Xtreme NXTI 3P-1P User manual

NXTi 3P-1P Online UPS
10kVA Model
User & Installaon Manual
www.xpcc.com | © 2015 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 6/24/15)

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 2
Uninterrupble Power Supply
Table of Contents
Safety and EMC Instrucons.........................................................................3
Transportaon and Storage.............................................................................................................3
Preparaon......................................................................................................................................3
Installaon.......................................................................................................................................3
Standards.........................................................................................................................................4
Installaon and Operaon............................................................................4
Unpacking and Inspecon...............................................................................................................4
Rear Panel View...............................................................................................................................5
Single UPS Installaon.....................................................................................................................6
UPS Installaon for Parallel System.................................................................................................7
Soware Installaon........................................................................................................................8
Operaons...................................................................................................9
Buon Operaon.............................................................................................................................9
LED Indicators and LCD Panel..........................................................................................................9
Audible Alarm................................................................................................................................11
Single UPS Operaon.....................................................................................................................12
Parallel Operaon..........................................................................................................................15
Abbreviaon Meaning in LCD Display............................................................................................16
LCD Seng....................................................................................................................................18
Operang Mode/Status Descripon.............................................................................................24
Fault Code.....................................................................................................................................29
Warning Indicator..........................................................................................................................29
Warning Code............................................................................................................................... 30
Troubleshoong.........................................................................................30
Storage and Maintenance...........................................................................32
Storage...........................................................................................................................................32
Maintenance.................................................................................................................................32
Specicaons.............................................................................................33

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 3
Uninterrupble Power Supply
Safety and EMC Instrucons
Please read carefully the following user manual and the safety instrucons before installing the unit or using the
unit!
Transportaon and Storage
• Please transport the UPS system only in the original package to protect against shock and impact. The UPS
must be stored in the room where it is venlated and dry.
Preparaon
• Condensaon may occur if the UPS system is moved directly from cold to warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system
to acclimate the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
• Do not block venlaon holes in the UPS housing.
Installaon
• Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to
the UPS output sockets or terminal.
• Place cables in such a way that no one can step on or trip over them.
• Do not block air vents in the housing of UPS. The UPS must be installed in a locaon with good venlaon.
Ensure enough space on each side for venlaon.
• UPS has provided earthed terminal, in the nal installed system conguraon, equi-potenal earth bond-
ing to the external UPS baery cabinets.
• The UPS can be installed only by qualied maintenance personnel.
• An appropriate disconnect device as short-circuit backup protecon should be provided in the building
wiring installaon.
• An integral single emergency switching device which prevents further supply to the load by the UPS in any
mode of operaon should be provided in the building wiring installaon.
• Connect the earth before connecng to the building wiring terminal.
• Installaon and Wiring must be performed in accordance with the local electrical laws and regulaons.
Operaon
• Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any me since
this would cancel the protecve earth of the UPS system and of all connected loads.
• The UPS system features its own, internal current source (baeries). The UPS output sockets or output ter-
minal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
• In order to fully disconnect the UPS system, rst press the “OFF” buon and then disconnect the mains
• Ensure that no liquid or other foreign objects can enter into the UPS system.
• The UPS can be operated by any individuals with no previous experience.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 4
Uninterrupble Power Supply
Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2 Category C3
Radiated Emission..................................:IEC/EN 62040-2 Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2 Level 4
RS...........................................................:IEC/EN 61000-4-3 Level 3
EFT..........................................................:IEC/EN 61000-4-4 Level 4
SURGE....................................................:IEC/EN 61000-4-5 Level 4
CS...........................................................:IEC/EN 61000-4-6 Level 3
Power-frequency Magnec eld............:IEC/EN 61000-4-8 Level 4
Low Frequency Signals...........................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial applicaon in the second environment-installaon re-
stricons or addional measures may be needed to prevent disturbances.
Installaon and Operaon
There are two dierent types of online UPS: standard and long-run models. Please refer to the following model
table.
Model Type Model Type
NXTi-10K 3-1 Standard model NXTi-10KL 3-1 Long-run model
We also oer oponal parallel funcon for these two types by request. The UPS with parallel funcon is called as
“Parallel model”. We have described detailed installaon and operaon of Parallel Model in the following chapter.
