manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Evco
  6. •
  7. Controllers
  8. •
  9. Evco EVBOX Light JS200 User manual

Evco EVBOX Light JS200 User manual

EVCO S.p.A. | EVBOX Light JS200 | Instruction sheet ver. 1.0 | Code 104LJS200E103 | Page 1 of 3 | PT 48/17
EVBOX Light JS200 Control solutions for cold rooms with
remote moto-condensing unit
EN
ENGLISH
- Degree of protection IP65.
- Power supply 115... 230 VAC.
- Cabinet probe and evaporator probe (PTC/NTC).
- Door switch input.
- Compressor relay 30 A res. @ 250VAC.
- Alarm buzzer.
- TTL MODBUS slave port for EVconnect app, EPoCA remote monitoring system or for
BMS.
- Direct connection to the load.
1 MEASUREMENTS AND INSTALLATION | Measurements in mm (inches)
1.1 User interface
To be fitted on-board, fixing screws not provided.
N.B.
To ensure the degree of protection IP65 of the whole covering, install the device
using the appropriate holes only.
1. If the connecting cables come from above, drill a hole having a diameter suitable the
cables to pass on the upper part of the container using the proper drilling lead (5); if
vice versa the cables come from below, drill the hole on the lower part of the container.
The maximum diameter of the hole must be 14.0 mm (9/16 in).
2. Make sure the gasket (2) is into the proper seat.
3. If the connecting cables come from above, fasten the container against the wall with 2
screws (1) using the proper holes on the lower part of the container (3); if vice versa
the cables come from below, fasten the container using the holes on the upper part.
Use cylindrical head screw.
4. Screw the junction for rigid tube (9) to the cover cap (10).
5. Connect the user interface (11) to the control module as shown in the section
ELECTRICAL CONNECTION getting the cables to pass through the proper hole (5) and
through the junction for rigid tube (9).
6. Fasten the user interface (11) pushing it from the front into the proper seat (6).
7. Make sure the gaskets (4) are into the proper seats.
8. Fasten the cover caps (10) and (12) on the upper part and on the lower part of the
container.
9. Fasten the container against the wall with 2 screws (1) using the proper holes (7) on
the cover cap (10).
10. Fasten the coverscrew caps (8) into the proper holes (7) of the cover cap (10).
1.2 Control module
To be fitted on a DIN rail, in a control panel.
INSTALLATION PRECAUTIONS
- Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
- Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
- Any metal parts close to the control module must be far enough away so as not to
compromise the safety distance.
- In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
N.B.
- Use cables of an adequate section for the current running through them.
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- If using an electrical or pneumatic screwdriver, adjust the tightening torque.
- If the device has been moved from a cold to a warm place, the humidity may have
caused condensat. to form inside. Wait about an hour before switching on the power.
- Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS.
- Disconnect the power supply before doing any type of maintenance.
- Do not use the device as safety device.
- For repairs and for further information, contact the EVCO sales network.
3 FIRST-TIME USE
1. Install following the instructions given in the section MEASUREMENTS AND
INSTALLATION.
2. Connect the user interface to the control module as shown in the section ELECTRICAL
CONNECTION without powering up the device.
3. Power up the device and an internal test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
4. Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use.
