manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Power Supply
  8. •
  9. ABB CP-T 24/20.0 User manual

ABB CP-T 24/20.0 User manual

ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82
69123 Heidelberg / Germany
www.abb.com/lowvoltage
Primary switch mode power supplies
CP-T 24/20.0, CP-T 48/10.0
1SVC 427 051 M0000 A7 (05/16)
Out-
put
Input
Fig. 1
Fig. 2 Fig. 3
8 mm
Fig. 4 Fig. 5 Derating
-30 60 70
10
20
30
40
50
60
70
80
90
100
Pout [%]
Ta[°C]
2CDC 272 030 F0211
Connector size range:
Fine-strand with ferrule 0.2-4.0 mm² (24-11 AWG)
Rigid 0.2-6.0 mm² (24-10 AWG)
13-14 (Spring-type terminals):
Fine-strand with ferrule 0.2-0.34 mm² (24-22 AWG)
Rigid 0.12-0.5 mm² (26-20 AWG)
Tightening torque of input connector: Max. 1 Nm (9 lb.in)
Tightening torque of output connector: Max. 0.6 Nm (5.5 lb.in)
Use copper conductors 60/75 °C only
ADDITIONAL INFORMATION RELATING TO UL APPROVALS
FOR USE IN POLLUTION DEGREE 2 ENVIRONMENT
ACCORDING TO ANSI-ISA 12.12:
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, and D OR
NON-HAZARDOUS LOCATIONS ONLY.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS
POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
WARNING - EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF
MATERIALS USED IN THE SWITCHING ELEMENTS IN THE DEVICE.
Sealed Device: Switch Model ST-22 manufactured by Seki Controls Company , LTD.
Switch Case: LG Chemical LTD., Type Lupox GP2306FT-NP, PBT Resin
Switch Epoxy: Emerson & Coming, Type ST 2850FT-FRJ-CA9, Epoxy Resin
We recommend to periodically inspect the device named above for any degradation of properties
and replace if degradation is found.
ACCORDING TO UL 508:
MAX. SURROUNDING AIR TEMPERATURE Ta= 50 °C
INFORMATION COMPLÉMENTAIRE POUR USA/CANADA
POUR UTILISATION DANS UN ENVIRONNEMENT DE DEGRÉ DE POLLUTION 2.
SELON ANSI-ISA 12.12:
CET ÉQUIPEMENT EST ADAPTÉ À UNE UTILISATION SELON LA CLASS I, DIVISION 2, GROUPES
A, B, C, D OU ENVIRONNEMENTS NON DANGEREUX SEULEMENT.
AVERTISSEMENT – RISQUE D’EXPLOSION – LA SUBSTITUTION DE COMPOSANTS PEUT
NUIRE À LA CONFORMITÉ CLASSE I, DIVISION 2.
AVERTISSEMENT - RISQUE D’EXPLOSION – NE PAS DÉBRANCHER UN COMPOSANT AVANT
D’AVOIR COUPÉ L’ALIMENTATION OU D’ÊTRE EN PRÉSENCE D’UNE ZONE NON DANGEREUSE.
AVERTISSEMENT - L‘EXPOSITION À CERTAINS PRODUITS CHIMIQUES PEUVENT DÉGRADER
LES PROPRIÉTÉS D‘ÉTANCHÉITÉ DES MATÉRIAUX UTILISÉS PAR LES ÉLÉMENTS DE
COMMUTATION À L‘INTÉREUR DU DISPOSITIF.
Élément de commutation scellé: modèle ST-22 fabriqué par Seki Controls Company, Ltd.
Enveloppe de l’élément de commutation: LG Chemical LTD, de type Lupox GP2306FT-NP, Résine PBT
Epoxy de l’élément de commutation: Emerson & Coming, résine époxy de type ST 2850FT-FRJ-CA9
Nous vous recommandons de contrôler périodiquement les éléments de commutation ci-dessus
pour toute dégradation des propriétés et les remplacer s’il y a dégradation.
SELON UL 508:
MAX. TEMPÉRATURE AMBIANTE Ta= 50 °C
Warnung! Gefährliche Spannung! Installation nur durch elektrotechnische Fachkraft.
Warning! Hazardous voltage! Installation by person with electrotechnical expertise only.
Avertissement! Tension électrique dangereuse! Installation uniquement par des personnes qualifiées en électrotechnique.
¡Advertencia! ¡Tensión peligrosa! La instalación deberá ser realizada únicamente por electricistas especializados.
Avvertenza! Tensione pericolosa! Far installare solo da un elettricista specializzato.
Varning! Farlig spänning! Installation får endast utföras av en elektriker.
Oсторожно! Опасное напряжение! Монтаж должен выполняться только специалистом-электриком.
警告!危险电压!仅可由电气专业人员安装。
Betriebs- und Montageanleitung
Primär getaktete Schaltnetzteile CP-T Reihe
Hinweis: Diese Betriebs- und Montageanleitung enthält nicht sämtliche Detailinformationen zu allen Typen der Produktreihe und kann auch nicht jeden Einsatzfall