Unpacking and Inspecon
Unpack the package and check the package contents. The shipping package contains:
• One UPS
• One user manual
• One monitoring soware CD
• One RS-232 cable (opon)
• One USB cable
• One EPO plug
• One parallel cable (only available for parallel model)
• One share current cable (only available for parallel model)
• One baery cable (only available for 10KL)
NOTE: Before installaon, please inspect the unit. Be sure that nothing inside the package is damaged during
transportaon. Do not turn on the unit and nofy the carrier and dealer immediately if there is any damage or
lacking of some parts. Please keep the original package in a safe place for future use.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 5
Uninterrupble Power Supply
Rear Panel View
10K/10KL Rear Panel
10K/10KL Input/Output Terminal
1. RS-232 communicaon port
2. USB communicaon port
3. Emergency power o funcon connector (EPO connector)
4. Share current port (only available for parallel model)
5. Parallel port (only available for parallel model)
6. Intelligent slot
7. Charger fan
8. Power stage fan
9. Maintenance bypass switch

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 6
Uninterrupble Power Supply
10. Input circuit breaker
11. Output circuit breaker for receptacles
12. Output receptacles: connect to mission-crical loads
13. Input/Output terminal (Refer to Diagram 4, 5, 6 and 7 for the details)
14. Output terminal: connect to mission-crical loads
15. Programmable output terminal: connect to non-crical loads
16. External baery terminal (only available for Long-run model)
17. Ulity input terminal
18. Grounding terminal
Single UPS Installaon
Installaon and wiring must be performed in accordance with the local electric laws/regulaons and execute the
following instrucons by professional personnel.
1. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid
the hazards of electric shock or re.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than
the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2. Switch o the mains switch in the building before installaon.
3. Turn o all the connected devices before connecng to the UPS.
4. Prepare wires based on the following table:
Model Wiring spec (AWG)
Input Output Baery Ground
10K 8 8 8
10KL 8 8 8 8
NOTE 1: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use
8AWG or thicker wire for safety and eciency.
NOTE 2: The selecons for color of wires should be followed by the local electrical laws and regulaons.
5. Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the fol-
lowing terminal block diagrams: (Connect the earth wire rst when making wire connecon. Disconnect
the earth wire last when making wire disconnecon!)
Terminal Block wiring diagram of 10K/10KL
NOTE 1: Make sure that the wires are connected ghtly with the terminals.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 7
Uninterrupble Power Supply
NOTE 2: There are two kinds of outputs: output terminal/outlets and programmable terminal. Please con-
nect non-crical devices to the programmable terminal and crical devices to the output terminal/outlets.
During power failure, you may extend the backup me to crical devices by seng shorter backup me
for non-crical devices.
NOTE 3: Please install the output breaker between the output terminal and the load, and the breaker
should be qualied with leakage current protecve funcon if necessary.
6. Insert the EPO plug into the EPO slot on the rear panel.
7. Put the terminal block cover back to the rear panel of the UPS.
Warning: (Only for standard model)
• Make sure the UPS is not turned on before installaon. The UPS should not be turned on during wiring
connecon.
• Do not try to modify the standard model to the long-run model. Parcularly, do not try to connect the
standard internal baery to the external baery. The baery type and voltage may be dierent. If you con-
nect them together, it maybe causes the hazard of electric shock or re!
Warning: (Only for long-run model)
Make sure a DC breaker or other protecon device between UPS and external baery pack is installed. If not,
please install it carefully. Switch o the baery breaker before installaon.
NOTE: Set the baery pack breaker in “OFF” posion and then install the baery pack.
• Pay highly aenon to the rated baery voltage marked on the rear panel. If you want to change the num-
bers of the baery pack, please make sure you modify the seng simultaneously. The connecon with
wrong baery voltage may cause permanent damage of the UPS. Make sure the voltage of the baery
pack is correct
• Pay highly aenon to the polarity marking on external baery terminal block, and make sure the correct
baery polarity is connected. Wrong connecon may cause permanent damage of the UPS.