PAR.
DEF.
PARAMETER
MIN... MAX.
SP 0.0 setpoint r1... r2
P0 1 probe type 0 = PTC 1 = NTC
P2 0 temperature unit of measurement 0 = °C 1 = °F
d1
0
defrost type
0 = electric 1 = hot gas
2 = compressor stopped
Then check that the remaining settings are appropriate; see the section
CONFIGURATION PARAMETERS.
5. Disconnect the device from the mains.
6. Make the electrical connection as shown in the section ELECTRICAL CONNECTION
without powering up the device.
7. For the connection in an RS-485 network connect the interface EVIF22TSX or
EVIF23TSX, to activate real time functions connect the module EVIF23TSX, to use the
device with the EPoCA remote monitoring system, connect the EVIF25TWX module, to
use the device with the Android APP EVconnect connect the interface EVIF25TBX
(EVlink); see the relevant instruction sheets. If EVIF22TSX or EVIF23TSX is used,
set parameter bLE to 0.
8. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on and off
1.
If POF = 1 (default), touch the ON/STAND-BY key for 2s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED
ON
OFF
FLASHING
compressor on
compressor off
- compressor protection active
- setpoint being set
evaporator fan on
evaporator fan off
evaporator fan stop active
cabinet light on
cabinet light off
cabinet light on by digital input
AUX 1
auxiliary function 1 on
auxiliary function 1 off
- auxiliary function 1 on by digital
input
- auxiliary function 1 delay active
AUX 2
auxiliary function 2 on
auxiliary function 2 off
- auxiliary function 2 on by digital
input
- auxiliary function 2 delay active
defrost or pre-drip
active
-
- defrost delay active
- dripping active
- energy saving active
- low consumption
active
-
-
view time
-
set date, time and day of the
current week
view temperature
-
quick cooling active
HACCP
saved HACCP alarm
-
new HACCP alarm saved
alarm active
-
-
If Loc = 1 (default) and 30s have elapsed without the keys being pressed, the display will show
the “Loc” label and the keypad will lock automatically.
4.2 Unlock keypad
Touch a key for 1s: the display will show the label “UnL”.
4.3 Set the setpoint (if r3 = 0, default)
Check that the keypad isn’t locked.
1.
Touch the SET key.
2.
Touch the UP or DOWN key within 15s to set the value within the
limits r1 and r2 (default “-40... 50”)
3.
Touch the SET key (or do not operate for 15s).
4.4 Activate manual defrost
Check that the keypad isn’t locked and that quick cooling isn’t active.
1.
Touch the DEFROST key for 2s.
If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.5 Cabinet light on/off (if u1 or u11 = 0, default)
1.
Touch the CABINET LIGHT key.
4.6 Button-operated load on/off (if u1 or u11 = 2)
1. Touch the CABINET LIGHT key (for 2s if u1 or u11 = 0=).
If u1 or u11 = 1, the demisting switch on for the u6 duration.
4.7 Silence buzzer (if u9 = 1, default)
Touch a key.
If u1 or u11 = 3 and u4 = 1, the alarm output is deactivated.
5 ADDITIONAL FUNCTIONS
5.1 Activate/deactivate overcooling
Check that the keypad isn’t locked and that defrosting isn’t active.
1.
Touch the UP key for 2s.
The setpoint becomes “setpoint - r6”, for the r7 duration.
5.2 Activate/deactivate energy saving in manual mode
Check that the keypad isn’t locked.
1.
Touch the DEFROST key.
The setpoint becomes “setpoint + r4”, at maximum for HE2 duration.
5.3 Activate the high or low humidity functions (if F0 = 5)
Check that the keypad isn’t locked.
1.
Touch the DOWN key for 1s.
2.
Touch the UP or DOWN key within 15s to select the label “rH”.
3. Touch the SET key for 2s until the display shows the right label
for the function (only touch the key to see the function
activated).
LAB.
DESCRIPTION
rhL
