SKF CMPT DCL User manual

SKF alarm and display module CMPT DCL
Copyright © 2014 by SKF Group
All rights reserved.
Aurorum 30, 977 75 Luleå
Sweden
Telephone: +46 (0) 31 337 10 00, Fax: +46 (0) 920 134 40
Part No. 32163200
Revision D
Instruction Manual

SKF Reliability Systems
SKF Condition Monitoring Center
Aurorum 30
977 75 Luleå
Sweden
Telephone: +46 (0) 31 337 10 00
FAX: +46 (0) 920 134 40
For technical support, contact:
for customers in Europe, Middle East and Africa.
Telephone: +46 (0) 31 337 65 00
or
for customers in North America, South America and Asia.
Telephone: +1 800 523 7514
Telephone in Latin America: +55 11 4448 8620
Visit us at our web site
www.skf.com/cm
® SKF is a registered trademark of the SKF Group

SKF alarm and display module CMPT DCL TOC-3
Instruction Manual, Revision D
Table of Contents
Description 1 - 4
Features 2 - 6
Specifications 3 - 7
Dimensions/Front panel 4 - 8
Caution 5 - 9
Wiring Connections 6 - 10
Configuration 7 - 11
Configuration for CMPT CTU Vibration and
Temperature Transmitter 8 - 13
....................................................................................................8 - 13
Vibration/Temperature and Alarm High
....................................................................................................8 - 16
Alarm Limit Setting and Alarm Options
....................................................................................................8 - 17
Completed Configuration and Connection to CMPT CTU
....................................................................................................8 - 17
Default Configuration when DCL is part of an SKF enclosure
....................................................................................................8 - 17
Connections with Relay Contacts
Optional Configurations 9 - 18
....................................................................................................9 - 18
Lock
....................................................................................................9 - 18
Display and Output Dampening
Appendix 10 - 19

Description
SKF alarm and display module CMPT DCL
1-4
Instruction Manual, Revision D
Description
1
Figure 1-1: CMPT DCL display and alarm module
This Instruction Manual provides detailed wiring connection and configuration
information for the CMPT DCL display and alarm module.
The CMPT DCL is configured by SKF when it is part of an assembled CMPT enclosure.
The CMPT DCL must otherwise be properly installed and configured by the user.
Important: Please read this Instruction Manual and the cautionary notes thoroughly.
·The SKF CMPT DCL is a digital alarm and display module. It is part of a machinery
fault detection system to monitor analog signals from the SKF CMPT CTU vibration
and temperature transmitter, various thermocouples and Resistive Temperature
Detectors (RTDs).
·The DCL is a single channel module with digital display and alarm function with LED
event lamp and relay contacts.
·The front panel digital display provides the user a visual indication of the monitored
signal. The display can be scaled to indicate vibration (gE, g, mm/s, inch/s),
temperature (°C, °F), etc. The DCL has programmable alarm, relay and variable
time delay functions. The DCL can indicate HIGH, LOW, HIGH-LOW, and various
other alarm limits. The front panel event lamp illuminates (red) to indicate alarm.
·The relay contacts are programmable with various options (Normally
Open/Normally Close, Non-latching/latching).
·The DCL provides a 4 to 20 mA output signal proportional to the scaled analog
input signal.

SKF alarm and display module CMPT DCL 1-5
Description
Instruction Manual, Revision D
·Two CMPT DCL modules are needed for stand-alone monitoring of an SKF CMPT
CTU vibration transmitter (one each for vibration and temperature). One CMPT
CTU and two DCL modules together are a user-friendly fault detection system of
machinery vibration and temperature.
·The CMPT CTU transmitter can also be connected directly to a PLC/DCS
automation system without the DCL modules.

