SKF Lincoln 85307 User manual

Operating instructions
Model 85307; dual-line system
Electronic lubrication control unit
Date of issue August 2020
Form number 404772
Version 2

Contents
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operational precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Explanation of signal words for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Keypad layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LED code descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Setup mode
Dual-line system using two pressure switches and hydraulic change-over valve . . . 10
Run mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Running system (pump run). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Running system (pump pause). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Running system (vent cycles) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Stage 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Stage 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Stage 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Stage 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Stage 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Wiring of pump with two pressure switches and hydraulic change-over valve . . . . . . . 22
Wiring of pump with solenoid relay contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fault indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Setup mode
Dual-line system using 1/2cycles and hydraulic change-over valve . . . . . . . . . . . . . . 25
Run mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Running system (pump run). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Running system (pump pause). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Stage 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Stage 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Stage 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Stage 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Wiring of pump with dual-line system using 1/2cycles and hydraulic change-over valve 31
Fault indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2

Description
Lubrication controller 85307 is a universal
electronic control unit compatible with
dual-line, single-line and progressive
lubrication systems. Provides flexibility and
control over traditional single-line systems.
Controller digital display quickly identifies
system status with easy-to-identify codes.
Programming of unit requires simple
information allowing operator to focus
on specific utilized system.
Features
• Runs progressive, single-line and
dual-line lubrication systems.
• Timing intervals from 5 seconds to
24 hours.
• Cycle counting.
• 10 V to 30 V operation.
• Short circuit/open circuit detection with
audible warning.
• External fault lamp drive (flash or steady
output).
• Low level reservoir monitoring.
• Two sensor switch inputs.
• Visual and audible fault indication.
• Non-volatile memory.
• Built-in blown fuse indicator.
• 3-digit LED display indicates exact
system status.
• Simple setup procedure.
• Test mode allows testing of all circuits
connected to controller.
• Practical housing with mounting bracket.
Table 1
Specifications
Voltage 10 V to 30 V
Current drain 150 mA maximum (no load), 70 mA nominal
Pump output 7 A rms. maximum
Lamp output 3 A maximum
Switching Solid state short circuit protected
Fuse 8 A fast blow 0.79 in (20 mm) glass
Connection 14 way MOLEX MINIFIT - JR
Communications RS232 type
Dimensions 2.8 × 5.7 × 1.5 in (70 × 145 × 38 mm) 1)
Weight 0.66 lbs (300 g)
Protection IP54
Temperature range 5 °F to 122 °F (–15 °C to +50 °C)
1) Includes mounting bracket.
3

Explanation of signal
words for safety
NOTE
Emphasizes useful hints and
recommendations as well as
information to prevent property damage
and ensure efficient trouble-free
operation.
CAUTION
Indicates a dangerous situation that can
lead to light personal injury if
precautionary measures are ignored.
WARNING
Indicates a dangerous situation that
could lead to death or serious injury if
precautionary measures are ignored.
DANGER
Indicates a dangerous situation that will
lead to death or serious injury if
precautionary measures are ignored.
Safety
Read and carefully observe operating
instructions before unpacking and operating
equipment. Equipment must be operated,
maintained and repaired exclusively by
persons familiar with operating instructions.
Local safety regulations regarding
installation, operation and maintenance
must be followed.
Operate equipment only after safety
instructions and this service manual are
fully understood.
Operational
precautions
User must have total understanding of
controller specifications. Never connect any
other voltage supply other than specified in
manuals contained within.
Operator/owner must ensure installation
or inspections are executed by authorized
personnel who have thoroughly read
operating instruction manual.
Switch machine off before performing any
setup or work on controller. Position
machine so no harm can be caused to any
person should machine be switched on
during setup of controller. Operator or
personnel working on machine must be
advised in the event machine needs to be on
for setup of controller.
Never switch machine on without prior
knowledge of operator/owner or someone
with full knowledge of machines operation.
WARNING
• Never weld on machine while main
switch of machine is on. Ensure main
switch is off and correctly tagged.
Welding on machine can cause
serious damage to controller.
• Do not alter or modify any part
of controller.
• Always mount controller in
suitable area.
• Do not mount controller near an area
with excessive heat.
• Always use correct specified fuse
rating for controller.
• Never exceed voltage rating of
controller.
• Never expose controller to direct
sunlight.
• Never expose controller to water or
other substances.
4