low humidity function (evaporator fan with F17 and F18 if the compressor is
off, on if the compressor is on)
rhH
high humidity function (evaporator fan on)
4.
Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
EVCO S.p.A. | EVBOX Light JS200 | Instruction sheet ver. 1.0 | Code 104LJS200E103 | Page 2 of 3 | PT 48/17
5.4 View/delete compressor functioning hours
Check that the keypad isn’t locked.
1.
Touch the DOWN key for 1s.
2.
Touch the UP or DOWN key within 15s to select a label.
LAB.
DESCRIPTION
CH1
view compressor functioning hundreds of hours
CH2 view second compressor functioning hundreds of hours (if u1 oru11 = 7)
rCH delete compressor and second compressor functioning hours
3. Touch the SET key.
4.
Touch the UP or DOWN key to set “149” (to select rCH).
5.
Touch the SET key.
6.
Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
5.5 View the temperature detected by the probes
Check that the keypad isn’t locked.
1.
Touch the DOWN key for 1s.
2.
Touch the UP or DOWN key within 15s to select a label.
LAB.
DESCRIPTION
Pb1 cabinet temperature (if P4 = 0, 1 or 2)
inlet air temperature (if P4 = 3)
Pb2
evaporator temperature (if P3 = 1 or 2)
Pb3
auxiliary temperature (if P4 = 1, 2 or 3)
Pb4 calculated product temperature (CPT; if P4 = 3)
3. Touch the SET key.
4.
Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1.
Touch the SET key for 4s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set the PAS value
(default “-19”).
4.
Touch the SET key (or do not operate for 15s): the display will
show the label “SP”.
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15s to set the value.
8.
Touch the SET key (or do not operate for 15s).
9.
Touch the SET key for 4s (or do not operate for 60s) to exit the
procedure.
6.2 Set the date, time and day of the week (available with interface EVIF25TBX or
EVIF25TWX connected)
N.B.
- If the device is connected to the interface EVIF25TBX, do not disconnect the device
from the mains within two minutes since the setting of the time and day of the
week.
- if the device communicates with the EVconnect app, the date, time and day of the
week will be automatically set by the smartphone or tablet.
Check that the keypad isn’t locked.
1.
Touch the DOWN key for 1s.
2.
Touch the UP or DOWN key within 15s to select the label “rtc”.
3.
Touch the SET key: the display will show the label “y” followed
by the last two figures of the year.
4.
Touch the UP or DOWN key within 15s to set the year.
5. Repeat actions 3 and 4 to set the next labels.
LAB.
MEANING OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h time (00… 23)
n
minutes (00… 59)
6.
Touch the SET key: the display will show the label for the day of
the week.
7.
Touch the UP or DOWN key within 15s to set the day of the
week.
LAB.
DESCRIPTION
Mon Monday
tuE Tuesday
UEd Wednesday
thu
Thursday
Fri Friday
Sat Saturday
Sun Sunday
8. Touch the SET key: the device will exit the procedure.
9.
Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3 Reset the factory settings
N.B.
Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
1.
Touch the SET key for 4s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set “149”.
4.
Touch the SET key (or do not operate for 15s): the display will
show the label “dEF”.
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15s to set “1”.
7.
Touch the SET key (or do not operate for 15s).
8. Interrupt the power supply to the device.
9. Touch the SET key for 2s before action 6 to exit the procedure
beforehand.
7 CONFIGURATION PARAMETERS
N. PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2
CA1
0.0
cabinet probe offset
-25... 25 °C/°F
if P4 = 3, air in probe offset
3 CA2 0.0 evaporator probe offset -25... 25 °C/°F