Features
SKF alarm and display module CMPT DCL
2-6
Instruction Manual, Revision D
Features
2
·Monitors various inputs
Current (mA)
DC voltage (i.e. vibration or temperature signals from CMPT CTU)
Thermocouple
Resistive Temperature Detector (RTD)
·Digital LED display of monitored signals
·Programmable alarm function (one channel)
Alarm on HIGH, LOW or HIGH-LOW signal input, etc.
Front panel LED event lamp
Relay contacts
üNormally Open or Normally Closed
üLatching or non-latching
Time delay (0 to 9 999 seconds)
·Analog output signal (4 to 20 mA)
·Front panel user configurable
Input type
Display scaling
Alarm function
Analog output scaling
·No need for voltmeter and screw driver to set alarm function
·35 mm DIN rail mounted

SKF alarm and display module CMPT DCL 3-7
Specifications
Instruction Manual, Revision D
Specifications
3
Power requirements
Supply voltage: 24 V AC/DC (20 to 28 V AC/DC)
Supply current: 200 mA, maximum
Power: 6 W, maximum
Sensor input
Current*: 4 to 20 mA, 0 to 20 mA (Input impedance: 50 W)
Voltage: 0 to 10 V DC (Input impedance: 100 KW or greater)
0 to 1 V DC, O to 5 V DC, 1 to 5 V DC
Thermocouple: K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26).
External resistance 100 W or less
RTD: Pt100, JPt100 three wire system.
Allowable input wire resistance 10 W or less per wire
*50 W shunt resistor (0.1% precision) required at input terminals (not included)
Alarm function
LED event lamp on front display (red)
Relay contact: 48 V DC or AC / 1,0 Amp, maximum
Programmable
üAlarm setting value
üOptional alarm on HIGH limit, LOW limit, HIGH-LOW limit, HIGH-LOW range limit
üOptional Normally Open or Normally Closed relay contacts
üOptional Non-latching or latching relay contacts
üVariable time delay (0 to 9 999 seconds)
Output
Analog output signal (4 to 20 mA) proportional to scaled input
Digital display
Four H/7,4 mm x W/4 mm high-red LEDs,
Scaleable for vibration (gE, g , mm/s, inch/s), temperature (°C, °F)
Operating environment
Operating temperature: -10 °C to 50 °C (14 °F to 122 °F)
Storage temperature: -25 °C to 65 °C (-13 °F to 149 F°)
Humidity: 85 % maximum
IP rating: 30
Mechanical
Weight: 0,12 kg (0.27 lbs)
Enclosure: Polyethylene and PET resin
Color: Gray with green terminals
Connectors: One 4–pole screw clamp type/
0ne 5-pole screw clamp type (10 total)
Wiring: Power and analog output 0,2 mm to 1,5 mm
diameter (0.008 inch to 0.06 inch)
Input and relay out 0,2 mm to 0,5 mm diameter
(0.008 inch to 0.03 inch)
Mounting: 35 mm DIN-rail type EN50022
Dimensions (W x H x D): 22,5 x 75 x 100 mm (0.89 x 2.95 x 3.94 inches)
Approval
CE

Dimensions/Front panel
SKF alarm and display module CMPT DCL
4-8
Instruction Manual, Revision D
Dimensions/Front panel
4
Figure 4-2: Dimensions
1 OUT indicator:
A green LED lights up when OUT (control outputs)
is ON.
For DC current output type, it flashes in a 0,25
second cycle corresponding to the output
manipulated variable.
2 EVENT indicator (alarm)
5 The upper row of digital characters displays the
Present Value (PV)
6 The lower row of digital characteristics displays the
Setting Value (SV)
7 Increase Key ( )increases the numeric value
8 Decrease Key ( )decreases the numeric value
9 Mode key ( )changes the setting mode or
registers the setting value. [Registers the setting
value by pressing the Mode Key]
10 Sub-mode Key
(beneath the SKF logo)
brings up Auxiliary Function Setting Mode 2 in
combination with the Mode Key.
Figure 4-3: Front panel
The CMPT DCL has two rows of digital characters:
·the upper row displays the Present Value (PV). The PV is the value received from
the input device (CMPT DCL, either vibration or temperature). The upper row of
digital characters will display the Present Value (PV) from the CMPT DCL
transmitter when in the normal operating (default) state.
·the lower row displays the Setting Value (SV). The SV is an input set by the user
during configuration if the DCL is to use the HIGH-LOW or Range alarm settings.
Otherwise the SV is not used.