• Make sure the protecve earth ground wiring is correct. The wire current spec, color, posion, connecon
and conductance reliability should be checked carefully.
• Make sure the ulity input & output wiring is correct. The wire current spec, color, posion, connecon
and conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse and
short-circuited.
UPS Installaon for Parallel System
If the UPS is only available for single operaon, you may skip this secon to the next.
1. Install and wires the UPSs according to the Single UPS Installaon secon.
2. Connect the output wires of each UPS to an output breaker.
3. Connect all output breakers to a major output breaker. Then this major output breaker will directly con-
nect to the loads.
4. Each UPS is connected to an independent baery pack.
NOTE: The parallel system cannot use one baery pack. Otherwise, it will cause system permanent failure.
5. Refer to the following wiring diagram:

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 8
Uninterrupble Power Supply
Wiring diagram of parallel system for 10K/10KL
Soware Installaon
For opmal computer system protecon, install UPS monitoring soware to fully congure UPS shutdown.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 9
Uninterrupble Power Supply
Operaons
Buon Operaon
Buon Funcon
ON/Enter Buon • Turn on the UPS: Press and hold the buon more than 0.5s to turn on the UPS.
• Enter Key: Press this buon to conrm the selecon in seng menu.
OFF/ESC Buon • Turn o the UPS: Press and hold the buon more than 0.5s to turn o the UPS.
• Esc key: Press this buon to return to last menu in seng menu.
Test/Up Buon
• Baery test: Press and hold the buon more than 0.5s to test the baery while in
AC mode and CVCF* mode.
• UP key: Press this buon to display next selecon in seng menu.
Mute/Down Buon • Mute the alarm: Press and hold the buon more than 0.5s to mute the buzzer.
• Down key: Press this buon to display previous selecon in seng menu.
Test/Up + Mute/Down
Buon
• Press and hold the two buons simultaneous more than 1s to enter/escape the
seng menu.
* CVCF means Constant Voltage and Constant Frequency.
LED Indicators and LCD Panel
LED Indicators
There are 4 LEDs on front panel to show the UPS working status:
Mode Bypass Line Baery Fault
UPS On ● ● ● ●
No Output mode ○ ○ ○ ○
Bypass mode ● ○ ○ ○
AC mode ○ ● ○ ○
Baery mode ○ ○ ● ○
CVCF mode ○ ● ○ ○
Baery Test ● ● ● ○
ECO mode ● ● ○ ○
Fault ○ ○ ○ ●
Note: ● means LED is lighng, and ○ means LED is faded.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 10
Uninterrupble Power Supply
LCD Panel
Display Funcon
Backup me informaon
Indicates the baery discharge me in numbers
H: hours, M: minutes, S: seconds
Fault informaon
Indicates that the warning and fault occurs.
Indicates the fault codes
Mute operaon
Indicates that the UPS alarm is disabled.
Output & Baery voltage informaon
Indicates the output voltage, frequency or baery voltage. Vac: output voltage, Vdc:
baery voltage, Hz: frequency
Load informaon
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the output is short.
Mode operaon informaon
Indicates the UPS connects to the mains.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 11
Uninterrupble Power Supply
Indicates the baery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
Baery informaon
Indicates the Baery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the baery is not connected.
Indicates low baery level and low baery voltage.