der Produkte berücksichtigen. Alle Angaben dienen ausschließlich der Produktbeschreibung und sind nicht als vertraglich vereinbarte Beschaffenheit aufzufassen.
Weiterführende Informationen und Daten erhalten Sie in den Katalogen und Datenblättern der Produkte, über die örtliche ABB-Niederlassung sowie auf der ABB
Homepage unter www.abb.com. Technische Änderungen jederzeit vorbehalten. In Zweifelsfällen gilt der deutsche Text.
Installation nur durch elektrotechnische Fachkraft. Landesspezifische Vorschriften (z.B. VDE, etc.) beachten. Vor der Installation diese Betriebs- und Montageanleitung
sorgfältig lesen und beachten. Die Geräte sind wartungsfreie Einbaugeräte.
Operating and installation instructions
Primary switch mode power supplies CP-T range
Note: These operating and installation instructions cannot claim to contain all detailed information of all types of this product range and can even not consider every
possible application of the products. All statements serve exclusively to describe the product and have not to be understood as contractually agreed characteristics.
Further information and data is obtainable from the catalogues and data sheets of this product, from the local ABB sales organisations as well as on the ABB homepage
www.abb.com. Subject to change without prior notice. The German text applies in cases of doubt.
Installation by person with electrotechnical expertise only and in accordance with the specific national regulations (e.g., VDE, etc). Before installing this unit, read these
operating and installation instructions carefully and completely. The devices are maintenance-free chassis-mounted units.
Potentiometer „OUTPUT Adj“
can withstand torque of max.
0.02 Nm / 0.18 lb.in
Sicherheits- und Warnhinweise:
Anlage freischalten!
Vor Installations-, Wartungs- oder Änderungsarbeiten: Anlage spannungsfrei schalten, vor Wiedereinschalten sichern.
Vor Inbetriebnahme:
Achtung! Unsachgemäße Installation/Betrieb kann die Sicherheit beeinträchtigen und zu Betriebsstörungen oder zur Zerstörung des Gerätes führen. Vor der
Inbetriebnahme ist Folgendes sicherzustellen:
• Netzanschluss gemäß den landesspezifischen Vorschriften durchführen
• Zuleitungen und Gerät ausreichend absichern. Eine Trenneinrichtung für das Netzteil vorsehen, um das Gerät und die Zuleitungen im Bedarfsfall zu unterbrechen
• Schutzleiter an die Klemme oanschließen (Schutzklasse I)
• Die Sekundärseite des Netzteils ist nicht geerdet. Sie kann je nach Bedarf (wahlweise L+ oder L-) vom Anwender geerdet werden.
• Ausgangsleitungen für den Ausgangsstrom des Netzteils dimensionieren und polrichtig anschließen.
• Abstände zu benachbarten Geräten beachten um eine ausreichende Kühlung zu gewährleisten
Im Betrieb:
• Keinerlei Änderungen an der Installation (primär- und sekundärseitig) vornehmen! (Starkstrom!). Gefahr von Lichtbögen und elektrischem Schlag (Lebensgefahr!)
• Verbrennungsgefahr: In Abhängigkeit der Betriebsbedingungen kann die Gehäusetemperatur hohe Werte annehmen.
• Die interne Sicherung kann vom Anwender nicht ausgetauscht werden. Löst die interne Sicherung aus, liegt mit hoher Wahrscheinlichkeit ein Gerätedefekt vor.
In diesem Fall ist eine Überprüfung des Netzteiles durch den Hersteller erforderlich.
Achtung: Hochspannung! Gespeicherte Energie! Gefährliche Energie am Ausgang!
In den Netzteilen befinden sich Bauelemente mit hoher gespeicherter Energie und Stromkreise mit Hochspannung! Deshalb keine Gegenstände in das Gerät einfüh-
ren und das Gerät nicht öffnen. Bei einigen Geräten dieser Serie kann der Ausgang gefährlich hohe Energiemengen abgeben. Sicherstellen, dass Bedienpersonal
vor versehentlicher Berührung energieführender Teile geschützt ist.
Konvektionskühlung:
Die Lüftungsöffnungen nicht bedecken! Um das Gerät herum genügend Platz zur Kühlung lassen! Siehe Fig. 1
Montage:
1. DIN-Schiene (TH 35-15 oder TH 35-7,5 nach IEC/EN 60715) wie in Abbildung 1 dargestellt auf der Montageplatte befestigen, horizontale Einbaulage, Eingangs-
klemmen unten, auf allen Seiten Mindestabstand von 25 mm zu benachbarten Geräten einhalten.
2. Gerät wie in Abbildung 2 dargestellt auf die DIN-Schiene aufschnappen.
1) Gerät leicht nach oben kippen und auf DIN-Schiene aufsetzen.
2) Bis zum Anschlag nach unten klappen.
3) Unten gegen die Vorderseite drücken, um zu verriegeln. Leicht am Gerät rütteln, um Verriegelung zu überprüfen.
3. Entfernen von der DIN-Schiene wie in Abbildung 4 dargestellt. Isolierten Schraubendreher zur Entriegelung verwenden.
Elektrischer Anschluss (siehe Abbildung 3):
Korrekte Dimensionierung, Abisolierlänge und Anschluss der Kabel sicherstellen.
Frontelemente:
Potentiometer „OUTPUT Adjust“ zum Einstellen der Ausgangsspannung.
Schalter „single/parallel“ zur Einstellung von Einzel- oder Parallelbetrieb.
Schalter „U/I mode/Hiccup mode“ zur Einstellung des Ausgangsverhaltens bei Überlast.
Meldekontakt 13-14 (Halbleiter, max. 60 V DC / 0,3 A): Geschlossen, wenn die Ausgangsspannung größer als 19,4 V ist (nur bei 24 V-Geräten).
Typ grüne LED „OK“: An grüne LED „OK“: Aus rote LED „LOW“: An rote LED „LOW“: Aus
CP-T 24/20.0 M18,92 V m 18,83 V M2,92 V M 18,82 V
CP-T 48/10.0 M38,03 V m 38,01 V M2,85 V M 37,97 V
Externer Eingangsschutz:
Die Auswahl des externen Schutzelementes muss nach den geltenden nationalen Vorschriften erfolgen. Es ist auch die Spannung zu beachten!
Empfohlener Leitungsschutzschalter, z.B. bei 3 x 400 V, ABB-Type S203-xxB (B-Characteristic) oder S203-xxC (C-Characteristic) mit Nennströmen bis max. 20 A
Technische Daten:
Daten bei Tu = 25 °C und Bemessungswerten, sofern nichts anderes angegeben ist.
Safety instructions and warnings:
Disconnect system from supply network!
Before any installation, maintenance or modification work: Disconnect the system from the supply network and protect against switching on.
Before start of operation:
Attention! Improper installation/operation may impair safety and cause operational difficulties or destruction of the unit. Before operation the following must be
ensured:
• Connect to main according to the specific national regulations.
• Power supply cables and unit must be sufficiently fused. A disconnecting device has to be provided for the end product to disengage unit and supply cables
from supply mains if required.
• The protective earth conductor must be connected to the terminal o(Protection class I)
• The secondary side of the power supply unit is not earthed and can be earthed by the user according to the needs with L+ or L-.
• Rate the output lines for the output current of the power supply and connect them with the correct polarity.
• In order to ensure sufficient air-cooling the distance to other devices has to be considered.
In operation:
• Do not modify the installation (primary and secondary side)! High current! Risk of electric arcs and electric shocks (danger to life)!
• Risk of burns: Depending on the operation conditions the enclosure can become very hot.
• The internal fuse is not user-replaceable. If the internal fuse blows, most probably the device is defective. In this case, an examination of the switch mode power
supply by the manufacturer is necessary.
Warning: High voltage! Stored energy! Energy hazard at output!
The power supplies contain components with high stored energy and circuits with high voltage! Do not introduce any objects into the unit, and do not open the unit.
With some units of this range the output is capable of providing hazardous energy. Ensure that the service personnel is protected against inadvertent contact with
parts carrying energy.
Convection cooling:
Do not cover any ventilation holes! Leave sufficient space around the unit for cooling! See Fig. 1
Mounting:
1. Fasten the DIN rail (TH 35-15 or TH 35-7,5 according to IEC/EN 60715) as shown in Fig. 1 on the mounting plate, horizontal mounting position, input terminals on
bottom, respect on all sides the minimum distance of 25 mm to other units.
2. Snap on DIN rail as shown in Fig. 2
1) Tilt the unit slightly upwards and fit the unit on the DIN rail
2) Lift it downward until it hits the stop
3) Press against the bottom front side for locking. Shake the unit slightly to check the locking
3. Remove the unit from the DIN rail as shown in Fig. 4. Use an insulated screwdriver for the unlocking.
Electrical connection (see Fig. 3):
Ensure correct dimensioning, stripping length and connection of the cables.
Front elements:
Potentiometer „OUTPUT Adjust“ for the adjustment of the output voltage.
Switch „single/parallel“ for selection of single or parallel operation.
Switch „„U/I mode/Hiccup mode“ for selection of the output behavior in case of an overload.
Signalling contact 13-14 (solid-state, max. 60 V DC / 0.3 A) is ON when the output voltage is higher than 19.4 V (on 24 V devices only).
Type green LED „OK“: ON green LED „OK“: OFF red LED „LOW“: ON red LED „LOW“: OFF
CP-T 24/20.0 M18.92 V m 18.83 V M2.92 V M 18.82 V
CP-T 48/10.0 M38.03 V m 38.01 V M2.85 V M 37.97 V
External input protection:
Observe the national regulations when selecting the external circuit breaker. Voltage also to be considered!
Recommended line protection device, e.g. with 3 x 400 V, ABB type S203-xxB (B-characteristic) or S203-xxC (C-characteristic) with rated currents of max. 20 A.
Technical data:
Data at Ta = 25 °C and rated values, unless otherwise indicated.
Input circuit CP-T 24/20.0 and CP-T 48/10.0
Rated input voltage 3 x 400-500 V AC
Input voltage range 340-575 V AC / 480-820 V DC
Frequency range 47-63 Hz
Internal input fuse 3.15 A slow-acting / 500 V AC / phase
Output circuit
Rated output voltage / power see rating label
Tolerance of the output voltage 0...+1 %
Adjustment range of the output voltage see rating label
Derating of the output current 60 °C < Ta< 70 °C see Fig. 5
Characteristic curve of output configurable, U/I characteristic curve or hiccup mode
Open-circuit protection continuous open-circuit proof
Parallel connection in order to increase power configurable, 2 devices, min. 0.1 Ir- max. 0.9 Ir
Isolation data
Rated insulation voltage input / output circuit 3 kV AC
input circut / PE 1.5 kV AC
Pollution degree 2
General data
Degree of protection housing / terminals IP20 / IP20
Ambient temperature ranges Taoperation / storage -30...+70 °C (-22...158 °F) / -40...+85 °C (-40...185 °F)
rated load -30...+60 °C (-22...140 °F)
Altitude during operation IEC/EN 60068-2-13 max. 5000 m
Dimensions (WxHxD) 150 x 131 x 118.8 mm (5.91 x 5.16 x 4.68 in)
Eingangskreis CP-T 24/20.0 und CP-T 48/10.0
Bemessungseingangsspannung 3 x 400-500 V AC
Eingangsspannungsbereich 340-575 V AC / 480-820 V DC
Frequenzbereich 47-63 Hz
Interne Eingangssicherung 3.15 A träge / 500 V AC / Phase
Ausgangskreis
Bemessungsausgangsspannung / -leistung siehe Leistungsschild
Toleranz der Ausgangsspannung 0...+1 %
Einstellbereich der Ausgangsspannung siehe Leistungsschild
Derating des Ausgangsstromes 60 °C < Tu< 70 °C siehe Fig. 5
Ausgangskennlinie konfigurierbar, Hiccup-Modus oder U/I Kennlinie
Leerlaufschutz dauerleerlauffest
Parallelschaltbarkeit zur Leistungserhöhung konfigurierbar, 2 Geräte, min. 0,1 Ir- max. 0,9 Ir
Isolationsdaten
Bemessungsisolationsspannung Ein-/ Ausgangskreis 3 kV AC
Eingangskreis / PE 1,5 kV AC
Verschmutzungsgrad 2
Allgemeine Daten
Schutzart Gehäuse / Klemmen IP20 / IP20
Umgebungstemperaturbereiche TuBetrieb / Lagerung -30...+70 °C (-22...158 °F) / -40...+85 °C (-40...185 °F)
Bemessungslast -30...+60 °C (-22...140 °F)
Betriebshöhe IEC/EN 60068-2-13 max. 5000 m
Abmessungen (BxHxT) 150 x 131 x 118,8 mm (5,91 x 5,16 x 4,68 in)

