
Operation
The glass bulb contains a uid which
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter the
glass bulb, allowing the sprinkler to ac-
tivate and water to ow.
Design Criteria
UL AND C-UL LISTING CRITERIA
The TYCO RAPID RESPONSE Series
LFII (TY4334) Residential Horizontal
Sidewall Sprinklers are UL and C-UL
Listed for installation in accordance
with this section.
Residential Sprinkler Design Guide
When conditions exist that are outside
the scope of the provided criteria, re-
fer to the Residential Sprinkler Design
Guide TFP490 for the manufacturer’s
recommendations that may be ac-
ceptable to the local authority having
jurisdiction.
System Type
Only wet pipe systems may be utilized.
Ceiling Types
Smooth at horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13 as
applicable.
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA 13D
or NFPA 13R, the minimum required
sprinkler ow rate are given in Table A
as a function of temperature rating and
the maximum allowable coverage ar-
eas. The sprinkler ow rate is the mini-
mum required discharge from each of
the total number of “design sprinklers”
as specied in NFPA 13D or NFPA 13R.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
• The ow rates given in Table A as a
function of temperature rating and
the maximum allowable coverage
area.
• A minimum discharge of 0.1 gpm/ft2
over the “design area” comprised of
the four most hydraulically demand-
ing sprinklers for the actual coverage
areas being protected by the four
sprinklers.
Example No. 1: A corridor being pro-
tected is 8 ft. wide; consequently, an
actual coverage area of 8 ft. x 20 ft.
is being contemplated. Based on us-
ing the LFII (TY4334) Residential Hor-
izontal Sidewall Sprinklers, the ow
rate provided in Table A for a 16 ft x
20 ft. coverage area is 29 GPM. How-
ever based on minimum discharge of
0.1 gp m/ f t2the ow rate would be 16
GPM. In this case a minimum ow rate
of 29 GPM for this design sprinkler
must be utilized.
Example No. 2: The room being pro-
tected is 16 x 16 ft.. Based on using
the LFII (TY4334) Residential Hori-
zontal Sidewall Sprinklers, the ow
rate provided in Table A for a 16 ft. x
16 ft. coverage area is 21 GPM. How-
ever based on minimum discharge of
0.1 gp m/ f t2the ow rate would be 26
GPM. In this case a minimum ow rate
of 26 GPM for this design sprinkler
must be utilized.
Obstruction To Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as
with the obstruction criteria described
within the TYCO Technical Data Sheet
TFP490.
Operational Sensitivity
The sprinklers are to be installed with
an end-of-deector-boss to wall dis-
tance of 1-1/4 to 6 inches.
In addition the top-of-deector-to-
ceiling distance is to be within the
range (Ref. Table A) being hydraulically
calculated.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot ex-
ceed the width of the coverage area
(Ref. Table A) being hydraulically cal-
culated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 16 feet
for a 16 ft. x 20 ft. coverage area).
FM APPROVAL CRITERIA
The Series LFII (TY4334) Residen-
tial Horizontal Sidewall Sprinklers are
FM Approved for installation in accor-
dance with the applicable Factory Mu-
tual Loss Prevention Data Sheet FM
2-5. Criteria provided by FM may dif-
fer for UL and/or NFPA, therefore the
designer should review and become
familiar with Factory Mutual require-
ments before proceeding with design.
The following information pertaining to
System Type, Hydraulic Design, and
Sprinkler spacing are provided for ref-
erence and are not intended to provide
complete installation criteria as pro-
vided in the applicable Factory Mutual
Loss Prevention Data Sheet.
Residential Sprinkler Design Guide
When conditions exist that are outside
the scope of the provided criteria, re-
fer to the Residential Sprinkler Design
Guide TFP490 for the manufacturer’s
recommendations that may be ac-
ceptable to the local authority having
jurisdiction.
System Type
Only wet pipe systems may be utilized.
Hydraulic Design
The number of design sprinklers is
to be the four most hydraulically de-
manding sprinklers. The minimum re-
quired discharge from each of the four
sprinklers is to be greater than the
following:
• The ow rates given in Table B as a
function of the maximum allowable
coverage area.
• A minimum discharge of 0.1 gpm/ft2
over the “design area” comprised of
the four most hydraulically demand-
ing sprinklers for the actual coverage
areas being protected by the four
sprinklers.
Example No. 1: A corridor being pro-
tected is 10 ft. wide; LFII Sidewall
Sprinklers are being installed at 16 ft.
apart along the corridor. Consequent-
ly, an actual coverage area of 10 ft. x
16 ft. is being contemplated. Based
on using the LFII (TY4334) Residential
Horizontal Sidewall Sprinklers, the ow
rate provided in Table B for a 16 ft x
20 ft. coverage area is 32 GPM. How-
ever based on minimum discharge of
0.1 g pm/ f t2the ow rate would be 16
GPM. In this case a minimum ow rate
of 24 GPM for this design sprinkler
must be utilized.
Example No. 2: The room being pro-
tected is 16 x 16 ft.. Based on using the
LFII (TY4334) Residential Horizontal
Sidewall Sprinklers, the ow rate pro-
vided in Table B for a 16 ft x 16 ft. cov-
erage area is 24 GPM. However based
on minimum discharge of 0.1 gpm/ft2
the ow rate would be 26 GPM. In this
case a minimum ow rate of 26 GPM
for this design sprinkler must be uti-
lized (in no case shall the design pres-
sure be less than 7 psi).
Sprinkler Spacing.
The minimum spacing between sprin-
klers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot ex-
ceed the width of the coverage area
(Ref. Table B) being hydraulically cal-
culated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 16 feet
for a 16 ft. x 20 ft. coverage area).
TFP417
Page 3 of 6