Input & Baery voltage informaon
Indicates the input voltage or frequency or baery voltage. Vac: Input voltage, Vdc:
baery voltage, Hz: input frequency
Audible Alarm
Descripon Buzzer status Muted
UPS status
Bypass mode Beeping once every 2 minutes
YesBaery mode Beeping once every 4 seconds
Fault mode Beeping connuously
Warning

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 12
Uninterrupble Power Supply
Overload Beeping twice every second
No
Low baery
Beeping once every second
Baery unconnected
Over charge
EPO enable
Fan failure
Over temperature
Charger failure
L1 IP fuse broken
Baery fuse broken
Overload 3 mes in 30min
IP Neutral loss
IP phase abnormal
Converter Current unbalance
Inverter Current unbalance
Cover of maintain switch is open
Phase auto adapt failure
Fault
Bus start failure
Beeping connuously Yes
Bus over
Bus under
Bus unbalance
Converter over current
Inverter so start failure
High Inverter voltage
Low Inverter voltage
Inverter output short circuited
Negave power fault
Baery SCR short circuited
Inverter relay short circuited
Baery fuse broken in baery mode
Parallel communicaon failure
Parallel output current unbalance
Single UPS Operaon
Turn on the UPS with ulity power supply (in AC mode)
1. Aer power supply is connected correctly, set the breaker of the baery pack at “ON” posion (the step
only available for long-run model). Then set the line input breaker at “ON” posion(for dual input unit,
also set the bypass input breaker at “ON”). At this me the fan is running and the UPS enter to power on
mode for inializaon, several seconds later, UPS operates in Bypass mode and supplies power to the
loads via the bypass.
NOTE: When UPS is in Bypass mode, the output voltage will directly power from ulity aer you switch on
the input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, you

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 13
Uninterrupble Power Supply
should turn on the UPS. Refer to next step.
2. Press and hold the “ON” buon for 0.5s to turn on the UPS and the buzzer will beep once.
3. A few seconds later, the UPS will enter to AC mode. If the ulity power is abnormal, the UPS will operate
in Baery mode without interrupon.
NOTE: When the UPS is running out baery, it will shut down automacally at Baery mode. When the
ulity power is restored, the UPS will auto restart in AC mode.
Turn on the UPS without ulity power supply (in Baery mode)
1. Make sure that the breaker of the baery pack is at “ON” posion (only for long-run model).
2. Press the “ON” buon to set up the power supply for the UPS, UPS will enter to power on mode. Aer
inializaon UPS will enter to No Output mode, then Press and hold the “ON” buon for 0.5s to turn on
the UPS, and the buzzer will beep once.
3. A few seconds later, the UPS will be turned on and enter to Baery mode.
Connect devices to UPS
Aer the UPS is turned on, you can connect devices to the UPS.
1. Turn on the UPS rst and then switch on the devices one by one, the LCD panel will display total load level.
2. If it is necessary to connect the inducve loads such as a printer, the in-rush current should be calculated
carefully to see if it meets the capacity of the UPS, because the power consumpon of this kind of loads
is too big.
3. If the UPS is overload, the buzzer will beep twice every second.
4. When the UPS is overload, please remove some loads immediately. It is recommended to have the total
loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system
safety.
5. If the overload me is over acceptable me listed in spec at AC mode, the UPS will automacally transfer
to Bypass mode. Aer the overload is removed, it will return to AC mode. If the overload me is over ac-
ceptable me listed in spec at Baery mode, the UPS will become fault status. At this me, if bypass is
enabled, the UPS will power to the load via bypass. If bypass funcon is disabled or the input power is not
within bypass acceptable range, it will cut o output directly.
Charge the baeries
1. Aer the UPS is connected to the ulity power, the charger will charge the baeries automacally except
in Baery mode or during baery self-test.
2. Suggest to charge baeries at least 10 hours before use. Otherwise, the backup me may be shorter than
expected me.
3. Make sure the baery numbers seng on the control board is consistent to real connecon.
Baery mode operaon
1. When the UPS is in Baery mode, the buzzer will beep according to dierent baery capacity. If the bat-
tery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the baery voltage drops to
the alarm level, the buzzer will beep quickly (once every sec) to remind users that the baery is at low level
and the UPS will shut down automacally soon. Users could switch o some non-crical loads to disable
the shutdown alarm and prolong the backup me. If there is no more load to be switched o at that me,
you have to shut down all loads as soon as possible to protect the devices or save data. Otherwise, there
is a risk of data loss or load failure.
2. In Baery mode, if buzzer sound annoys, users can press the Mute buon to disable the buzzer.
3. The backup me of the long-run model depends on the external baery capacity.
4. The backup me may vary from dierent environment temperature and load type.
5. When seng backup me for 16.5 hours (default value from LCD panel), aer discharging 16.5 hours, UPS
will shut down automacally to protect the baery. This baery discharge protecon can be enabled or
disabled through LCD panel control.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 14
Uninterrupble Power Supply
Test the baeries
1. If you need to check the baery status when the UPS is running in AC mode/CVCF mode, you could press
the “Test” buon to let the UPS do baery self-test.
