MCX402-BRD User manual

Roger

Roger MCX402-BRD User manual

Roger B71/BCHP HW02 Product manual

Roger

Roger B71/BCHP HW02 Product manual

Roger B73/LTM Product manual

Roger

Roger B73/LTM Product manual

Roger RKD32 User manual

Roger

Roger RKD32 User manual

Roger MCI-5 User manual

Roger

Roger MCI-5 User manual

Roger MC16-RAW-KIT User manual

Roger

Roger MC16-RAW-KIT User manual

Roger PRT32 Installation guide

Roger

Roger PRT32 Installation guide

Roger PRT12MF-DES User manual

Roger

Roger PRT12MF-DES User manual

Roger MCT68ME-IO User manual

Roger

Roger MCT68ME-IO User manual

Roger MCT12E User manual

Roger

Roger MCT12E User manual

Roger CPR32-SE v2.0 User manual

Roger

Roger CPR32-SE v2.0 User manual

Roger MCX16-UZ User manual

Roger

Roger MCX16-UZ User manual

Roger MCT82M-IO-HR User manual

Roger

Roger MCT82M-IO-HR User manual

Roger H70/104AC Product manual

Roger

Roger H70/104AC Product manual

Popular Control System manuals by other brands

Allen-Bradley 1756-EN2T installation instructions

Allen-Bradley

Allen-Bradley 1756-EN2T installation instructions

IPAS DALI Series Operating and mounting instructions

IPAS

IPAS DALI Series Operating and mounting instructions

Balboa Deluxe Digital Control owner's manual

Balboa

Balboa Deluxe Digital Control owner's manual

Kichler Lighting 3R200, 3R400, 3W500 instruction manual

Kichler Lighting

Kichler Lighting 3R200, 3R400, 3W500 instruction manual

TELECO AUTOMATION TVRDS868B01 Installer instruction manual

TELECO AUTOMATION

TELECO AUTOMATION TVRDS868B01 Installer instruction manual

Siemens Desigo TRA Mounting and installation manual

Siemens

Siemens Desigo TRA Mounting and installation manual

ETC Expression Show Control System manual

ETC

ETC Expression Show Control System manual

CAME GARD series STANDARD INSTALLATION

CAME

CAME GARD series STANDARD INSTALLATION

Genius SPIN 3 installation guide

Genius

Genius SPIN 3 installation guide

btsr SMART 200 TTS operating manual

btsr

btsr SMART 200 TTS operating manual

Blue Elephant ELE6090 manual

Blue Elephant

Blue Elephant ELE6090 manual

Siemens SIMATIC S5 CPU Direct Driver manual

Siemens

Siemens SIMATIC S5 CPU Direct Driver manual

Motion Concepts M270 Technical & service manual

Motion Concepts

Motion Concepts M270 Technical & service manual

HUUM UKU manual

HUUM

HUUM UKU manual

Triangle MicroSystems PETROSMART EZ installation instructions

Triangle MicroSystems

Triangle MicroSystems PETROSMART EZ installation instructions

ETC IRIDEON Installation and user manual

ETC

ETC IRIDEON Installation and user manual

Hayward CAT 4000 owner's manual

Hayward

Hayward CAT 4000 owner's manual

DoorKing 80 Series Installation & owner's manual

DoorKing

DoorKing 80 Series Installation & owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.