Installation Methods
Installation with BET
Ensure that proper drainage is provided for the shown
installation methods.
1) In landscaped areas (soil with gravel base), pic. 1
2) In paved areas (concrete with gravel base), pic. 2
pic. 1 pic. 2
pic. 3 pic. 4 pic. 5 pic. 6
gravel (drainage)
concrete
soil
Phase Two
(Electrical connection, aiming)
4) Switch off mains electrical supply.
5) Check that rating shown on luminaire label conforms
with the mains electrical supply. Observe the maxi-
mum permissible wattage in connection with BET
installation blockouts (refer to table “Installation
Accessories”).
6) Loosen screws Kand remove cover B. Remove
cover Gand lens/gasket assembly H/I by removing
the six countersunk screws J.
Installation without BET
3) In landscaped areas (soil with gravel), pic. 3
4) In landscaped areas (soil with concrete and graval
base), pic. 4
5) In paved areas (concrete), pic. 5
6) In paved areas (concrete with gravel base) see pic. 6
Installation with Blockout BET
Phase One
(During earth or masonry works)
1) Put the mounting ring Eon to the installation
blockout Oin that way, that the connector L lock
into position on the blind rivets S.
2) A suitable recess to be provided to accomodate
installation blockout/mounting ring assembly E/O.
Proceed as follows:
a) Set in position together with supply cable(s) P.
b) Luminaire mounting ring Eto be flush with surface
F(if the floor will be tiled or paved afterwards
leave an appropriate gap).
c) Point arrow Rtowards the object (wall, tree,
column ...) to be illuminated.
3) During ongoing earth and/or masonry works, ensure
that installation blockout/mounting ring assembly
E/O is not damaged and maintains its original
shape. If necessary use a cover plate.
7) Remove the chassis M from the luminaire housing N.
8) Ensure that all surfaces are clean and dry. Then
remove gel bag from aluminium envelope. Place
bag inside the bottom of the luminaire N.
9) Remove the two screws Qfrom mounting ring E.
Open the packaging of the desiccant bag. Place
the bag in the lower part of the luminaire housing.
10) Connect wires of luminaire cable Aand mains
supply cable Pin sealable junction box C(e.g.
WE-EF product no. 185-1624) and/or provided
UL410-D wire nuts. Seal junction box properly.
11) Insert the housing into the blockout. Fix mounting
ring Eto luminaire by inserting two stainless screws
Qand tightening them equally.
12) Assemble in reverse order.
13) Set lens/gasket assembly H/I, cover Gand the six
countersunk screws Jin position as described.
Then, while taking all necessary precautions to
ensure safety:
a) Leave the screws untightened and ignite the lumin-
aire for approx. 30 minutes to allow any moisture
to evaporate.
b) Begin tightening the countersunk screws Jin steps
in a criss-cross pattern, until all six screws are pro-
perly seated and secured. Repeat tightening proce-
dure, again in a criss-cross pattern, for another two
rounds with a torque of 9 Nm.
14) Set luminaire in position while observing to avoid
stress on junction box C, cable Aand cable gland D.
15) Reposition cover Band tighten screws K.