SKF alarm and display module CMPT DCL 5-9
Caution
Instruction Manual, Revision D
Caution
5
Read and understand these instructions thoroughly before working with the CMPT DCL.
The CMPT DCL shall be used by persons qualified to work with electrical
instrumentation.
Caution - Damage or injury can result
•The CMPT DCL is powered by 24 V DC. Do not apply higher voltage.
•Do not connect the sensor input (DC voltage) to the CMPT DCL (terminals 5, 6
and 7) until after the unit is powered and the input type is configured. See sections
"Configuration" and "Configuration for CMPT CTU vibration and temperature
transmitter".
•The CMPT DCL relay contacts are rated 48 VAC/DC, 1 Wmaximum. Do not apply
higher voltage / current.
•Higher voltage (110–240 V AC) power may exist in the same proximity as the
CMPT DCL. Use caution to avoid contact with any voltage source.
•Make sure that the power is disconnected prior to working with electrical wiring.
•Make sure that the CMPT DCL is installed in an environment within its
specifications (see section "Specifications")
Lightning strikes, power surges and other electrical anomalies can damage this device.
For the protection of your equipment, SKF recommends the power connections be
made through a surge protector.

Wiring Connections
SKF alarm and display module CMPT DCL
6-10
Instruction Manual, Revision D
Wiring Connections
6
The electrical connections and terminals of the CMPT DCL are listed below. The same
figure is also applied to the side of each module. It is recommended to use 1,5 mm
(AWG 18 gauge) wire with the DCL.
CMPT DCL
DCL terminal
+24 V DC
1
0 V DC
2
+4 to 20 mA OUT
3
4 to 20 mA COMMON
4
INPUT HIGH (+)
5
INPUT COMMON (-)
6
RTD INPUT
7
RELAY OUTPUT (contact)
8
RELAY OUTPUT (contact)
9
Figure 6-4: Wiring connections and terminals
Connecting the CMPT DCL with the CMPT CTU – vibration or temperature input (0
to 10 V DC)
Two CMPT DCL modules are needed to monitor both vibration and temperature from
the CMPT CTU transmitter. Optionally, one CMPT DCL can monitor either vibration or
temperature from the CMPT CTU. The following connections are made to connect the
DCL with the CTU.
CMPT CTU terminal to CMPT DCL terminal
Vibration
0 –10 V VIB OUT 16 5
VIB COMMON OUT 15 6
Temperature
0–10 V TEMP OUT 13 5
TEMP COMMON OUT 12 6

SKF alarm and display module CMPT DCL 7-11
Configuration
Instruction Manual, Revision D
Configuration
7
The CMPT DCL is configured by SKF when supplied assembled as part of an SKF CMPT
enclosure. See Section “Default configuration when DCL is part of an SKF enclosure” for
the default settings.
The DCL must be configured by the user if supplied as a separate component (i.e. part
of a CMPT 1CM type kit).
The DCL is configured by pressing the keys on the front panel. There are four “setting
modes”to set the configuration.
The four Setting Modes have the following functions:
·Main Setting Mode (Press the Key (Key 9) to enter this mode) – Sets the
desired value for the Setting Value (SV). The setting value is used as part of the
alarm level setting if a High-Low or Range type monitoring is desired.
·Sub-Setting Mode (Press the Key while holding the Key) –Sets the Alarm
setting and other optional features.
·Auxiliary Function Setting Mode 1 (Press the Key while holding the Key) –
Locks the settings of the DCL.
·Auxiliary Function Setting Mode 2 (Press the Key while holding the
Key
beneath the SKF logo) – Sets the input type voltage), digital display scaling, alarm
mode, relay features, and alarm delay, and converter function.
The following figure is a schematic diagram of the four setting modes.
Figure 6-5: CTU configuration diagram
Note: The basic configuration of the DCL is made in Auxiliary Function Setting Mode
2.
The user must enter one or more of the ‘Setting Modes’ to change the default settings
of the DCL or to set the initial configuration of the DCL. Upon completing the
configuration of each setting mode the DCL returns to the PV display. The configuration
is saved even when disconnected from the power source. The settings can be locked to
prevent unintentional changes in Auxiliary Function Setting Mode 1.

