GE SHARPSHOOTER 6150-ID User manual

15
10
5
0
5
10
10 50510
Hotorcoldairdirected
ontosensor
Pets
Intermittent
heatsources
Windows
Figure3. Cross traffic Figure4. Blocking coverage pattern
6150-ID SHARPSHOOTER™PIR
installation instructions
Sunlightor
reflectedsunlight
Description
The 6150-ID (Figure 1) is an addressable PIR device that
interfaces with the PinPoint system. This system provides
flexibleandreliabletwo-waycommunicationbetweenthe
device and the controller.
Mounting location
Avoidfalsealarmsources(Figure2)
The unit should not “see” sources of heat or cold. For
false alarm free operation, no part of an unwanted hot
spot should enter any part of a zone.
Locatefor crosstraffic (Figure3)
Place the unit where intruders move across the beams,
not toward the unit. For best detection, an intruder
should cross the entire zone.
Donotblockthecoveragepattern(Figure4)
The unit requires a clear line of sight. Inform end-users
not to block the coverage pattern with inventory or
furniture.
Figure 1. Exploded view
g
Figure2. Falsealarmsources
SlidingLEDcover
Standardlens
(Maskingkitincluded)
Swivelmountingbracket
#8x3/4"(2cm)screw
forballjointshoe
Frontcover
Two#6x3/4"(2cm)screwsfor
mountingthebracketorcase
(Two#6wallanchorsare
includedforsheetrockmounting)
Mountingknockouts
Lensshield/circuit
boardassembly
Base
LED

26150-ID Sharpshooter PIR
Installation Instructions
7. Strip1/4inch(6.4mm)ofinsulationfromeach
PinPoint wire. Connect the wiring to the appropriate
screw terminals (Figure 8) and tighten the screws.
Make sure the cable is slack in the wall to avoid
stressing the wires at their connections.
8. Snap the cover back on the base and seal all
openings.
9. Walk test the unit to confirm correct operation (see
Walk test).
10. Slide the LED cover up to hide the LED (Figure 1), if
desired.
Installation
1. Run the PinPoint system wiring to the unit location.
2. Open the unit by snapping the front cover down and
off the base (Figure 1).
CAUTION You must be free of all static electricity
before handling sensor circuit boards.
Touch a grounded, bare metal surface
before touching ciruit boards or wear a
grounding strap.
3. Use the masking kit (Figure 5) if you need to adjust
zone coverage for your application. See Masking.
4. Set the pulse and sensitivity DIP switches (Figure
6). See DIPswitches.
5. Set the PinPoint address DIP switches (Figure 6).
Devices are shipped with DIP switches set to 255.
This is an invalid address. Thedevice will not
communicatewiththecontrollerandthewalktest
LEDwillnotlightuntilavalidaddresshasbeenset.
Refer to the controller's manual to determine the
correct address setting for each unit.
6. Pull the PinPoint wiring through the base and attach
the base to the wall using the corner or flat wall
knockouts (Figure 7). For optimal coverage using
the standard lens, mount 6 feet 10 inches (2.1 m)
above the floor.
See Swivel bracket mounting for instructions on
mounting with the swivel bracket (Figures 9 and 10).
Figure7. Mounting without the swivel bracket
Figure 8. PinPoint wiring
- + - +
CornerFlatwall
15
10
5
0
5
10
10 50510
Wiring
knockout
Corner
mounting
knockout
Flatwallmounting
knockouts
Corner
mounting
knockout
Figure5. Masking
WVUT SRQPONM
ABCDEFGHJKL C
STANDARD LENS
PEEL AND STICK TO GROVE SIDE OF LENS
Figure6. DIP switches Pulse (1) and
sensitivity (2)
DIP switches
PinPoint address
DIP switches
on12 on1 2
345678