4 CA3 0.0 auxiliary probe offset -25... 25 °C/°F
5 P0 1 probe type 0 = PTC 1 = NTC
6 P1 1 enable °C decimal point 0 = no 1 = yes
7
P2
0
temperature unit of
measurement 0 = °C 1 = °F
8
P3
1
evaporator probe function
0 = disabled
1 = defrost + fan
2 = fan
9
P4
0
configurable input function
0 = digital input
1 = condenser probe
2 =
critical temperature probe
3 = air out probe
if P4 = 3, regulation temperature
= product temperature (CPT)
10
P5
0
value displayed
0 = regulation temperature
1 = setpoint
2 = evaporator temperature
3 = auxiliary temperature
4 = air in temperature
11
P7
50
inlet air weight for calculated
product temperature (CPT)
0... 100 %
CPT = {[(P7 x (inlet air T)] +
[(100 - P7) x (outlet air T)] :
100}
12
P8 5 display refresh time 0... 250 s : 10
N.
PAR.
DEF.
REGULATION
MIN... MAX.
13
r0 2.0 setpoint differential 1... 15 °C/°F
14
r1 -40 minimum setpoint -99 °C/°F... r2
15
r2 50.0
maximum setpoint r1... 199 °C/°F
16
r3 0 enable setpoint block
0 = no 1 = yes
17
r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
18
r6 0.0 setpoint offset in overcooling 0... 99 °C/°F
19
r7 0 overcooling duration 0... 240 min
20
r12
1
position of the r0 differential
0 = asymmetric
1 = symmetric
N. PAR. DEF. COMPRESSOR MIN... MAX.
21
C0
0
compressor on delay after
power-on 0... 240 min
22
C1
5
delay between 2 compressor
switch-ons
0... 240 min
23
C2 3 compressor off minimum time 0... 240 min
24
C3 0 compressor on minimum time 0... 240 s
25
C4
10
compressor off time during
cabinet probe alarm 0... 240 min
26
C5
10
compressor on time during
cabinet probe alarm 0... 240 min
27
C6
80.0
threshold for high condensation
warning 0... 199 °C/°F
differential = 2 °C/4 °F
28
C7
90.0
threshold for high condensation
alarm 0... 199 °C/°F
29
C8 1 high condensation alarm delay 0... 15 min
30
C10
0
compressor hours for service
0... 999 h x 100
0 = disabled
31
C11
10
second compressor switch-on
delay 0... 240 s
N. PAR. DEF. DEFROST MIN... MAX.
32
d0
8
automatic defrost interval
0... 99 h
0 = only manual
if d8 = 3, maximum interval
33
d1
0
defrost type
0 = electric
1 = hot gas
2 = compressor stopped
34
d2 2.0 threshold for defrost end -99... 99 °C/°F
35
d3
30
defrost duration
0... 99 min
se P3 = 1, maximum duration
36
d4 0 enable defrost at power-on 0 = no 1 = yes
37
d5 0 defrost dealy after power-on 0... 99 min
38
d6
1
value displayed during defrost
0 = regulation temperature
1 = display locked
2 = dEF label
39
d7 2 dripping time 0... 15 min
40
d8
0
defrost interval counting mode
0 = device on hours
1 = compressor on hours
2 = hours evaporator
temperature < d9
3 = adaptive
4 = real time
41
d9
0.0
evaporation threshold for
automatic defrost interval
counting
-99... 99 °C/°F
42
d11 0 enable defrost timeout alarm 0 = no 1 = yes
43
d15
0
compressor on consecutive time
for hot gas defrost 0... 99 min
44
d16
0
pre-dripping time for hot gas
defrost 0... 99 min
45
d18
40
adaptive defrost interval
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
46
d19
3.0
threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °C/°F
optimal evaporation
temperature - d19
47
d20
180
compressor on consecutive time
for defrost 0... 999 min
0 = disabled
48
d21
200
compressor on consecutive time
for defrost after power-on and
overcooling
0... 500 min
if (regulation temperature -
setpoint) > 10°C/20 °F
0 = disabled
49
d22
-2.0
evaporation threshold for
adaptive defrost interval counting
(relative to optimal evaporation
temperature)
-10... 10 °C/°F
optimal evaporation
temperature + d22
50
d25
0
enable air out probe for defrost
during evaporator probe alarm 0 = no 1 = yes
51
d26
6
defrost interval during
evaporator probe alarm
0... 99 h
0 = only manual
