E2S D1xS2FDC024-D User manual

INSTRUCTION MANUAL
D1xS2
Alarm Horn Sounder
Class II/III, Zone 20
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-151-IS
Issue 1
03-02-2022
Sheet 1 of 7
D1xS2F
D1xS2H
1) Product Table
Unit Type Code
Nominal
Input Voltage
Nominal
Current P2
Nominal
Current P3
Voltage Range
Sound
Pressure Level
dB(A)
Max*
P2/P3
Nom.†
P2/P3
D1xS2FDC024-D
12Vdc
289mA
356mA
11.5-54Vdc
103/106
98/102
24Vdc
324mA
740mA
48Vdc
195mA
391mA
D1xS2FAC230-D
115Vac
125mA
282mA
100-240Vac 50/60Hz
230Vac
78mA
167mA
D1xS2HDC024-D
12Vdc
289mA
356mA
11.5-54Vdc
106/109
103/105
24Vdc
324mA
740mA
48Vdc
195mA
391mA
D1xS2HAC230-D
115Vac
125mA
282mA
100-240Vac 50/60Hz
230Vac
78mA
167mA
*Max = Tone 4
Nom. = Tone 44
The table shows the input current taken by the various sounders.
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage.
Nominal current at nominal voltage.
Table 1: Electrical Ratings.
2) Warnings
CAUTION
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS
ATMOSPHERES:
DISCONNECT FROM SUPPLY BEFORE OPENING.
KEEP TIGHTLY CLOSED WHEN IN OPERATION.
WARNING
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES
FROM ENCLOSURE.
EQUIPMENT MUST NOT BEINSTALLED WITHTHE HORN FACING
UPWARDS OF HORIZONTAL
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS
PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING HAZARD - CLEAN
ONLY WITH A DAMP CLOTH
ATEX/IECEx INSTALLATIONS: IF TEMPERATURE EXCEEDS 70°C
AT ENTRY OR 80°C AT BRANCHING POINT USE SUITABLE
RATED CABLE AND GLANDS
ATTENTION
ATMOSPHÈRES DANGEREUSES :
COUPER L 'ALIMENTATION AVANT OUVERTURE.
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT.
AVERTISSEMENT
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES.
ÉQUIPEMENT NE DOIT PAS ETRE INSTALLE AVEC LE KLAXON
TOURNEE VERS LE HAUT DE HORIZONTAL.
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
ATEX/IECEx INSTALLATIONS : SI LA TEMPÉRATURE DÉPASSE
70 °C À L'ENTRÉE OU 80 °C AU POINT DE BRANCHEMENT,
UTILISER UN CÂBLE ET DES JOINTS D'ÉTANCHÉITÉ
APPROPRIÉS

