EVCOS.p.A.|EV3H94|Instructionsheetver.1.0|Code1043H94E104|Page4of5|PT05/21
No. PAR. DEF. ALARMS MIN... MAX.
42
A0
0
select value for low temper-
ature alarm
0 = DHW tank upper tempera-
ture
1 = DHW tank lower tempera-
ture
2 = evaporator temperature
43 A1 10.0
low temperature alarm
threshold 0... 50 °C/°F
44
A2
0
low temperature alarm type
0 = disabled
1 = absolute
45
A3
0
select value for high tem-
perature alarm
0 = DHW tank upper tempera-
ture
1 = DHW tank lower tempera-
ture
2 = evaporator temperature
46
A4
90.0
high temperature alarm
threshold
0... 199 °C/°F
default 75.0 in
EV3H94N9PXRX01 and
EV3H94N9VXRX01
47
A5
0
high temperature alarm type
0 = disabled
1 = absolute
48
A6
120
high temperature alarm de-
lay from power-on 0... 240 min
49
A7
15
high/low temperature alarm
delay 0... 240 min
50
A10
120
power failure duration for
alarm recording 0... 240 min
51
A11
2.0
high/low temperature alarm
reset differential 1... 30 °C/°F
No. PAR. DEF. FAN MIN... MAX.
52 F0 1 enable fan 0 = no 1 = yes
No. PAR. DEF. ANTI-LEGIONELLA MIN... MAX.
53
H0
30
anti-legionella interval
0... 99 d (days)
0 = none
54 H1 70.0
anti-legionella thermal
threshold 10... 199 °C/°F
55
H3
2
anti-legionella thermal
threshold maintenance dura-
tion
0... 240 min
0 = function disabled
No. PAR. DEF. DIGITAL INPUTS MIN... MAX.
56
i0
0
multi-purpose input function
0 = disabled
1 = pressure switch
2 = green
57
i2
0
compressor-on delay from
pressure switch alarm reset 0... 120 min
58 i3 0 enable photovoltaic system 0 = no 1 = yes
59
i4
1
photovoltaic system input
activation 0 = with contact closed
1 = with contact open
60
i5
1
high pressure input activa-
tion
0 = with contact closed
1 = with contact open
61
i8
3
number of pressure switch
alarms for unit blocked
alarm
0... 15
0 = disabled
62
i9
240
counter reset time for pres-
sure switch alarms 1... 999 min
63
i10
24
pressure switch alarm delay
from compressor-on 0... 240 sx10
64
i11
60
time pre opening hot gas
defrost valve 0... 240 s
65
i12
0
fan off during pressure
switch/unit blocked alarm
0 = no 1 = yes
default 1 in
EV3H94N9PXRX01 and
EV3H94N9VXRX01
No. PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
66
u0
1
enable relay K2 and relay K4
inversion 0 = no (defrost on K2)
1 = yes (defrost on K4)