if d25 = 1
N.
PAR.
DEF.
ALARMS
MIN... MAX.
52
A0
0
select value for high/low
temperature alarms 0 = regulation temperature
1 = evaporator temperature
53
A1
0.0
threshold for low temperature
alarm -99... 99 °C/°F
54
A2
0
low temperature alarm type
0 = disabled
1 = relative to setpoint
2 = absolute
55
A4
0.0
threshold for high temperature
alarm -99... 99 °C/°F
56
A5
0
high temperature alarm type
0 = disabled
1 = relative to setpoint
2 = absolute
57
A6
120
high temperature alarm delay
after power-on 0... 240 min
58
A7
15
high/low temperature alarms
delay 0... 240 min
59
A8
15
high temperature alarm delay
after defrost 0... 240 min
60
A9
15
high temperature alarm delay
after door closing 0... 240 min
61
A11
2.0
high/low temperature alarms
reset differential 1... 15 °C/°F
N. PAR. DEF. FANS MIN... MAX.
62
F0
1
evaporator fan mode during
normal operation
0 = off 1 = on
2 = on if compressor on
3 = thermoregulated (with
regulation temperature
+ F1)
4 = thermoregulated (with
regulation temperature
+ F1) if compressor on
5 = according to F6
6 =
thermoregulated (with F1)
7 = thermoregulated (with
F1) if compressor on
63
F1
-4.0
threshold for evaporator fan
operation -99... 99 °C/°F
64
F2
0
evaporator fan mode during
defrost and dripping 0 = off 1 = on
2 = according to F0
65
F3
2
evaporator fan off maximum
time 0... 15 min
66
F4
30
evaporator fan off time during
energy saving 0... 240 s x 10
if F0 ≠5
67
F5
30
evaporator fan on time during
energy saving 0... 240 s x 10
if F0 ≠5
68
F6
0
high/low humidity operation
0 = low humidity (with F17
and F18 if compressor
off, on if compressor on)
1 = high humifity (on)
69
F7
5.0
threshold for evaporator fan on
after dripping (relative to
setpoint)
-99... 99 °C/°F
setpoint + F7
70
F8
2.0
threshold for evaporator fan
operation differential 1... 15 °C/°F
71
F9
10
evaporator fan off delay after
compressor off 0... 240 s
if F0 = 2 or 5
72
F10
1
condenser fan mode
0 =
thermoregulated (with F11)
1 = thermoregulated (with
F11) if compressor off,
on if compressor on
2 = thermoregulated (with
F11) if compressor off,
on if compressor on, off
during defrost, pre-
dripping and dripping
73
F11
15.0
threshold for condenser fan on
0... 99 °C/°F
differential = 2 °C/4 °F
74
F12
30
condenser fan off delay after
compressor off 0... 240 s
if P4 ≠ 1
75
F17
60
evaporator fan off time with low
humidity 0... 240 s
76
F18
10
evaporator fan on time with low
humidity 0... 240 s
N. PAR. DEF. DIGITAL INPUTS MIN... MAX.
77
i0
5
door switch input function
0 = disabled
1 = compressor +
evaporator fan off
2 = evaporator fan off
3 = cabinet light on
4 = compressor +
evaporator fan off,
cabinet light on
5 = evaporator fan off +
cabinet light on
78
i1
0
door switch input activation
0 = with contact closed
1 = with contact open
79
i2
30
open door alarm delay
-1... 120 min
-1 = disabled
80
i3
15
regulation inhibition maximum
time with door open -1... 120 min
-1 = until the closing
81
i5
7
multi-purpose input function
0 = disabled
1 = energy saving
2 = iA alarm
3 = iSd alarm
4 = button-operated load on
5 = device on/off
6 = LP alarm
7 = C1t alarm
8 = C2t alarm
82
i6
0
multi-purpose input activation
0 = with contact closed
1 = with contact open
83
i7
0
multi-purpose input alarm delay
0... 120 min
if i5 = 3 or 7, compressor on
delay after alarm reset
84
i8
0
number of multi-purpose input
activations for high pressure
alarm
0... 15
0 = disabled
if i5 = 3
85
i9
240
reset counter time for high
pressure alarm
1... 999 min
86
i10
0
door closed consecutive time for
energy saving
0... 999 min
after regulation temperature
< SP
0 = disabled
87
i13
180
number of door openings for
defrost 0... 240
0 = disabled
88
i14
32
