Introduction
1-3
7SS60 Manual
E50417-G1176-C132-A2
Functional
components The 7SS60 digital busbar protection has two separate functional parts. One part is the
7SS601 measuring system. The measuring system detects and processes the mea-
sured values. It evaluates the restraint current IRand the differential current Idand
makes a tripping decision where required. The other part of the system, which will be
referred to as peripheral system, has the task of summating the feeder currents and
feeding the current sum into the measured value detection system. The current sum-
mation takes into account the switchgear status of the station.
If selective protection is desired for each phase, each phase is allocated its own mea-
suring system. Otherwise, the three phase currents are combined in a summation cur-
rent transformer, and the result processed. In that case only one measuring system is
required.
If a busbar is divided into two sections by a sectionalizing isolator or a bus coupler,
each section must have its own measuring system. Accordingly, six measuring sys-
tems are required for the phase-selective protection.
7SS601
measuring system The 7SS601 measuring system can detect one alternating current Idand one pulsat-
ing direct currentIR. The measuring inputs are galvanically isolated from the electronic
equipment by a current transformer or an optocoupler.
3 binary inputs are provided for the detection of external binary signals.
The system has 2 command relays with supervision. Command relay 1 consists of 2
relays connected in parallel. This relay cannot be marshalled; the function %37ULS
()1R) is permanently allocated to it. Command relay 2 is available for having
command functions marshalled to it. All command relays have a NO contact.
It has also 3 signal relays with changeover contacts, one of which is used for output
of the device blocked annunciation. The relay functionality (NC or NO)can be selected
by a jumper setting. The module is equipped with a serial RS485 interface. The con-
verter for the auxiliary power supply is integrated in the module.
Peripheral system Depending on the type and size of the systems that are to be protected by the 7SS60
busbar protection,differenttypesand numbers ofperipheralmodules areneeded.The
peripheral modules are installed in a 7XP204 housing; the number of housings re-
quired is determined by the number of modules used. Each 7XP204 housing can hold
up to 4 peripheral modules.
The following modules are available for the different functions:
•Restraint/command output module 7TM700
•Preferential treatment/isolator replica module 7TR710
•Command output module 7TS720
Restraint/command
output module
7TM700
This module comprises 5 units for the formation of restraint currents. It has also 5 in-
dependent TRIP command relays with 2 NO contacts each for multiplication of TRIP
commands generated by the 7SS601 measuring system.
The secondary current from the main current transformer of a feeder is normalized to
100 mA by a matching or summation current transformer and fed into the Idsumma-
tion path of the associated measuring system. The summation current Idis thus equiv-
alent to the vectorial addition of all feeder currents. Beside Id, the measuring system
requires a restraint value, which is formed by adding up the magnitudes of all currents.
The restraint units are used to form the current magnitudes. They rectify the feeder
currents and add them up in the IRsummation path.