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-151-IS
Issue 1
03-02-2022
Sheet 2 of 7
3) Marking & Rating Information
The D1xS2 Alarm Horns comply with the following standards for
hazardous locations:
3.1 Class/Division Ratings for US & Canada
Standards
Class I UL 1203 & CSA C22.2 No 25-1966
Class Division Ratings for US (NEC)
Model No:
Rating
D1xS2-DC024-D /
D1xS2-AC230-D
Class Division Ratings for Canada (CEC)
Model No:
Rating
D1xS2-DC024-D
D1xS2-AC230-D
Class Zone Ratings for US (NEC)
Model No:
Rating
D1xS2-DC024-D /
D1xS2-AC230-D
Class Zone Ratings for Canada (CEC)
Model No:
Rating
D1xS2-DC024-D
D1xS2-AC230-D
Ambient Temperature Range
IP Rating
IP66 to EN60529
4) Special Conditions for Safe Use
To access the Ex d chamber, loosen the M4 grub screw on the
sounder cover. Open the enclosure by turning the sounder cover
counterclockwise and remove the cover.
Electrical connections are to be made into the terminal blocks on the
PCBA, using solid wire 0.5-4mm2 / AWG 20-12 or stranded wire,
sizes 0.5-2.5mm2 / AWG 24-14. Wire insulation needs to be stripped
8mm. Wires may be fitted securely with crimped ferrules. Terminal
screws need to be tightened down with a tightening torque of 0.45
Nm / 3.5 Lb-in.
Internal earthing connections should be made to the Internal Earth
terminal in the base of the housing using a ring crimp terminal to
secure the earth conductor under the earth clamp. The earth
conductor should be at least equal in size and rating to the incoming
power conductors but at least a mini mum of 0.82mm2 / 18AWG in
size.
External earthing connections should be made to the M5 earth stud,
using a ring crimp terminal to secure the earth
conductor to the earth stud. The external earth conductor should be
at least 4mm2 in size.
On completion of the installation the flameproof threaded joint should
be inspected to ensure that they are clean and that they have not
been damaged during installation.
Ensure the O-ring seal is in place and undamaged.
When fitting the flameproof cover ensure the thread is engaged
correctly. Fully tighten the cover all the way, ensure no gap is visible
between the cover and base of the sounder enclosure.
The cable entries have two M20 x 1.5 6H entry thread and a single
cable glands, only
suitably rated and certified cable glands must be used. They must be
suitable for the type of cable being used and also meet the
requirements of the current installation standards EN 60079-14 /
IEC60079-14.
If the installation is made using conduit, openings must have a
Any unused cable entries must be closed with suitably rated and
certified blanking plugs.
The plastic horn is not anti-static and the metallic enclosure has a
non-conductive coating. These may generate an ignition-capable
level of electrostatic charges under certain extreme conditions. The
user should ensure that the equipment is not installed in a location
where it may be subjected to external conditions that might cause a
build-up of electrostatic charges on non-conducting surfaces.
Repair of the flameproof threaded joints and cemented joints is not
permitted.

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-151-IS
Issue 1
03-02-2022
Sheet 3 of 7
5) Product Mounting and Access
5.1 Mounting
Fig 1: Mounting Locations
5.2 Installation procedure
a. Secure the D1x unit to a flat surface via the three 7mm
fixing holes in the mounting bracket.
b. Remove the explosionproof cover of the alarm horn by
unscrewing it, taking care not to damage the
explosionproofthreads in the process (Refer tosection 5).
c. Fit an M20/NPT suitably rated cable gland or conduit entry
into the hole in the enclosure and connect the field wiring
to the appropriate alarm horn terminals as shown in fig. 6
(AC) or fig 8. (DC). The power supply terminals are
duplicated so that units may be connected in parallel. An
end of line monitoring resistor may be fitted to DC units
only (see section 12). If the second and third M20/NPT
entries are not used, suitably rated stopping plugs must
always be fitted.
d. Replace the explosionproof cover of the loudspeaker,
taking care not to damage the explosionproof threads.
Tighten fully.
5.3 Hornless Variants
6.4 Access to the Explosionproof Enclosure
Fig 2: Accessing the enclosure
6) Installation Requirements
6.1 Safe Installation Requirements
Warning High voltage may be present,
risk of electric shock.
DO NOT open when energised,
disconnect power before opening.
The sounder must only be installed by suitably qualified personnel in
accordance with the latest issues of the relevant standards.
6.2 Cable Selection and Connections
When selectingthe cablesize, consideration must be given to the input
current that each unit draws (see table 1), the number of sounders on
the line and the length of the cable runs. The cable size selected must
have the necessary capacity to provide the input current to all the
sounders connected to the line.
AC: 1.0 - 2.5mm2/ AWG18 - AWG12
DC: 0.2 - 2.5mm2/ AWG24 - AWG12
Figure 3: Wire Preparation.
When connecting wires to the terminals great care should be taken to
dress the wires so that when the cover is inserted into the chamber
the wires do not exert excess pressure on the terminal blocks. This is
particularly important when using cables with large cross-sectional
areas such as 2.5mm².
6.3 Earthing
Internal Earth
Marked with G
External Earth
D1xS2F
D1xS2H