door open consecutive time for
defrost 0... 240 min
0 = disabled
N. PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
89
u1
0
auxiliary output configuration
0 = cabinet light
1 = demisting
2 = button-operated load
3 = alarm
4 = door heaters
5 = heater for neutral zone
6 = condenser fan
7 = second compressor
8 = on/stand-by
90
u2
0
enable cabinet light and button-
operated load in stand-by 0 = no 1 = yes
manual
91
u4
1
enable alarm output off silencing
the buzzer 0 = no 1 = yes
92
u5
-1.0
threshold for door heaters on
-99... 99 °C/°F
differential = 2 °C/4 °F
93
u6 5 demisting on duration 1... 120 min
94
u7
-5.0
neutral zone threshold for
heating (relative to setpoint)
-99... 99 °C/°F
differential = 2 °C/4 °F
setpoint + u7
95
u9 1 enable alarm buzzer 0 = no 1 = yes
96
u11
0
auxiliary output 2 configuration
(not available in EVLJS224)
0 = cabinet light
1 = demisting
2 = button-operated load
3 = alarm
4 = door heaters
5 = heater for neutral zone
6 = condenser fan
7 = second compressor
8 = on/stand-by
N. PAR. DEF. REAL TIME CLOCK MIN... MAX.
97
Hr0 0enable clock 0 = no 1 = yes
EVCO S.p.A. | EVBOX Light JS200 | Instruction sheet ver. 1.0 | Code 104LJS200E103 | Page 3 of 3 | PT 48/17
N. PAR. DEF. ENERGY SAVING MIN... MAX.
98
HE2 0 energy saving maximum duration
0... 999 min
N. PAR. DEF. REAL TIME ENERGY SAVING MIN... MAX.
99
H01 0 energy saving time 0... 23 h
100
H02 0 energy saving maximum duration
0... 24 h
N. PAR. DEF. REAL TIME DEFROST (if d8 = 4) MIN... MAX.
101
Hd1 h- 1st daily defrost time h- = disabled
102
Hd2 h- 2nd daily defrost time h- = disabled
103
Hd3 h- 3rd daily defrost time h- = disabled
104
Hd4 h- 4th daily defrost time h-= disabled
105
Hd5 h- 5th daily defrost time h-= disabled
106
Hd6 h- 6th daily defrost time h-= disabled
N. PAR. DEF. RESERVED
MIN... MAX.
107
Sd0 - - - reserved reserved
108
Sd1 - - - reserved reserved
109
Sd2 - - - reserved reserved
110
Sd3 - - - reserved reserved
111
Sd4 - - - reserved reserved
112
Sd5 - - - reserved reserved
N. PAR. DEF. SAFETIES MIN... MAX.
113
POF 1 enable ON/STAND-BY key 0 = no 1 = yes
114
Loc 1 enable keypad lock 0 = no 1 = yes
115
PAS -19 password -99... 999
116
PA1 426 level 1 password -99... 999
117
PA2 824 level 2 password -99... 999
N. PAR. DEF. DATA-LOGGING EVLINK MIN... MAX.
118
rE0 60 data-logger sampling interval 0... 240 min
119
rE1
4
recorded temperature
0 = none 1 = cabinet
2 = evaporator
3 = auxiliary
4 = cabinet and evaporator
5 = all
N. PAR. DEF. MODBUS MIN... MAX.
120
LA 247 MODBUS address 1... 247
121
Lb
2
MODBUS baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
122
LP
2
parity
0 = none 1 = odd
2 = even
N. PAR. DEF. BLUETOOTH MIN... MAX.
123
bLE
1
serial port configuration for
connectivity
0 = free
1 = forced for EVconnect or
EPoCA
2-99= EPoCA local network
address
8 ALARMS
COD.
DESCRIPTION
RESET
TO CORRECT
Pr1 cabinet probe alarm automatic
- check P0
Pr2
evaporator probe alarm automatic
- check probe integrity
Pr3 auxiliary probe alarm automatic
- check electrical connection
rtc clock alarm manual set date, time and day of the week
AL low temperature alarm automatic
check A0, A1 and A2
AH high temperature alarm automatic
check A4 and A5
id open door alarm automatic
check i0 and i1
PF
power failure alarm
manual
- touch a key
- check electrical connection
COH high condensation warning automatic check C6
CSd
high condensation alarm
manual
- switch the device off and on
- check C7
iA multi-purpose input alarm automatic check i5 and i6
iSd
high pressure alarm
manual
- switch the device off and on
- check i5, i6, i8, i9
LP
low pressure alarm
automatic
check i5 and i6
C1t
compressor thermal switch
alarm
automatic
check i5 and i6
C2t