3
Swivel bracket mounting
The swivel bracket allows aiming and adjusting the unit
formaximumdetectionandavoidanceoffalsealarms
(Figure 9).
The swivel bracket’s snap-off tabs allow angle mounting,
for applications such as hallway protection. Break the
tabs off by bending them back and forth.
Use these screws for mounting:
•Two #6x 3/4"(19 mm)screws formounting the
bracket or the base to the wall
•One#8 x 3/4"(19 mm) screwfor mounting thebase
onto the bracket (insert into ball joint shoe)
Align the arrows on the ball joint shoe with the zeroes on
the base for 6 foot 10 inch (2.1 m) mounting for typical
coverage. This is the 0 degree setting. For every 1 foot
(0.3 m) above the typical mounting height, tilt the shoe
down1degree. Forexample,for7feet10inches(2.4m),
tilt the shoe down 1 degree, or for 8 feet 10 inches (2.7 m),
tilt the shoe down 2 degrees.
Turn the swivel bracket screw (Figure 10) until snug.
DIP switches
DIP switches on the back of the circuit board (Figure 6)
set pulse, sensitivity, and PinPoint address.
Pulse(DIPswitch 1)
ON Bi-curtainmode(3pulse),thefactorydefault,
increasesfalsealarmimmunityinsmallerareas
and requires the intruder to pass through two
curtains to trigger an alarm. Do not use for single
curtain applications or ranges under 5 feet (1.5
m).
OFF Standard curtain mode (2 pulse) is used for wide-
angle or single-curtain applications. It requires
the intruder to only pass through one curtain to
triggeranalarm.
Notes Operation in the standard curtain mode is for
the specified ranges of 33 feet (10.1m) and
45 feet (13.7 m).
For operation in bi-curtain mode, the unit
has 30 feet (9.1m) of range only.
For ranges from 30 to 45 feet (9.1 to 13.7
m), the unit will provide detection within 6
steps or 14 feet (4.3 m) across the plane of
coverage.
Masking
To avoid smudging the masking strips, make sure your
hands are clean before using the masking kit.
1. To unsnap the shield from the front cover, grasp the
edge of the circuit board and gently rotate the lens
shield/circuit board assembly up from the bottom
(see figure 1). Remove the lens from the shield.
2. Locate the lettered masking strip on the masking kit,
peel off the masking strip, and press onto the
corresponding grooved segment on the lens. The
notch of the lens must be up.
3. Reinstall the lens in the shield. The notch on the lens
should match the notch on the shield.
4. Snap the shield/circuit board assembly into the front
cover.
Sensitivity(DIPswitch 2)
ON High sensitivity range up to 45 feet (13.7 m)
OFF Lowsensitivity rangeunder 33feet(10.1 m)
(factorydefault)
It's important to program the unit correctly for optimum
sensitivity and walk test the unit regularly (see Walk test).
Figure 9. Swivel bracket mounting
Figure10. Swivel bracket screw
Flatwall
onetab Corner
twotabs
Flatwall
notabs
Cornermounting
holes
Wiringhole Flatwallmounting
holes
Ceiling
Cornermounting
holes
Allow1.6in.(40mm)
minimum

46150-ID Sharpshooter PIR
Installation Instructions
Walk test
A walk test mode for testing the unit operation and
coverage pattern is provided. Do the following to walk test
the unit:
1. Ensure the unit is enrolled in the PinPoint system. The
walk test LED will not light unless the unit is enrolled.
2. Pull the front cover away from the base until the
tamper switch opens to enable the walk test mode.
3. When the unit is remounted on the base, the unit
remains in the walk test mode for 3 to 4 minutes. If
additional time is required, releasing and depressing
the tamper switch will reset the walk test timer.
Depending on pulse and sensitivity DIP switch
settings, the walk test mode allows the unit to alarm
whenever one or two curtain areas are entered. The
LED visible on the front cover lights to indicate an
alarm.
4. Walk test the detection pattern and make any
necessary adjustments.
5. Replace and walk test the unit to verify the unit is
communicatingwiththecontroller.
Note After the walk test mode times out in 3 to 4
minutes, the unit returns to normal operating
mode. In normal operating mode, the unit
LED is disabled to reduce voltage loss on the
PinPoint bus.
Maintenance
When installed and used properly, the unit provides years
ofservicewith minimalmaintenance.To ensureproper
operation, you should walk test the unit annually (see
Walk test).
Clean the inside of the unit with a soft bristled brush or
compressed air. Clean the cover with a damp (water) cloth
as needed to keep it free of dust and dirt. Always test the
unitaftercleaning.
Figure11. Dimensions
1.9in.
(48mm)
2.2in.
(55mm)
2.9in.
(74mm)
3.7in.
(94mm)
2.4in.
(61mm)
45°
FrontView SideView
TopView