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Fig. 1
Keypad layout
Item Description
1Enter button
2 Run/pause buttton
3 Setup indicator
4 Mounting bracket
5 LED display
6 Cycle indicator
7 Second indicator
8 Minute indicator
9 Hour indicator
10 Select value down or silent buzzer
11 Blown fuse indicator
12 Fuse holder, 8 A
13 Power positive/negative
14 Ignition input/aux power output positive
15 Sensor 1 positive/negative
16 Sensor 2 positive/negative
17 External lamp
18 Reservoir sensor connection
19 Pump motor positive/negative
20 RS 232 connection
21 Reservoir low level status indicator
22 Sensor 2 status indicator
23 Sensor 1 status indicator
24 Pump status indicator
5

sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
LED code descriptions
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
SLS = single-line system
PLS = progressive-line system
DLS = dual-line system
n – 0 = normally open (sensors)
n – C = normally closed (sensors)
6

sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
L – S = external lamp steady (continued supply)
L – F = external lamp flashing (pulsed supply)
nFE = non-fatal error (pump continues on low level fault)
r= run time in cycles
P= pause time in seconds, minutes or hours
7

sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
Fig. 12
Fig. 13
Fig. 14
Fig. 15
Fig. 16
LED code descriptions
F= fault time in seconds, minutes or hours
U= vent time in seconds, minutes or hours
rCC = run cycle counter
YES = confirms program changes
tSt = test mode for checking installed devices
8

sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
sec
min
hrs
cyc
SETUP
Fig. 17
Fig. 18
Fig. 19
Fig. 20
Fig. 21
t= time out or dwell time for sensors
FE = fatal errors (pump stops on Low Level Fault)
nO = do not select selection
r= run time in seconds, minutes or hours
.= standby mode
9

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
AB C
Setup mode
Dual-line system using two pressure switches and hydraulic change-over valve
Fig. 22
1 To enter setup mode:
Press and hold ENTER while switching on controller
power source.
2 Release ENTER and red LED next to SETUP illuminates.
Green LED next to PUMP flashes. PLS (progressive-line system)
appears in display (Fig. 22 A).
3 Press Δto select system type required:
Continue to press until dLS displays (Fig. 22 B).
4 Press ENTER to confirm use of dual-line system (Fig. 22 C).
10

S
TEP 5
A B
5 P (pause) appears in display. Press Δto change time (Fig. 23 A).
LED changes from seconds to minutes to hours. Display indicates
amount of pause time when function is applied.
6 Press ENTER to confirm pause time.
In example, pause time of 4 hours is confirmed (Fig. 23 B).
Fig. 23
11

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
A B
7 t (time out) for pressure switches displays. Adjust by pressing Δ
to required time. Large systems time out is substantially greater
than smaller systems. Time out, or dwell time, is actual time it
takes pressure switch to close contacts. When pressure switch
closes, signal is sent to controller that system is pressurized.
Should a pipe break, pressure switch remains open. This is a
safety and control feature to indicate to controller when system
can change over. Time out setting in PROXY 1 will apply by default
for that of PROXY 2 when using two pressure switches system.
8 Press Δto increase time out.
9 Press ENTER to accept (Fig. 24 A).
10 n-O (normally open) displays indicating whether pressure switch
is normally open or normally closed. n-O switches are used for
dual-line systems.
11 Press Δto choose either n-O or n-C.
12 Press ENTER to accept choice (Fig. 24 B).
Fig. 24
12

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
A B
13 nO (do not select) displays. Green LED on PROXY 2 illuminates.
Because two pressure switches system is being used, press Δto
select YES.
14 Press ENTER to accept and proceed to next part of setup
(Fig. 25 A).
15 System skips PROXY 2 setup and defaults to settings made in
PROXY 1. Number of cycles dual-line system will run before going
into pause cycle displays. Controller has unique feature of running
multiple cycles because system monitors state of pressure switch,
closed or opened, to allow next cycle to commence.
16 Press Δto select number of run (r) cycles.
17 Press ENTER to accept settings (Fig. 25 B).
Fig. 25
13

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
A B
18 nO displays. Green LED on reservoir illuminates. Option of low
level detection displays. If low level detection is not required,
push Δand select nO.
19 Press ENTER to accept.
20In this example low level option is selected. Press Δuntil YES
displays.
21 Press ENTER to accept choice (Fig. 26 A).
22 n-O displays indicating whether sensor is normally open or
normally closed. Press Δto choose between n-O or n-C.
23 Press ENTER to accept choice (Fig. 26 B).
Fig. 26
NOTE
10-second delay occurs on startup when using low level sensor
to ensure paddle assembly is in correct position.
Sensor activates on low level after 10 seconds. Low level
warning displays when unit reaches pause status.
14

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
A B
24 FE (fatal error) or nFE (nonfatal error) appears in display.
Option FE (fatal error) is used to stop pump on low level warning.
Typically used on pumps with reservoir capacities from 0.26 to
2.6 gal (1 to 10 l). It is preferred to stop pump at low level to
maintain layer of grease above pump element area thereby
not allowing air pockets to form around pump element when
filling up reservoir. Option nFE (nonfatal error) is recommended
on larger pump reservoirs with substantial distance from pump
tube to bottom of reservoir.
25 Select choice and press ENTER (Fig. 27 A).
26 L - F (lamp flashing) displays. This option is used with external
warning lamp. Typically, if monitoring is installed, this function is
used. Press Δand change status from L - F (lamp flashing) to
L - S (lamp static). L - F is a pulsed output supply and L -S is a
constant output supply.
27 Press ENTER with either choice selected to proceed to next part
of programming (Fig. 27 B).
Fig. 27
15