second compressor thermal
switch alarm
automatic
check i5 and i6
dFd
defrost timeout alarm
manual
- touch a key
- check d2, d3 and d11
- - -
user interface-control
module communication
alarm
manual
check electrical connection
9 TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container User interface
White, self-extinguishing
Control module
Open frame board on plastic
support.
Category of heat and fire resistance
D
Measurements
User interface
150.0 x 245.0 x 37.1 mm
(5 15/16 x 9 5/8 x 1 7/16 in)
Control module:
142.0 x 122.0 x 37.0 mm (5
9/16 x 4 13/16 x 1 7/16 in)
Mounting methods for the
control device
User interface
To be fitted on a DIN rail, in a
control panel
Control module
To be installed on an
electrical switchboard
Degree of protection
provided by the covering User interface
IP65
Control module
IP00
Connection method
Plug-in screw terminal blocks
for wires up to 1 mm²
Fixed screw terminal blocks
for wires up to 2.5 mm²
Fixed screw terminal blocks
for wires up to 5 mm²
Faston, 6.3 mm
Pico-Blade connector
Maximum permitted length for connection cables
User-interface-control module: 10 m (32.8 ft)
Power supply: 10 m (32.8 ft)
Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
Operating temperature
From 0 to 55 °C (from 32 to 131 °F)
Storage temperature
From -25 to 70 °C (from -13 to 158 °F)
Operating humidity
Relative humidity without condensate from
10 to 90%
Pollution status of the control device
2
Conformity
RoHS 2011/65/CE
WEEE 2012/19/EU
REACH (EC) Regulation
1907/2006
EMC 2014/30/UE LVD 2014/35/UE
Power supply
115... 230 VAC (+10% -15%), 50/60 Hz (±3
Hz), max. 6 VA insulated
Earthing methods for the control device
With earth terminal
Rated impulse-withstand voltage
2.5 KV
Over-voltage category
II
Software class and structure
A
Analogue inputs
2 for PTC or NTC probes (cabinet probe and
evaporator probe)
PTC probes
Sensor type
KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field
From -50 to 150 °C (from -58 to 302 °F)
Resolution
0.1 °C (1 °F)
NTC probes
Sensor type
ß3435 (10 K@ 25 °C, 77 °F)
Measurement field
From -40 to 105 °C (from -40 to 221 °F)
Resolution
0.1 °C (1 °F)
Digital inputs
1 dry contact (door switch)
Dry contact
Contact type
5 VDC, 2 mA
Power supply
None
Protection
None
Other inputs
Input configurable for analogue input (auxiliary probe) or
digital input (multi-purpose input)
Digital outputs
5 (4 for EVLJS224) with electro-mechanical relay
(compressor, defrost, evaporator fan, auxiliary relay 1 and
auxiliary relay 2)
Compressor relay (K2)
SPST, 30 A res. @ 250 VAC
Defrost relay (K4)
SPST, 16 A res. @ 250 VAC
Evaporator fan relay (K5)
SPST, 8 A res. @ 250 VAC
Auxiliary relay 1 (K3)
SPST, 16 A res. @ 250 VAC
Auxiliary relay 2 (K1, not available in
EVLJS224)
SPST, 30 A res. @ 250 VAC
The device guarantees double insulation between each digital output connector and the rest
of the components of the device
Type 1 or Type 2 Actions
Type 1
Additional features of Type 1 or Type 2
actions
C
Displays
LED custom display, 3 digit, with function
icons
Alarm buzzer
Incorporated
Communications ports
1 TTL MODBUS slave port for EVconnect app,
EPoCA remote monitoring system or for BMS
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of EVCO and thus
protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the
full or partial reproduction and disclosure of the content other than with the express approval of EVCO.
The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the
device. EVCO accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the
equipment.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
Tel. 0437/8422 | Fax 0437/83648
email [email protected] | web www.evco.it

