GE Multilin 469 Motor Management Relay 1-5
1 INTRODUCTION 1.2 SPECIFICATIONS
1
ANALOG CURRENT OUTPUT
Type: Active
Range: 4 to 20 mA, 0 to 1 mA
(must be specified with order)
Accuracy: ±1% of full scale
Maximum Load: 4 to 20 mA input: 1200 Ω
0 to 1 mA input: 10 kΩ
Isolation: 36 Vpk
(Isolated with RTDs and Analog Inputs)
4 Assignable Outputs: phase A current, phase B current, phase
C current, 3 phase average current,
ground current, phase AN (AB) voltage,
phase BN (BC) voltage, phase CN (CA)
voltage, 3 phase average voltage, hot-
test stator RTD, hottest bearing RTD,
hottest other RTD, RTD # 1 to 12, Power
factor, 3-phase Real power (kW), 3-
phase Apparent power (kVA, 3-phase
Reactive power (kvar), Thermal Capacity
Used, Relay Lockout Time, Current
Demand, kvar Demand, kW Demand,
kVA Demand, Motor Load, Torque
OVERLOAD / STALL PROTECTION / THERMAL MODEL
Overload Curves: 15 Standard Overload Curves, Custom
Curve, Voltage Dependent Custom
Curve for high inertia starting (all curves
time out against average phase current)
Curve Biasing: Phase Unbalance
Hot/Cold Curve Ratio
Stator RTD
Running Cool rate
Stopped Cool Rate
Line Voltage
Overload Pickup: 1.01 to 1.25 (for service factor)
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: ±100 ms or ±2% of total time
Elements: Trip and Alarm
TERMINALS
Low Voltage (A, B, C, D terminals): 12 AWG max.
High Voltage (E, F, G, H terminals): #8 ring lug, 10 AWG wire std.
PHASE SHORT CIRCUIT
Pickup Level: 4.0 to 20.0 ×CT primary in steps of 0.1
of any one phase
Time Delay: 0 to 1000 ms in steps of 10
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: +50 ms
Elements: Trip
MECHANICAL JAM
Pickup Level: 1.01 to 3.00 ×FLA in steps of 0.01 of any
one phase, blocked on start
Time Delay: 1 to 30 s in steps of 1
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: ±0.5 s or ±0.5% of total time
Elements: Trip
OUTPUT RELAYS
Relay contacts must be considered unsafe to touch
when the 469 is energized! If the output relay con-
tacts are required for low voltage accessible applica-
tions, it is the customer’s responsibility to ensure
proper insulation levels.
Configuration: 6 Electromechanical Form C
Contact Material: silver alloy
Operate Time: 10 ms
Max ratings for 100000 operations
UNDERCURRENT
Pickup Level: 0.10 to 0.95 ×CT primary in steps of
0.01 of any one phase
Time Delay: 1 to 60 s in steps of 1
Block From Start: 0 to 15000 s in steps of 1
Pickup Accuracy: as per Phase Current Inputs
Timing Accuracy: ±0.5 s or ±0.5% of total time
Elements: Trip and Alarm
CURRENT UNBALANCE
Unbalance: I2/I
1if Iavg > FLA
I2/I
1×Iavg /FLAifI
avg < FLA
Range: 0 to 100% UB in steps of 1
Pickup Level: 4 to 40% UB in steps of 1
Time Delay: 1 to 60 s in steps of 1
Pickup Accuracy: ±2%
Timing Accuracy: ±0.5 s or ± 0.5% of total time
Elements: Trip and Alarm
GROUND INSTANTANEOUS
Pickup Level: 0.1 to 1.0 ×CT primary in steps of 0.01
Time Delay: 0 to 1000 ms in steps of 10
Pickup Accuracy: as per Ground Current Input
Timing Accuracy: +50 ms
Elements: Trip and Alarm
PHASE DIFFERENTIAL INSTANTANEOUS
Pickup Level: 0.05 to 1.0 ×CT primary in steps of 0.01
of any one phase
Time Delay: 0 to 1000 ms in steps of 10
Pickup Accuracy: as per Phase Differential Current Inputs
Timing Accuracy: +50 ms
Elements: Trip
VOLTAGE MAKE/CARRY BREAK MAX.
LOAD
CONTINUOUS 0.2S
DC
RESISTIVE 30 V 10 A 30 A 10 A 300 W
125 V 10 A 30 A 0.5 A 62.5 W
250 V 10 A 30 A 0.3 A 75 W
DC
INDUCTIVE L/
R=40ms
30 V 10 A 30 A 5 A 150 W
125 V 10 A 30 A 0.25 A 31.3 W
250 V 10 A 30 A 0.15 A 37.5 W
AC
RESISTIVE 120 V 10 A 30 A 10 A 2770 VA
250 V 10 A 30 A 10 A 2770 VA
AC
INDUCTIVE
P.F.=0.4
120 V 10 A 30 A 4 A 480 VA
250 V 10 A 30 A 3 A 750 VA