Configuration
SKF alarm and display module CMPT DCL
7-12
Instruction Manual, Revision D
Once entered into a Setting Mode, the user sequences through the settings using the
Mode Key (Key 9). The , Keys (Keys 7 and 8) are used to set a parameter or
value. The settings for the CMPT DCL to monitor the CMPT CTU are defined in the
section “Configuration for CMPT CTU vibration and temperature transmitter”on the
next page.
Important: Changing the configuration in Auxiliary Function Setting Mode 2 will
change the alarm level setting made in Sub-setting mode. The alarm level setting
should only be made after the configuration in Auxiliary Function Setting Mode 2.
The CMPT DCL is a multi-functional device. It can monitor various types of analog
signals (voltage, current, thermocouple, RTDs) and display and alarm in different ways.
See the Appendix for tables for each Setting Mode, meaning of each Key step, and
listing of the sensor input types.

SKF alarm and display module CMPT DCL 8-13
Configuration for CMPT CTU Vibration and Temperature Transmitter
Instruction Manual, Revision D
Configuration for CMPT CTU Vibration and
Temperature Transmitter
8
Configure the CMPT DCL for use with the CMPT CTU by entering the Auxiliary
Function Setting Mode 2.
Press and hold the Mode Key (Key 9) and the Sub-mode Key
(Keys 10 ) at the
same time for 3 seconds to enter the Auxiliary Function Setting Mode 2.
Sequence through the Auxiliary Function Setting Mode 2 by pressing the Mode
Key(Key 9). Change the setting of each parameter using the Increase Key (Key 7) or
Decrease Key (Key 8). See the steps in the section below for the correct setting of
the DCL.
Vibration/Temperature and Alarm High
Follow this procedure to set the DCL to display and monitor vibration or temperature
signals (0 to 10 V DC) from the CMPT CTU. This procedure sets the alarm function for
High vibration and activates the relay for Normally Open (NO) and Non-latching
function. See section “Alarm Limit setting and alarm options”to set the Alarm setting
value.
Caution – Damage can result. Do not connect the CMPT CTU wiring or any other DC
input voltage to the CMPT DCL terminals 5 and 6 until after the unit is configured.
Damage to the CMPT DCL or CMPT CTU can result.
Enter the Auxiliary Function Setting Mode 2 by pressing and holding the Mode Key
(Key 9) and the Sub-mode Key
(Key 10) at the same time for 3 seconds.
Sequence through Step 1 to 15 by pressing the Mode Key (Key 9).
Set the value / parameter in each setting using the , Keys (Keys 7 or 8).
Change the parameters below to configure the DCL to monitor vibration or temperature
level.
1. Input type selection
(0 to 10 V DC input)
2. Scaling high limit setting vibration
Vibration
The DCL can be configured to indicate the actual vibration level (gE, g, mm/s or
inch/s) based on the Range setting of the CMPT CTU or the percentage of full CTU
scale (100 %).
If the DCL is set for the percentage of full scale, the CMPT CTU Range can be
changed without the need to re-configure the DCL. The default setting (0 to
100 % full scale) is recommended when the value of the vibration is low (i.e. Range 0
or 2). Use the tables below to set the DCL to indicate actual vibration
value.
For percentage of full scale, set the Scaling high limit setting = 9999*.
See Note below.