2. Users also can set baery self-test through monitoring soware.
3. If the UPS is at baery self-test, the LCD display and buzzer indicaon will be the same as at Baery mode
except that the baery LED is ashing.
Turn o the UPS with ulity power supply in AC mode
1. Turn o the inverter of the UPS by pressing “OFF” buon for at least 0.5s, and then the buzzer will beep
once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from ulity power to
output terminal even though you have turned o the UPS (inverter).
NOTE 2: Aer turning o the UPS, please be aware that the UPS is working at Bypass mode and there is
risk of power loss for connected devices.
2. In Bypass mode, output voltage of the UPS is sll present. In order to cut o the output, switch o the line
input breaker(for dual input unit, also switch o the bypass line breaker). A few seconds later, there is no
display shown on the display panel and UPS is complete o.
Turn o the UPS without ulity power supply in Baery mode
1. Turn o the UPS by pressing “OFF” buon for at least 0.5s, and then the buzzer will beep once.
2. Then UPS will cut o power to output and there is no display shown on the display panel.
Mute the buzzer
1. To mute the buzzer, please press the “Mute” buon for at least 0.5s. If you press it again aer the buzzer
is muted, the buzzer will beep again.
2. Some warning alarms can’t be muted unless the error is xed.
Operaon in warning status
1. When Fault LED ashes and the buzzer beeps once every second, it means that there are some problems
for UPS operaon. Users can get the warning indicator from LCD panel. Please check the trouble shoong
table for details.
2. Some warning alarms can’t be muted unless the error is xed.
Operaon in Fault mode
1. When Fault LED illuminates and the buzzer beeps connuously, it means that there is a fatal error in the
UPS. Users can get the fault code from display panel. Please check the trouble shoong table for details.
2. Please check the loads, wiring, venlaon, ulity, baery and so on aer the fault occurs. Don’t try to turn
on the UPS again before solving the problems. If the problems can’t be xed, please contact the distributor
or service people immediately.
3. For emergency case, please cut o the connecon from ulity, external baery, and output immediately
to avoid more risk or danger.
Operaon of changing baery numbers
1. This operaon is only available for professional or qualied technicians.
2. Turn o the UPS. If the load couldn’t be cut o, you should remove the cover of maintenance bypass
switch on the rear panel and turn the maintenance switch to “BPS” posion rst.
3. Switch o the line input breaker (for dual input unit, also switch o the bypass input breaker), and switch
o the baery breaker (only available for long-run model).
4. Remove the cabinet cover, and disconnect baery wire for standard model. Then modify the jumper of JS3
on the control board to set the baery numbers as following table.
NOTE: JS3 seng on the control board: please shorts the Pin1 & Pin2 for 18 pcs baeries; shorts the Pin3
& Pin4 for 19 pcs baeries; and shorts the Pin5 & Pin6 for 20 pcs baeries.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 15
Uninterrupble Power Supply
5. Modify the baery pack for the seng number carefully. Aer complete it, put the cover back, switch on
the baery breaker for long-run model.
Parallel Operaon
Parallel system inial startup
1. Make sure all of the UPSs are parallel models and have the same conguraon. Then, follow the wiring
steps.
2. Turn o the input and output breakers of each UPS, and turn o the baery breaker if the UPS is long-run
model.
3. Remove the cover of parallel share current port on the UPS. Connect each UPS one by one with parallel
cable and share current cable.