5
Zone patterns
0°6°
6'10"
(2.1m)
7'6"
(2.3m) 40'
(12.2m)
0
Topview Sideview
Figure14. Curtain
Figure13. Longrange
Figure12. Standard
Figure16. Extra wide angle
0140°
20ft.
(6.1m) 20ft.
(6.1m)
6ft.10in.
(2.1m) 0
Topview
Sideview
Figure15. Pet alley
35ft.
(10.7m)
035ft
(10.7m) 35ft.
(10.7m)
0
3ft.3in.
(1.0m)
Topview
Sideview
45ft.
(13.7m)
40ft.
(12.2m)
30ft.
(9.1m)
20ft.
(6.1m)
10ft.
(3.0m)
0
010ft.
(3.0m) 20ft.
(6.1m) 30ft.
(9.1m) 40ft.
(12.2m) 45ft.
(13.7m)
6ft.10in.
(2.1m)
60°30°15°
Topview
4°
Sideview
36°
36°
0°6°6ft.10in.
(2.1m)
7ft.6in.
(2.3m) 9ft.
(2.7m) 90'
(27.5m)
Topview Sideview

66150-ID Sharpshooter PIR
Installation Instructions
Specifications
Housing material Flame retardant ABS
Operating voltage 8 to 27V (as supplied by the
PinPointbus)
Currentdraw 250µA typical average
3 mA with LED momentarily on
Transmit condition Alarm, tamper
Detection range 45 ft. (13.7 m)
Operatingtemperature 32 to 131°F (0 to 55°C)
Relative humidity 10 to 90% non-condensing
Maximum line length 10,000 ft. (3 km)
Standard swivel bracket ± 10° left/right, 10° up, 15° down
LED indicator Walk test
Dimensions:
Width 2.9 in. (74 mm)
Depth 2.4 in. (61 mm)
Height 3.7 in. (94 mm)
Color Off-white
Coverage Patterns Standard (installed) 45 ft. x 90°
Long Range (optional) 90 ft. x 6°
Curtain (optional) 40 ft. x 6°
Pet Alley (optional) 35 ft. x 90°
Extra Wide Angle (optional) 20 ft.
x 140°
Listings FCC, CE
GE Security
12345 SW Leveton Drive
Tualatin, OR 97062
503-692-4052
USA & Canada: 800-547-2556
Tech Support: 800-648-7424
www.gesecurity.com
1042134 Rev B September 2004
FCC compliance
This device complies with Part 15 of the FCC rules. Operation is
subject to the following conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interference that may cause undesired operation.
Product ordering
Product Description
6150-ID Addressable, passive infrared motion
sensor for use with the PinPoint bus
with swivel bracket and standard lens
Lenses
6070 Standard lens, 45 ft. (13.7 m) x 90°
6071 Long range lens, 90 ft. (27.4 m) x 6°
6072 Extra wide angle lens, 20 ft. (6.1 m) x
140°
6073 Curtain lens, 40 ft. (12.2 m) x 6°
6074 Pet alley lens (12°tilt), 35 ft. (10.7 m)
x 90°
6077 Pet alley lens (non-tilt), 35 ft. (10.7 m)
x 90°
6076 Single beam pet alley, 50 ft. (15.2 m) x
6°
Table of contents
Other GE Industrial Equipment manuals

GE
GE ecomagination Profibus DP AF-650 GP User manual

GE
GE RAB8116B User manual

GE
GE GEH-2906B User manual

GE
GE MicroVersaTrip Plus User manual

GE
GE VT-700 User manual

GE
GE Multilin DGPR User manual

GE
GE ArcamEBM Spectra H User manual

GE
GE WAVE Cabinet 20 User manual

GE
GE Mark VIeS Parts list manual

GE
GE AKD-10 User guide
Popular Industrial Equipment manuals by other brands

Neslab
Neslab System I Liquid to Liquid Instruction and operation manual

Dixon
Dixon 6200X Installation & operating instructions

HYTROL
HYTROL 190-E24MC Installation and maintenance manual

YASKAWA
YASKAWA GA500 series Installation and operation instruction

Enerpac
Enerpac LGH Series instruction sheet

Dodge
Dodge USN 500 Series instruction manual