Configuration for CMPT CTU Vibration and Temperature Transmitter
Vibration/Temperature and Alarm High
SKF alarm and display module CMPT DCL
8-14
Instruction Manual, Revision D
Scale high limit settings @100 mV/g accelerometer (sensor) sensitivity
Accel Env
(gE3)
Accel (g)
Vel (mm/s)
Vel (inch/s)
Range 0
30
30
Use default setting
Range 1
100
100
50
Use default
setting
Range 2
300
300
150
Use default
setting
Range 4
1000
1000
500
28
Scale high limit settings @230 mV/g accelerometer (sensor) sensitivity
Accel Env
(gE3)
Accel (g)
Vel (mm/s)
Vel (inch/s)
Range 0
13
13
Use default setting
Range 1
44
44
22
Use default
setting
Range 2
130
130
65
33
Range 4
435
435
217
111
Temperature 1200 for °Celsius* or 2480 for °Fahrenheit
*default setting
Note: If the DCL was previously set for the decimal point at one place (via Manual
reset setting), the above values for Scale high limit setting must be divided by 10.
3. Scaling low limit setting
Vibration *
Temperature for °Celsius* or for °Fahrenheit
Note: Setting the Scaling low limit setting = 320 also sets the Setting Value (SV in
Main Setting Mode) to 320 ( or 32.0 after the decimal point is set). The Alarm Level
( ) in Sub setting mode must be adjusted. See Alarm Limit Setting and Alarm
Options section.
4. Decimal point place setting
Three digits after decimal point
5. PV filter time constant setting
No change (Not applicable)
6. Out high limit setting
No Change (Change only if other than 20 mA high is desired)
7. Out Low limit setting
No change (Change only if other than 0 mA low is desired)

SKF alarm and display module CMPT DCL 8-15
Configuration for CMPT CTU Vibration and Temperature Transmitter
Vibration/Temperature and Alarm High
Instruction Manual, Revision D
8. Alarm action selection
High limit alarm
9. Alarm action Normally Closed / Normal Open
Normally Closed (NC) – (Energized)
Normally Open (NO) – (Deenergized)
10. Alarm HOLD function selection
Non-latching
Latching (Hold)
Note: When the Alarm HOLD function selection is set to HOLD (latching), the 24 V
DC supply to the DCL must be interrupted to reset the relay. A manual reset button
(by others) can be used for this purpose.
11. Alarm hysteresis setting
1.0 No change (Not applicable)
12. Alarm action delayed timer setting
0Optional no change (set at desired value)
13. Direct/Reverse selection
No Change (Not applicable)
14. Output status selection when input is abnormal
No Change (Not applicable)
15. Controller/Converter function selection
Converter function
The configuration in Auxiliary Function Setting Mode 2 is complete. See Section "
Default Configuration when DCL is part of an SKF enclosure" for completion of
installation.
IMPORTANT NOTE : CHANGING THE CONFIGURATION IN AUXILIARY FUNCTION
MODE SETTING 2 WILL CHANGE THE ALARM LEVEL SETTING MADE IN
SUB-SETTING MODE. THE ALARM LEVEL SETTING SHOULD ONLY BE MADE AFTER
THE CONFIGURATION IN AUXILIARY FUNCTION MODE SETTING 2.

Configuration for CMPT CTU Vibration and Temperature Transmitter
Alarm Limit Setting and Alarm Options
SKF alarm and display module CMPT DCL
8-16
Instruction Manual, Revision D
Alarm Limit Setting and Alarm Options
To set the Alarm setting, place the CMPT DCL in Sub-setting Mode.
Press and hold the Increase Key (Key 7) and the Mode Key (Key 9) to enter the
Sub-setting Mode.
Sequence through the Sub-setting Mode by pressing the Mode Key (Key 9).
Change the setting of each parameter using the Increase Key (Key 7) or Decrease
Key (Key 8). See the Steps 1 through 7 below for the correct setting of the DCL.
1. OUT proportional band setting (analog out)
. No change (Not applicable)
2. Integral time setting
No change (Not applicable)
3. Derivative time setting
No change (Not applicable)
4. Manual reset setting
No change (Not applicable)
5. Alarm setting
Vibration .(60 % of full scale CMPT CTU Range)
Temperature or to the desired value °C
.or to the desired value °F
Typical alarm value is 100 °C (212 °F)
NOTE: Setting the Scaling low limit setting = 32.0 (Auxiliary function setting mode)
sets the Setting Value (SV in Main Setting Mode) to 32. The Alarm Level ( )
setting must be reduced by the SV value to alarm at the desired value.
(ie., = desired alarm value – SV)
Example Desired alarm value = 212 °F , Set = 212 – 32 = 180
6. Loop break alarm time setting
No change (Not applicable)
7. Loop break alarm span setting
No change (Not applicable)
Sub-setting mode programming is complete.
If the High-Low or High Range alarm setting modes are desires, contact SKF for
Instructions.
IMPORTANT NOTE: CHANGING THE CONFIGURATION IN AUXILIARY FUNCTION MODE
SETTING 2 WILL CHANGE THE ALARM LEVEL SETTING MADE IN SUB-SETTING
MODE. THE ALARM LEVEL SETTING SHOULD ONLY BE MADE AFTER THE
CONFIGURATION IN AUXILIARY FUNCTION MODE SETTING 2 IS COMPLETE.

