
19
ENGLISH
• All operators or refrigeration circuit maintenance personnel should obtain
a valid certificate issued by an industry-approved assessment agency to
determine their qualification for safe disposal of refrigerants as required
by the industry-approved assessment specification.
• Remember the environment when disposing of packaging around the ap-
pliance and when the appliance has reached its by date.
• A warning that the appliance shall be stored in a well-ventilated area
where the size corresponds to the room area as specified for operation.
• The appliance shall be stored to prevent mechanical damage from occur-
ring.
• Information for spaces where refrigerant pipes are allowed, including
statements
• that the installation of pipework shall be kept to a minimum.
• that pipework shall be protected from physical damage and, in the case
of flammable refrigerants, shall not be installed in an unventilated space.
• that compliance with national gas regulations shall be observed.
• that mechanical connections shall be accessible for maintenance pur-
poses.
• that, for appliances containing flammable refrigerants, the minimum floor
area of the room shall be mentioned in the form of a table or a single
figure without reference to a formula.
• A warning to keep any required ventilation openings clear of obstruction.
• A notice that servicing shall be performed only as recommended by the
manufacturer.
• A warning that ducts connected to an appliance shall not contain a poten-
tial ignition source.
• When the portable air conditioner or dehumidifier is turned on, the fan can
work continuously stable under normal conditions to provide the minimum
air volume of 100m3/h even when the compressor is closed due to the
temperature controller.
• Do not pierce or burn.
• Use only implements recommended by the manufacturer for defrosting or
cleaning.
• Do not perforate any of the components in the refrigerant circuit. Refriger-
ant gas may be odorless.
• Use care when storing the appliance to prevent mechanical faults.