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
85307 Controller
28tSt (test mode) appears in display. Press Δfor pump to start
turning (Fig. 28). Correct pump from turning in wrong direction
by changing polarity of wiring. Check other sensors by energizing
them manually and observing if green LED illuminates. If LED
does not illuminate, a problem exists with wiring or setup
procedure. With external warning lamp, press ∇and LED will
either flash or show steady, indicating external device is working.
29 If all is correct, switch controller power to off and then to on
for unit to proceed into normal mode. Red setup LED will not
illuminate when unit is in normal run mode.
NOTE
tSt must appear on display before switching off power to unit.
System does not save changes if power to unit is turned off
during any part of programming. tSt must appear on display for
changes to be confirmed.
Fig. 28
16

Fig. 29
Fig. 30
Run mode
Unit proceeds in run (r) mode after power is terminated on unit and
then switched on again. All devices selected are displayed (Fig. 29).
Running system (pump run)
Run (r) time displays when controller is switched on. Time appears
from actual time set and counts down to zero. Green LED indicates
minutes (Fig. 30). Green LED next to PUMP flashes to indicate pump
is turning or pumping.
NOTE
After each cycle received, amount decreases by one until all
cycles have been received. Unit then proceeds to pause time.
17

STEP 5
Fig. 31
Fig. 32
Running system (pump pause)
Controller enters pause time when required run time is reached.
Pause (P) time counts down from original setup time to zero and
then resumes run time (Fig. 31). Green LED is steady next to PUMP
indicating pump is on but not turning while in pause mode.
Running system (vent cycles)
In dual-line system, when U(vent) displays, pump stops pumping
until line A or B pressure switch opens or line is totally vented.
As cycles complete, cycle count in Udisplay counts down (Fig. 32).
18

M
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESERVOIR
RUN
PAUSE
ENTER
A A
BB
R
P
1)
85307 Controller
2)
M
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESER VOIR
RUN
PAUSE
ENTER
A A
BB
R
P
2)
1)
85307 Controller
Stage 1
Cycle begins to pump lubricant through line B. As line begins to
pressurize, pressure switch closes. Green LED on controller
illuminates. Pump continues to pump until it reaches pressure set
on change-over valve. At this stage, pressure switch remains closed.
Stage 2
As pressure reaches change-over valve, direction of flow changes.
Grease in line A begins to pressurize while line B vents. As line A
reaches 290 psi (20 bar), pressure switch closes and shuts pump off
until line B is totally vented. Pressure switch in line B must be open
before cycle will continue. Both LEDs illuminate.
Diagram 1
Diagram 2
1) Set at 5 076 psi (350 bar).
2) Set from 290 to 580 psi (20 to 40 bar).
1) Set at 5 076 psi (350 bar).
2) Set from 290 to 580 psi (20 to 40 bar).
19

-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESER VOIR
RUN
PAUSE
ENTER
MA A
BB
R
P
1)
2)
85307 Controller
-
- --
8Amp
P2
RES IGN
P1
12V
24V
M
+++
+
-
TX RX
sec
min
hrs
cyc
SETUP
Fuse
PROXY 1
PUMP
PROXY 2
RESER VOIR
RUN
PAUSE
ENTER
MA A
BB
R
P
1)
2)
85307 Controller
Diagram 3
Diagram 4
Stage 3
As line B vents, pump continues to pressurize line A until it reaches
pressure setting of change-over valve. LED for line A pressure switch
remains on in this process. In display, rindicates cycles set have not
yet been completed.
Stage 4
As pressure reaches line A, it switches over change-over valve and
changes direction of flow. Line B begins to pressurize until it reaches
290 psi (20 bar). As pressure switch in line B closes, pump stops and
waits for pressure switch on line A to open. Both LEDs illuminate.
U2 (vent) shows in display and indicates two cycles remaining.
1) Set at 5 076 psi (350 bar).
2) Set from 290 to 580 psi (20 to 40 bar).
1) Set at 5 076 psi (350 bar).
2) Set from 290 to 580 psi (20 to 40 bar).
20
Other manuals for Lincoln 85307
3
Table of contents
Other SKF Control Unit manuals

SKF
SKF Lincoln 85307 User manual

SKF
SKF LCG2-A Series User manual

SKF
SKF BCU User manual

SKF
SKF BPSG2-PTA-MOD-EX-SS Manual

SKF
SKF SCU 1 User manual

SKF
SKF MAXILUBE MAX 230-IF105 Series User manual

SKF
SKF LINCOLN 85831 User manual

SKF
SKF SGA-011 User manual

SKF
SKF DCV5-4+924 Manual

SKF
SKF Lincoln 85307 User manual
Popular Control Unit manuals by other brands

Keyautomation
Keyautomation CT1RD Instructions and warnings for installation and use

Corsair
Corsair COMMANDER PRO installation guide

AutomationDirect
AutomationDirect Productivity2000 P2-08ND3-1 manual

IMG STAGE LINE
IMG STAGE LINE LDC-400 instruction manual

Sel
Sel 651R installation instructions

Lake Shore
Lake Shore 240 Series quick start guide