SKF alarm and display module CMPT DCL 8-17
Configuration for CMPT CTU Vibration and Temperature Transmitter
Completed Configuration and Connection to CMPT CTU
Instruction Manual, Revision D
Completed Configuration and Connection to CMPT CTU
After the Auxiliary Function Mode 2 configuration is complete, it is permissible to
connect the output from the CMPT CTU to the DCL according to Section 4. The OUT
lamp on the front panel should be flashing Green. The PV should indicate the value of
vibration or temperature from the CMPT CTU. The current (4 to 20 mA) analog output
signal (DCL terminals 3 and 4) is proportional to the full scale set for either vibration or
temperature.
Default Configuration when DCL is part of an SKF enclosure
The CMPT DCL is initially configured by SKF when included as part of an assembled
enclosure. The DCL, for vibration or temperature is configured as follows:
Vibration
Percentage of full CMPT CTU scale Range
Temperature
Celsius
0 to 120 °C
Alarm
High Level
60% of full scale for vibration / 100 °C for
temperature
Relay
Normally Open (NO)
Output scaling
Full scale
Proportional to full scale vibration or
temperature (4 to 20 mA)
Function
Converter
4 to 20 mA output
Connections with Relay Contacts
The CMPT CDCL relay contact functions can operate remote low power (< 48 V DC / 1
Amp) lamps, buzzers and relays. These can be used to indicate an Alarm event.
Connect the remote device to DCL terminals 8 and 9.

Optional Configurations
SKF alarm and display module CMPT DCL
9-18
Instruction Manual, Revision D
Optional Configurations
9
The CMPT DCL can optionally be configured to prevent changes to the configuration
and to dampen the changes in display and output source values.
NOTE: When the Alarm HOLD function selection is set to HOLD (latching), the 24 V DC
supply to the DCL must be interrupted to reset the relay.
Lock
The settings of the DCL can be locked to prevent unwanted changes. Enter Auxiliary
Function Setting Mode 1 by pressing the Key and the Enter the Auxiliary Function
Setting Mode 1 by pressing and holding the Mode Key (Key 7) and the Sub-mode
Key (Key 9) at the same time for 3 seconds. See the Appendix Table 3.
There are three Lock settings.
None of the settings can be changed
Only the main setting mode can be changed
All setting values can be changed, but values are not saved after the
power is turned off.
Display and Output Dampening
If the display values changes too rapidly for the User due to the dynamics of the input, it
is possible to dampen the display and output signal. To dampen the display and output
values enter the Auxiliary Function Setting Mode II, see section "Vibration/Temperature
and Alarm High" and Appendix Table 4. to change the display, change the PV filter time
constant setting ( ) to a value greater than 0 seconds. The maximum value is
10 seconds. Do not use too high a value or the display and output may not represent
the input signal well.