Other Evco Controllers manuals

Evco EV9376 User manual

Evco

Evco EV9376 User manual

Evco c-pro 3 nano CHILL User manual

Evco

Evco c-pro 3 nano CHILL User manual

Evco Vcolor 579 User guide

Evco

Evco Vcolor 579 User guide

Evco EV3 Basic Split User manual

Evco

Evco EV3 Basic Split User manual

Evco C-PRO NANO Series User manual

Evco

Evco C-PRO NANO Series User manual

Evco EV3 HP User guide

Evco

Evco EV3 HP User guide

Evco EVRS 200 Series User manual

Evco

Evco EVRS 200 Series User manual

Evco EVBOX Light J500 Series User manual

Evco

Evco EVBOX Light J500 Series User manual

Evco C-pro 3 giga User manual

Evco

Evco C-pro 3 giga User manual

Evco EVJ 500 Series User manual

Evco

Evco EVJ 500 Series User manual

Evco Vcolor 869 User guide

Evco

Evco Vcolor 869 User guide

Evco EV8338 User manual

Evco

Evco EV8338 User manual

Evco EV3271 User manual

Evco

Evco EV3271 User manual

Evco EV3S204 User manual

Evco

Evco EV3S204 User manual

Evco EV3 WEB User guide

Evco

Evco EV3 WEB User guide

Evco EV3143 User manual

Evco

Evco EV3143 User manual

Evco EVJS 800 Series User guide

Evco

Evco EVJS 800 Series User guide

Evco Vcolor 279 Instructions for use

Evco

Evco Vcolor 279 Instructions for use

Evco EV3B94 User manual

Evco

Evco EV3B94 User manual

Evco Vcolor 229 M Series User manual

Evco

Evco Vcolor 229 M Series User manual

Evco EVJ 700 User guide

Evco

Evco EVJ 700 User guide

Evco c-pro 3 Series User manual

Evco

Evco c-pro 3 Series User manual

Evco EVD HP User guide

Evco

Evco EVD HP User guide

Evco EVFTFT219 User manual

Evco

Evco EVFTFT219 User manual

Popular Controllers manuals by other brands

Mitsubishi MELSEC Q Series user manual

Mitsubishi

Mitsubishi MELSEC Q Series user manual

DekunTech G2 Series instruction manual

DekunTech

DekunTech G2 Series instruction manual

Siemens RVD110 Basic documentation

Siemens

Siemens RVD110 Basic documentation

Micropelt MVA003 EnOcean quick start

Micropelt

Micropelt MVA003 EnOcean quick start

Brodersen GC-10 installation guide

Brodersen

Brodersen GC-10 installation guide

Comunello SPIN instruction manual

Comunello

Comunello SPIN instruction manual

Wecon PLCLV5V-2RS485BD manual

Wecon

Wecon PLCLV5V-2RS485BD manual

Spa Guts VS300 Series Operation guide

Spa Guts

Spa Guts VS300 Series Operation guide

AUMA AUMATIC AC 01.2 manual

AUMA

AUMA AUMATIC AC 01.2 manual

Santerno Sinus Penta user manual

Santerno

Santerno Sinus Penta user manual

Crouzet MILLENIUM II+ Series installation manual

Crouzet

Crouzet MILLENIUM II+ Series installation manual

PowerTraveller REDSTART 50 quick start guide

PowerTraveller

PowerTraveller REDSTART 50 quick start guide

CEStronics AccessOne TSG8 Assembly and operating manual

CEStronics

CEStronics AccessOne TSG8 Assembly and operating manual

Allen-Bradley MicroLogix 1400 instruction manual

Allen-Bradley

Allen-Bradley MicroLogix 1400 instruction manual

Vaillant auroMATIC VRS 570 Wiring Diagram Book

Vaillant

Vaillant auroMATIC VRS 570 Wiring Diagram Book

Carrier 40VMD 006 Installation and maintenance instructions

Carrier

Carrier 40VMD 006 Installation and maintenance instructions

Deskontrol Electronics deskontroller 64 user manual

Deskontrol Electronics

Deskontrol Electronics deskontroller 64 user manual

Hunter Hydrawise Pro-HC quick start

Hunter

Hunter Hydrawise Pro-HC quick start

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.