
Customer service and technical support
888.747.4LED (888.747.4533)
Europe: Customer service and technical support
+31 88 12 44 900
P/N 401251 Rev F 2017-06-06
12 VDC Power Supply Capacity Chart
Input Output
Power supply Part number Nominal input voltage Input current Power output Output current Maximum feet (meters)
Self-Contained 20 W 701680 100-240 V 0.55 A 20 W 1.5 A 8 (2.5)
Compact 12/25 W 410174 100-277 V 0.40 A 25 W 1.9 A 10.4 (5)
60C1 60 W 701507-60C1 100-277 V 0.80 A
60 W 4.5 A 25 (8)
60W1 60 W 701507-60W1 100-240 V 0.85 A
60W2 60 W 701507-60W2 100-277 V 0.80 A
MODW(E) 60 W 701507-MODW(E) 100-240 V 1.00 A
MOD277 60 W 701507-MOD277 277-347 V 0.50 A
120D1 120 W 701507-120D1 100-277 V 1.70 A 2 × 60 W 2 × 4.5 A 2 × 25 (8)
Power used per foot (meter) in watts: 2.1 W (6.8)
Troubleshooting
NOTE: A licensed electrician should perform all applicable steps.
Entire BendLUX leg does not light after
complete installation.
Check connection from power supply lead to rst section of BendLUX. Make sure polarity of connections made at power supply lead, any jumper
wire, and at rst section are correct. All connections must be RED-to-RED and BLACK-to-BLACK.
Still does not light. Disconnect BendLUX from power supply. Check output voltage of power supply using a multimeter. The output voltage should be 12.0 VDC ±
0.5 VDC. If there is no output voltage, have a licensed electrician check input voltage. Make sure power supply is connected correctly and getting
primary power. If power supply is connected properly and getting primary power and there is still no output voltage, replace power supply.
Still does not light. If power supply is getting primary power, has the correct output, and no sections light, there may be a short in the secondary wiring.
Check all connections and cap all loose wires.
The beginning of a leg lights, but entire leg
does not light or lights intermittently.
The primary cause of a portion of a BendLUX leg not lighting or lighting intermittently is a bad connection or reverse polarity connection between
sections that light and sections that don’t light. Check this connection.
An entire power supply leg of BendLUX
is dim.
Ensure maximum number of feet (meters) has not been exceeded (see above 12 VDC Power Supply Capacity Chart). Check secondary voltage.
If voltage is below 11.5 VDC, power supply leg may be overloaded.
One segment does not light, but all others
in the leg light.
BendLUX is designed so if one segment fails, it will not cause the entire leg to go out. If one segment does not light, but all others in the leg do,
replace the entire section with a new one.
BendLUX is covered by patents pending.
UL le number: E215393
4. Connect power supply: See Power Supply
Installation Guide for more information
regarding power supply installation.
NOTE: To avoid signicant line loss, do not use more than 6 ft (1.83 m) in series.
6 ft
(1.83 m)
6 ft
(1.83 m)
6 ft
(1.83 m)
6 ft
(1.83 m)
25 ft (8 m)
Maximum
NOTE: Each 12 V circuit must be limited to 5 A (60 W) or less. For North American installations, a power supply that meets NEC Class 2 specications is required.
BendLUX
Installation Guide for 701960-6WS241
PAGE 2 OF 2