SKF alarm and display module CMPT DCL 10-19
Appendix
Instruction Manual, Revision D
Appendix
10
IMPORTANT NOTE: CHANGING THE CONFIGURATION IN AUXILIARY FUNCTION MODE
SETTING 2 WILL CHANGE THE ALARM LEVEL SETTING MADE IN SUB-SETTING
MODE. THE ALARM LEVEL SETTING SHOULD ONLY BE MADE AFTER THE
CONFIGURATION IN AUXILIARY FUNCTION MODE SETTING 2.
The CMPT DCL has many features that can be configured to enhance the monitoring
from the CMPT DCL and also for thermocouples and RTDs. This basic DCL model has
some intrinsic features that are not implemented within SKF Copperhead fault detection
(controller function, heater burnout, communication protocol, etc.). The configurations
not applicable to the CMPT DCL are marked- NOT APPLICABLE.
See the tables below for those features.
Table 1
Character
Name, Description, Setting range
Main Setting Mode
Default value
SV
0
• Sets the SV for controlled object.
• Scaling low limit value to scaling high limit value
(For DC input, the placement of the decimal point follows the selection)
Table 2
Character
Name, Description, Setting range
Sub Setting Mode
Default value
AT setting – NOT APPLICABLE
• Performs PID auto-tuning. However, when PID auto-tuning does not
finish after 4 hours, PID auto-tuning is shut down compulsory.
• PID auto-tuning cancellation:
• PID auto-tuning performance:
OUT proportional band setting
2.5%
• Sets the proportional band.
• The control action becomes ON/OFF when set to 0.0
• Setting range: 0.0 to 110.0%
Integral time setting NOT APPLICABLE
200 seconds
• Sets the integral time.
• Setting the value to 0 disables this function.
• Not available for ON/OFF action.
• Setting range: 0 to 1000 seconds
Derivative time setting NOT APPLICABLE
50 seconds
• Sets the derivative time.
• Setting the value to 0 disables this function.
• Not available for ON/OFF action.
• Setting range: 0 to 300 seconds

Appendix
SKF alarm and display module CMPT DCL
10-20
Instruction Manual, Revision D
Character
Name, Description, Setting range
Sub Setting Mode
Default value
Anti-reset windup setting NOT APPLICABLE
50%
• Sets anti-reset windup.
• Available only for PID action.
• Setting range: 0 to 100%
OUT proportional cycle setting
30 or 3 seconds
• Sets the proportional cycle value for the control output (OUT).
• Not available for ON/OFF action or DC current output.
• Setting range: 1 to 120 seconds
Manual reset setting
0.0
• Sets the reset value manually.
• Available only for P and PD action.
• Proportional band converted value
(For DC input, the placement of the decimal point follows the selection)
Alarm setting
0
• Sets the action point for the alarm output.
• Setting the value to 0 or 0.0 disables this function (excluding Process
high and Process low alarms). When Loop break alarm and Heater
burnout alarm are applied together, they
utilize output terminals.
• Not available when No alarm action is selected during Alarm action
selection.
• See (Table 5.3-1).
(For DC input, the placement of the decimal point follows the selection.)
.
Heater burnout alarm setting NOT APPLICABLE
0.0A
• Sets the heater current value for Heater burnout alarm.
• Setting the value to 0.0 disables this function.
• Self-holding is not available for the alarm output. When Alarm and
Loop break alarm are applied together, they utilize common output
terminals.
• Available only when Heater burnout alarm is added.
• Rating 5A: 0.0 to 5.0A
• Rating 10A: 0.0 to10.0A
• Rating 20A: 0.0 to 20.0A
• Rating 50A: 0.0 to 50.0A
Loop break alarm time setting NOT APPLICABLE
0 minutes
• Sets the action time to assess the Loop break alarm.
• Setting the value to 0 disables this function.
• When Alarm and Heater burnout alarm are applied together, they
utilize common output terminals.
• Setting range: 0 to 200 minutes
Loop break alarm span setting NOT APPLICABLE
0
Table of contents
Other SKF Control Unit manuals

SKF
SKF LCG2-A Series User manual

SKF
SKF BCU User manual

SKF
SKF MAXILUBE MAX 230-IF105 Series User manual

SKF
SKF Lincoln 85307 User manual

SKF
SKF SCU 1 User manual

SKF
SKF DCV5-4+924 User manual

SKF
SKF Lincoln 758 Product manual

SKF
SKF LINCOLN 85831 User manual

SKF
SKF SMBM-X Series User manual

SKF
SKF Lincoln 85307 User manual