This manual suits for next models

1

Other ABB Power Supply manuals

ABB GH Q630 7043 P0001 Service manual

ABB

ABB GH Q630 7043 P0001 Service manual

ABB Infinity S User manual

ABB

ABB Infinity S User manual

ABB Infinity S J5964803 L209 User manual

ABB

ABB Infinity S J5964803 L209 User manual

ABB CPS6000 User manual

ABB

ABB CPS6000 User manual

ABB CP-E 5/3.0 User manual

ABB

ABB CP-E 5/3.0 User manual

ABB ACS880-207 User manual

ABB

ABB ACS880-207 User manual

ABB CPS6000-Systems-48V DC Power User manual

ABB

ABB CPS6000-Systems-48V DC Power User manual

ABB ProcessMaster 500 User manual

ABB

ABB ProcessMaster 500 User manual

ABB Symphony Harmony Series User manual

ABB

ABB Symphony Harmony Series User manual

ABB 4234 600 User manual

ABB

ABB 4234 600 User manual

ABB Infinity S User manual

ABB

ABB Infinity S User manual

ABB CP-ASI/2.8 User manual

ABB

ABB CP-ASI/2.8 User manual

ABB RPB 520 User manual

ABB

ABB RPB 520 User manual

ABB 4234 600 User manual

ABB

ABB 4234 600 User manual

ABB NES4812-23-AC1-PS4-DC1E-LVBD User manual

ABB

ABB NES4812-23-AC1-PS4-DC1E-LVBD User manual

ABB CPS2400U User manual

ABB

ABB CPS2400U User manual

ABB CP-E Series User manual

ABB

ABB CP-E Series User manual

ABB ODPSE230C User manual

ABB

ABB ODPSE230C User manual

ABB NES48-19-4U-AC7-PS3-DIN15B250P-LVBD-ACSPD User manual

ABB

ABB NES48-19-4U-AC7-PS3-DIN15B250P-LVBD-ACSPD User manual

ABB ACS550-01 User manual

ABB

ABB ACS550-01 User manual

ABB NES48-23-AC1-PS4-DC1E-LVBD User manual

ABB

ABB NES48-23-AC1-PS4-DC1E-LVBD User manual

ABB PCS100 UPS-I User manual

ABB

ABB PCS100 UPS-I User manual

ABB 83310-500 User manual

ABB

ABB 83310-500 User manual

ABB SV/S 30.160.1.1 User manual

ABB

ABB SV/S 30.160.1.1 User manual

Popular Power Supply manuals by other brands

Keithley Series 2200 quick start guide

Keithley

Keithley Series 2200 quick start guide

MSA PS-103 operating manual

MSA

MSA PS-103 operating manual

Accuris E2301 Series operating manual

Accuris

Accuris E2301 Series operating manual

National Instruments NI PXI-1045 user guide

National Instruments

National Instruments NI PXI-1045 user guide

Stage Zero Volta 2K user manual

Stage Zero

Stage Zero Volta 2K user manual

Bartington Magmeter-2 Operation manual

Bartington

Bartington Magmeter-2 Operation manual

Pulsar PSD15040 manual

Pulsar

Pulsar PSD15040 manual

RCF FORUM FPS9600 user manual

RCF

RCF FORUM FPS9600 user manual

Heath Heathkit IP-32 Schematic diagram

Heath

Heath Heathkit IP-32 Schematic diagram

Calira VS 50ph operating instructions

Calira

Calira VS 50ph operating instructions

Omron L user manual

Omron

Omron L user manual

EVGA SuperNOVA 650P2 PLATINUM Series manual

EVGA

EVGA SuperNOVA 650P2 PLATINUM Series manual

SonicWALL NSA 2650 installation and replacement

SonicWALL

SonicWALL NSA 2650 installation and replacement

alfatronix AD Series Operating & assembly instructions

alfatronix

alfatronix AD Series Operating & assembly instructions

AKG B23 L User instructions

AKG

AKG B23 L User instructions

AMI 4Q06125PS-430 Installation, operation and maintenance instructions

AMI

AMI 4Q06125PS-430 Installation, operation and maintenance instructions

Riden RD6006 Instruction

Riden

Riden RD6006 Instruction

HEINE EN50 Instructions for use

HEINE

HEINE EN50 Instructions for use

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.