_______________________________________________________________________________________________________________________________
European SafetySystemsLtd. Impress House,Mansell Road, Acton,London W37QHsales@e2s.com Tel:+44 (0)20 87438880
www.e2s.com Fax: +44(0)2087404200
DocumentNo.IS5001 IssueD11-09-07Sheet 2of 6
3) Theequipmentisonlycertifiedforuseinambient
temperaturesintherange-40oCto+60oCand
shouldnotbeusedoutsidethisrange.
4) Thecertificatenumberhasan ‘X’suffix,which
indicatesthatthecertificatecontainsoneofmore
specialconditionsforsafeuse.Thoseinstalling or
inspectingtheequipmentshouldrefertothissection
ofthecertificate.
5) Theequipmenthasnotbeenassessedasasafety-
relateddevice(asreferredtobyDirective94/9/EC
AnnexII,clause1.5).
6) Installation ofthisequipmentshallbecarriedout by
suitably-trainedpersonnelinaccordancewiththe
applicablecodeof practice.
7) Repairofthisequipment shall onlybecarriedoutby
themanufacturerorinaccordancewiththe
applicablecodeof practice.
8) Thecertificationofthisequipmentreliesonthe
followingmaterialsusedinitsconstruction:
Enclosure: ABS Plastic
Iftheequipmentislikelytocomeintocontact with
aggressivesubstances,thenitistheresponsibilityof
theusertotakesuitableprecautionsthat prevent it
frombeing adverselyaffected,thusensuringthatthe
typeofprotectionisnotcompromised.
“Aggressivesubstances”-e.g. acidicliquidsor
gasesthat mayattackmetals,orsolventsthat may
affectpolymericmaterials.
“Suitableprecautions”-e.g. regularchecksaspart
ofroutineinspectionsorestablishingfromthe
material’sdatasheet thatitisresistanttospecific
chemicals.
SPECIALCONDITIONSFORSAFEUSE (as statedinthe
ECTypeExamination CertificateSIRA 05ATEX2084X)
ConditionsforIS-mAl Sounder
Theequipmenthasaningress protection rating ofIP65.
However,if ithasbeensuppliedwithoutcableentrydevices,
thentheusershall ensurethatthedevicesthatarefittedwill
providean ingress protectionthatisappropriatetothe
environmentinwhichitisinstalledi.e.IP20 orbetter.If only
oneofthetwocableentriesareused,thentheunusedentry
'knockout'shall beleft intactorfittedwithablanking device
thatensuresingress protectionappropriatetothe
environmentinwhichitisinstalledi.e.IP20orbetter.
Thetotalcapacitanceconnectedtoterminals+wrt-(i.e.the
capacitanceofthecableplusanyothercapacitance)shall
not exceed83nF.
Theequipmentshallnotbedirectlyinstalledinanyprocess
whereitsenclosuremight beelectro-staticallychargedbythe
rapidflowofanon-conductivemedia.
TheequipmentshallonlybesuppliedviaTerminals+w.r.t.
Terminals-fromabarrierhavingamaximumopencircuit
voltageUothatis< 28Vand amaximumshortcircuitcurrent
Iothatis< 93mA,whereIoisresistivelylimited.Thebarrier
shallbeATEX certifiedbyanotifiedbody.
4.2Zones, GasGroupsandTemperatureClassification
TheIS-mA1minialarmsounderhasbeencertifiedEExiaIIC
T4.Whenconnectedtoanapprovedsystemitmaybe
installedin:
Zone0explosivegasairmixture
continuouslypresent.
Zone1explosivegasairmixturelikelytooccurin
normaloperation.
Zone2explosivegasairmixturenotlikelytooccur,
andif itdoes,it willonlyexistforashort time.
Beusedwithgasesingroups:
Group Apropane
Group Bethylene
Group Chydrogen
Havingatemperatureclassification of:
T1 450ºC
T2 300ºC
T3 200ºC
T4 135ºC
4.3Terminals+and-
Powerissuppliedtothesounderviathe+and terminals
whichhavethefollowinginputsafetyparameters:
Ui = 28V
Ii = 93mA
Pi =660mW
Ci=0Li=0
TheIS-mA1soundermaybepoweredfroman ATEX certified
Zenerbarrierorgalvanicisolatorwhichhaveoutput
parametersequaltoorless than28V,93mAand 660mW,
whereIoisresistivelylimited.Thecableparametersstated
ontheselectedZenerbarrierorgalvanicisolatorcertificate
must beobserved.
Uptothree IS-mA1sounderscanbeconnectedinparallel
andpoweredfromacommonbarrierorisolator.Connecting
twosoundersinparallelwillreducetheoutputfromeachby
about3dB.Three soundersshouldonlybepoweredfroma
commonsupplywhenthemaximumsupplyvoltageis
available.
4.4TerminalsS2andS3
WhenterminalsS2orS3areconnectedto0V(-terminal)the
sounderoutputtonechangestothesecondorthirdstage
alarmrespectively.Theinputsafetyparametersforthese
terminalsare:
Ui = 28V
Ii = 0mA
Becausethepermittedinputcurrentiszero,theseterminals
mayonlybeconnectedtoadiodereturnbarrier,an
intrinsicallysaferelayoragalvanicisolator,allofwhichmust
havebeencertifiedbyan ECNotifiedBody.Onlydiodereturn
barrierswithavoltagedrop ofless than0.9Vmaybeused.
Alternatively,theseterminalsmaybeconnecteddirectlytoa
mechanicallyactivatedswitchwithinthehazardousarea.