4. Turn on the parallel system with ulity power supply (in AC mode)
a. Turn on the input breaker of each UPS. Aer all UPSs enter to bypass mode, measure the voltage
dierence between the output line1 of each UPS with mulmeter. If the voltage dierence is less
than 1V, it means all connecons are correct. If the dierence is more than 1V, recheck if the wir-
ings are connected correctly.
b. Aer voltage dierence is measured less than 1V, turn on each UPS in turns. Aer a while, the
UPSs will enter to AC mode synchronously. Measure the output voltage of each UPS to check if
the voltage dierence is less than 1.5V (typical 1V) with mulmeter. If the dierence is more than
1.5V, please calibrate output voltage by conguring inverter voltage (Program 15) in LCD seng. If
voltage dierence remains more than 1.5V, please contact your local distributor or service center
for help.
c. Turn o each UPS in turns and aer all of UPSs transfer to Bypass mode, turn on the output
breaker of each UPS.
d. Turn on each UPS in turns, aer a while, the UPSs will enter to AC mode synchronously and then
the parallel system installaon is complete.
5. Turn on the parallel system without ulity power supply (in Baery mode)
a. Turn on the baery breaker (only available in long-run model) and output breaker of each UPS.
NOTE 1: The output breaker of each UPS should be turned on when turning on the parallel system
without ulity power supply. Otherwise, the parallel system cannot be operated.
NOTE 2: It’s not allowed to share one baery pack for long-run UPSs in parallel system. Each UPS
should be connected to its baery pack.
b. Turn on any one UPS. A few seconds later, the UPS will enter to baery mode.
c. Then turn on another UPS. A few seconds later, the UPS will enter to baery mode and add to the
parallel system.
d. If you have the third UPS, follow the same procedure of c). Then the parallel system is complete.
Add one new unit into the parallel system
1. You cannot add one new unit into the parallel system when whole system is running. You must cut o the
load and shutdown the system.
2. Make sure all of the UPS are the parallel models.
3. Install the new parallel system refers to the previous secon.
Remove one unit from the parallel system
There are two methods to remove one unit from the parallel system:
First method:
1. Press the “OFF” key twice and each me should be lasted for more than 0.5s. Then, the UPS will enter into
bypass mode or no output mode without output.
2. Turn o the output breaker of this unit, and then turn o the input breaker of this unit.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 16
Uninterrupble Power Supply
3. Aer it shuts down, you can turn o the baery breaker (for long-run model) and remove the parallel and
share current cables. And then remove the unit from the parallel system.
Second method:
1. If the bypass is abnormal, you can not remove the UPS without interrupon. You must cut o the load and
shut down the system rst.
2. Make sure the bypass seng is enabled in each UPS and then turn o the running system. All UPSs will
transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance switches
from “UPS” to “BPS”. Turn o all the input breakers and baery breakers in parallel system.
3. Turn o the output breaker and remove the parallel cable and share current cable of the UPS which you
want to remove. Then, remove it from parallel system.
4. Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set the main-
tenance switches from “BPS” to “UPS and put the maintenance bypass covers back.
5. Turn on the remaining UPS according to the previous secon.
Warning: (Only for the parallel system)
• Before turning on the parallel system to acvate inverter, make sure that all unit’s maintenance switch at
the same posion.
• When parallel system is turned on to work through inverter, please do not operate the maintenance switch
of any unit.
Abbreviaon Meaning in LCD Display
Abbreviaon Display content Meaning
ENA Enable
DIS Disable
ATO Auto
BAT Baery
NCF Normal mode (not CVCF mode)
CF CVCF mode
SUB Subtract
ADD Add
ON On

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 17
Uninterrupble Power Supply
OFF O
FBD Not allowed
OPN Allow
RES Reserved
N.L Neutral line loss
CHE Check
O P.V Output voltage
PAR Parallel, 001 means the rst UPS
AN The rst phase
BN The second phase
CN The third phase
AB The rst line
BC The second line
CA The third line

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 18
Uninterrupble Power Supply
LCD Seng
There are three parameters to set up the UPS. Refer to following diagram.
Note: The following order of seng code only presents when UPS is in Bypass Mode or no-output mode. The set-
ng code number will change the numbers under other modes. For example, when the UPS is in AC mode, the to-
tal available seng becomes 7 only. Then, seng code of “Bypass mode seng” will become 01, “Baery backup
me seng” will become 02, and so on.