67 u9 1 enable alarm buzzer 0 = no 1 = yes
N. PAR. DEF. CLOCK MIN... MAX.
68 Hr0 1 enable clock 0 = no 1 = yes
69
Hd1
1
time for switch on on Mon-
day 1 = with On1 e OF1
2 = with On2 e OF2
70
Hd2
1
time for switch on on Tues-
day 1 = with On1 e OF1
2 = with On2 e OF2
71
Hd3
1
time for switch on on
Wednesday 1 = with On1 e OF1
2 = with On2 e OF2
72
Hd4
1
time for switch on on Thurs-
day 1 = with On1 e OF1
2 = with On2 e OF2
73
Hd5
1
time for switch on on Friday
1 = with On1 e OF1
2 = with On2 e OF2
74
Hd6
2
time for switch on on Satur-
day 1 = with On1 e OF1
2 = with On2 e OF2
75
Hd7
2
time for switch on on Sun-
day 1 = with On1 e OF1
2 = with On2 e OF2
76
HOn1
- - -
time for time band 1 on
00:00... 23:59 h:min
00:00 = disabled
77
HOF1
- - -
time for time band 1 off
00:00... 23:59 h:min
00:00 = disabled
78
HOn2
- - -
time for time band 2 on
00:00... 23:59 h:min
00:00 = disabled
79
HOF2
- - -
time for time band 2 off
00:00... 23:59 h:min
00:00 = disabled
80
Ant
- - -
time antilegionella on
00:00... 23:59 h:min
00:00 = disabled
N. PAR. DEF. SAFETIES MIN... MAX.
81 PA1 426 level 1 password -99... 999
82 PA2 824 level 2 password -99... 999
N. PAR. DEF. DATA-LOGGING EVLINK MIN... MAX.
83
bLE
1
enable Bluetooth
0 = no 1 = sì
>1 reserved
84
rE0
15
data-logger sampling inter-
val 0... 240 min
85
rE1
1
recorded temperature
0 = nessuna
1 = DHW tank upper
2 = DHW tank lower
3 = evaporator
4 = DHW tank upper and lower
5 = tutte
N. PAR. DEF. MODBUS MIN... MAX.
86 LA 247 MODBUS address 1... 247
87
Lb
2
MODBUS baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
88
LP
2
parity
0 = none 1 = odd
2 = even
9 ALARMS
CODE
DESCRIPTION RESET TO CORRECT
Pr1
DHW tank upper probe
alarm automatic
- check P0
- check probe integrity
- check electrical connection
Pr2
DHW tank lower probe
alarm automatic
Pr3 evaporator probe alarm automatic
rtc clock alarm manual set date, time and day of the week
AL low temperature alarm automatic check A0, A1 and A2
AH high temperature alarm automatic check A3, A4 and A5
PF
power failure alarm
manual
- touch a key
- check electrical connection
LHP
pressure switch/unit
blocked alarm automatic/
manual - switch the device off and on
- check i0, i8 and i9
HP
high pressure alarm
manual
- switch the device off and on
- check P3
FiL
compressor maintenance
alarm
automatic
check C10
by silencing the buzzer you delete the
compressor functioning hours
UtL
evaporator failure alarm
manual
- switch the device off and on
- check SPA and C14
10 TECHNICAL SPECIFICATIONS
Purpose of the control device function controller
Construction of the control device built-in electronic device
Container black, self-extinguishing.
Category of heat and fire resistance D.
Measurements
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x 2
5/16 in) with fixed screw terminal blocks 75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
3 3/16 in) with plug-in screw terminal blocks
Mounting methods for the control device
to be fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the covering IP65 (front)
Connection method
fixed screw terminal blocks for wires up to 2.5
mm² plug-in screw terminal blocks for wires up to
2.5 mm² (on request).
Maximum permitted length for connection cables
power supply: 10 m (32.8 ft) analogue inputs: 10 m (32.8 ft)
digital inputs: 10 m (32.8 ft) digital outputs: 10 m (32.8 ft).
Operating temperature From 0 to 55 °C (from 32 to 131 °F)
Storage temperature from -25 to 70 °C (from -13 to 158 °F)
Operating humidity
relative humidity without condensate from
10 to 90%
Pollution status of the control device 2.
Compliance:
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH (EC) Regulation no.
1907/2006
EMC 2014/30/EU LVD 2014/35/EU
Classification of the control device according
to protection from electrical shock class II according to standard EMC EN
60730-1 §2.7.5.
Power supply
115... 230 VAC (+10% -15%), 50/60 Hz (±3
Hz), max. 3.2 VA insulated
Earthing methods for the control device none
Rated impulse-withstand voltage 2.5 KV
Over-voltage category II.
Software class and structure A.
Analogue inputs
2 for PTC, NTC or Pt 1000 probes (DHW tank
upper probe and evaporator probe)
PTC probes Sensor type: KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field: from -50 to 150 °C (from -58 to 302 °F)
Resolution: 0.1 °C (1 °F).
NTC probes Sensor type: ß3435 (10 K@ 25 °C, 77 °F)
Measurement field: from -40 to 105 °C (from -40 to 221 °F)
Resolution: 0.1 °C (1 °F).