6en | Installation Battery Lead Supervision Module
2020.03 | 10 | F.01U.036.374 Installation manual Bosch Security Systems, Inc.
4 Installation
Removing power from the FACP
Caution!
Before installing the module in an existing system, inform the Central Station and the Local
Authority and disconnect all power to the control panel.
Remove AC power from the system at the dedicated 120VAC breaker and remove the standby
battery power before making or removing any connections to the FACP.
Mounting the module in the FACP enclosure
The module mounts to the side of the enclosure using the supplied plastic standoffs and
screws.
A snap track is included for enclosures that do not have a three‑hole mounting pattern on the
interior side walls. To mount the snap track, remove the backing from the tape, line the
hole(s) in the snap track up with the existing hole(s) in the enclosure, and firmly press it onto
the side of the enclosure. After mounting the snap track, secure it to the enclosure with at
least one screw and nut. Then mount the module to the snap track.
Wiring the module to the FACP
Caution!
Do not cross polarity. Red wires connect to the positive battery terminals. Black wires
connect to the negative battery terminals.
Use the following procedure when wiring the module to a FACP:
1. Connect the RED wire lead provided with the module to the positive (+) battery terminal
on the FACP.
2. Connect the other end of the RED wire lead to Terminal1 (CHRG+) on the module.
3. Connect the BLACK wire lead provided with the module to the negative (-) battery
terminal on the FACP.
4. Connect the other end of the BLACK wire lead to Terminal4 (CHRG-) on the module.
5. Connect the GREEN wire lead provided with the module to the zone or point input with
the EOL resistor on the FACP.
6. Connect the other end of the GREEN wire lead to Terminal2 (SUPV) on the module.
7. Connect the ORANGE wire lead provided with the module to the auxiliary power positive
terminal on the FACP or the auxiliary power supply.
8. Connect the other end of the ORANGE wire to Terminal3 (VAUX+) on the module.