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-151-IS
Issue 1
03-02-2022
Sheet 4 of 7
6.4 Cable Glands, Blanking Elements & Adapters
Ingress Protection
Adapters
The GNEx sounder range can be supplied with the following types of
adapters:
M20 to M25
It is important to note that stopping plugs cannot be fitted onto
adapters, only directly onto the M20 entries.
Any other adapters used must be suitably rated and certified.
If the installationis made usingconduit, openings must have a sealing
fitting connected as close as practical to the wall of the enclosure, but
in no case more than the size of the conduit or 50mm, whichever is
the lesser.
7) Settings
Following illustrations show the settings available for D1xS2 Alarm
Horn Sounders. See schematic diagram D190-06-001 for details.
7.1 SPL Configuration
See Table 1 for product power supply and Sound Pressure Levels
(SPL).
Configuration for DC Units
Figure 4: DC PCBA.
Configuration for AC Units
Figure 5: AC PCBA .
7.2 Stage Switching Polarity (DC Units)
Switching from positive switching (default) to negative switching - DC
Only.
NOTE: Max supply is 33V DC if higher DC voltage is required, use
Negative switching.
Figure 6: Stage Switching Polarity.
(default)
(default)

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-151-IS
Issue 1
03-02-2022
Sheet 5 of 7
7.3 Tone Selection
The D1x Alarm Horn Sounders have 64 different tones that can be
selected independently for the first and second stage alarms. The
tones are selected by operation of the tone setting DIP switch 1 & DIP
2witch 2 (see figures 6 and 7) on the PCB, for stage 1 and stage 2
respectively.
Default = Switch 2
S2 - Tone 1
0 0 0 0 0 0
Default = Switch 1
S1 – Tone 44
1 1 0 1 0 1
(ON = 1, OFF = 0)
Figure 7: DIP switch configuration
The sounder can also be switched to sound the third and fourth stage
alarm tones.
The tone table (D221-95-001-IS) shows the switch positions for the 64
tones on first and second stages and which tones are available for the
third and fourth stages dependent on the Stage 1 DIP switch setting.
Following table (Table 3) is a summary of DC: D190-06-001; AC:
D190-06-005 wiring options.
Config.
Voltage
Configuration Description
Features
Product
Option
Identifier
1a
DC
Single Stage Configuration
•Line monitoring
•Positive Switching
1
1b
DC
Two Stage Configuration
•Common Negative
•Positive Switching
1
1c
DC
Three/Four Stage Configuration
•Common Negative
•Positive Switching
1
2
DC
Three/Four Stages. Voltage Free 2nd, 3rd &
4th Stage Activation Configuration
•Common Positive
•
Customer Set H1 & H2 to Negative
Switching
1
3
DC
Two Stage Configuration
•Independent Stage Input
•Reverse Polarity Stage Monitoring
1
4
DC
Two Stage Configuration
•Line Stage Monitoring (Use suitable
monitoring relays/ modules)
•Not to be used in reverse polarity
monitoring
Y
5
DC
Two/Three Stage Voltage Free Activation
Configuration
K
6
DC
Three/Four Stage Configuration
•Independent Stage Input
•Line Stage Monitoring (Use suitable
monitoring relays/ modules)
•Positive Switching (Default)
V
1a
AC
Single Stage Configuration
1
1b
AC
Three/Four Stage Configuration
1
2
AC
Two/Three Stage Voltage Free Activation
Configuration
K
Table 3: Summary of Wiring Options. See Document D190-06-001 for DC Schematic Diagrams; D190-06-005 for AC Schematic
Diagrams.
This manual suits for next models
3
Other E2S Marine Equipment manuals

E2S
E2S D105 AlertAlarm User manual

E2S
E2S SONF1DC024 X Y Series User manual

E2S
E2S Minialert IS-mC1 User manual

E2S
E2S E2XS112UL User manual

E2S
E2S E2xS121EG Troubleshooting guide

E2S
E2S BExS110D-R User manual

E2S
E2S AL121H Series User manual

E2S
E2S BExCS110-L1 User manual

E2S
E2S AlertAlarm A105N User manual

E2S
E2S D1xS1 Series User manual