16 programs available list for parameter 1:
Code Descripon Bypass / No
Output mode
AC
mode
ECO
mode
CVCF
mode
Baery
mode
Baery
Test
01 Output voltage Y*
02 Output frequency Y
03 Voltage range for bypass Y
04 Frequency range for bypass Y
05 ECO mode enable/disable Y
06 Voltage range for ECO mode Y
07 ECO mode frequency range seng Y
08 Bypass mode seng Y Y
09 Baery backup me seng Y YYYYY
10 Programmable output seng Y YYYYY
11 Shutdown point for programmable
output Y YYYYY
12 Reserved /Neutral Loss**
13 Baery voltage adjustment Y YYYYY
14 Charger voltage adjustment Y YYYYY
15 Inverter voltage adjustment Y Y Y
16 Output voltage calibraon Y Y Y
17 Phase auto adapt enable/disable Y
*Y means that this program can be set in this mode.
**It is only available to operate when a loss of neutral line is detected. Otherwise, it will display “ ” in program
seng menu.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 19
Uninterrupble Power Supply
01: Output voltage
Interface Seng
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac
02: Output frequency
Interface Seng
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Parameter 2: Output Frequency
Seng the output frequency. You may choose following three op-
ons in parameter 2:
50.0Hz: The output frequency is seng for 50.0Hz.
60.0Hz: The output frequency is seng for 60.0Hz.
ATO: If selected, output frequency will be decided according to the
latest normal ulity frequency. If it is from 46Hz to 54Hz, the out-
put frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output
frequency will be 60.0Hz. ATO is default seng.
Parameter 3: Frequency mode
Seng output frequency at CVCF mode or not CVCF mode. You may
choose following two opons in parameter 3:
CF: Seng UPS to CVCF mode. If selected, the output frequency will
be xed at 50Hz or 60Hz according to seng in parameter 2.
The input frequency could be from 46Hz to 64Hz.
NCF: Seng UPS to normal mode (not CVCF mode). If selected, the
output frequency will synchronize with the input frequency within
46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to seng in
parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to
baery mode when input frequency is not within 46~54 Hz. If 60Hz
selected in parameter 2, UPS will transfer to baery mode when
input frequency is not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current fre-
quency.
03: Voltage range for bypass
Interface Seng
Parameter 2: Set the acceptable low voltage for bypass. Seng
range is from 110V to 209V and the default value is 110V.
Parameter 3: Set the acceptable high voltage for bypass. Seng
range is from 231V to 276V and the default value is 264V.

Xtreme Power Conversion Corporaon
NXTi 3P-1P User’s Manual
Page 20
Uninterrupble Power Supply
04: Frequency range for bypass
Interface Seng
Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Seng range is from 46.0Hz to 49.0Hz.
60 Hz system: Seng range is from 56.0Hz to 59.0Hz. The default
value is 46.0Hz/56.0Hz.
Parameter 3: Set the acceptable high frequency for bypass.
50 Hz: Seng range is from 51.0Hz to 54.0 Hz.
60 Hz: Seng range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: ECO mode enable/disable
Interface Seng
Parameter 3: Enable or disable ECO funcon. You may choose fol-
lowing two opons:
DIS: disable ECO funcon
ENA: enable ECO funcon
If ECO funcon is disabled, voltage range and frequency range for
ECO mode sll can be set, but it is meaningless unless the ECO func-
on is enabled.
06: Voltage range for ECO mode
Interface Seng
Parameter 2: Low voltage point in ECO mode. The seng range is
from -5% to -10% of the nominal voltage.
Parameter 3: High voltage point in ECO mode. The seng range is
from +5% to +10% of the nominal voltage.
07: Frequency range for ECO mode
Interface Seng
Parameter 2: Set low voltage point for ECO mode.
50 Hz system: Seng range is from 46.0Hz to 48.0Hz.
60 Hz system: Seng range is from 56.0Hz to 58.0Hz. The default
value is 48.0Hz/58.0Hz.
Parameter 3: Set high voltage point for ECO mode.
50 Hz: Seng range is from 52.0Hz to 54.0 Hz.
60 Hz: Seng range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
Table of contents
Other Xtreme UPS manuals