manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell Home
  6. •
  7. Security System
  8. •
  9. Honeywell Home PROA7PLUS Series Assembly instructions

Honeywell Home PROA7PLUS Series Assembly instructions

PROA7PLUS / PROA7 Security System
Installation and Setup Guide
This Quick Installation Guide provides the basic steps to quickly and easily install the
Burglar and Fire Alarm Control Panel, using the built-in programming defaults. The
control is designed to be placed on a desk/table top with the optional stand attached or
mounted to a wall using the wall mount.
STEP 1 - Installing the Rechargeable Backup Battery and
Power Connector
1. Remove the Control’s left and right side covers.
2. Install the PROWIFIZW (Wi-Fi®and Z-Wave®), PROLTE-Series (LTE)
Communications and/or PROTAKEOV Wireless Converter modules (if required).
3. Insert the Battery Pack into the case.
4. Connect the battery connector to the receptacle on the PC board.
5a. Connect the power cable to the GND and +9V terminals on the wall mount and to
the + and – terminals on the Power Supply. Refer to Table 1 for wire gauge and
length. Do not apply power at this time. OR
5b Connect the power supply connector to the receptacle on the desk mount. Do
not apply power at this time.
NOTE: If using the optional wall mount configuration, skip to the wall mounting
procedure. If using the PROA7DM Desk Mount refer to the Installation Guide
P/N 800-25157.
Optional PROWIFIZW, PROLTE-Series and PROTAKEOV Communications Module
Note: Refer to the Specific Module Installation section in the online Installation &
Reference Guide for installation instructions.
PROLTE-SERIES
MODULE
COVER
COVER
POWER
SUPPLY
RECEPTACLE
DETAIL A
MACHINE
SCREW
PROTAKEOV
MODULE
QS-148-V0
2-CELL
BATTERY PACK
(P/N 300-11186)
3-CELL
BATTERY PACK
(300-10186)
BATTERY
CONNECTOR
EXT INT
PROWIFIZW
MODULE
SCREW
SCREW
OR
Table 1 – Wiring Guide
Maximum distance between
power supply and control
Wire Gauge
(AWG)
Note: Use UL-listed limited energy
cable
Up to 25 feet (7.62m) # 22
Up to 45 feet (13.72m) # 20
Up to 70 feet (21.34m) # 18
Up to 110 feet (33.53m) # 16
Mounting the Base to a Wall (Optional)
For wall mounting, perform the following:
1. Secure the Mounting Plate to the wall with 4 screws.
2. Install the Tamper Screw as shown (if required).
3. Secure the Control to the Mounting Plate by aligning the slots on the wall mount
and sliding the unit up until tabs on the wall mount are engaged. Then push it
toward the wall until to lock it in place.
4. Secure the Control with the set screw.
QS-056-V0
WALL
MOUNTING
PLATE
TAMPER
SCREW
(IF REQ’D)
MOUNTING
SCREWS
(4-TYPICAL)
SET
SCREW
PROA7PLUS
12
SNAP
INTO
PLACE
ENGAGE
TOP CLEATS
STEP 2 - Setting up the Communication Links
Note: Do not connect to a receptacle controlled by a switch.
1. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-
up, the “Please Standby!” will be displayed on the home screen.
2. Settings →Wi-Fi →Master User Code →Wi-Fi Networks OR Add networks
Manually OR WPS →Enter required information OR follow prompts →Save
STEP 3 - Registration Programming and Testing
Registration, Programming and Testing is conducted through AlarmNet 360™. On a
laptop, PC or Smart Device, go to: www.alarmnet360.com or the AlarmNet360 App.
IMPORTANT: Once the programming procedure has started and the unit is
powered up, do not remove power, disconnect the battery, or open the case.
Disconnecting power or activating the tamper switch can cause unpredictable
programming results.
Testing the System
The following test modes are available:
•Test Sensors (Walk Test)
•Test Communicator
Enter Test mode (Walk Test)
1. Select Test and enter the Master User Code.
2. Select System Tests.
3. Select Test Sensors. The system enters Walk Test mode. Follow the prompts.
4. Open each protected door and listen for three beeps from the keypad, followed
by the zone’s Voice Descriptor. Identification of each faulted protection point,
battery and signal strength appears on the display.
5. Walk in front of the motion sensor and listen for three beeps and the zone’s voice
descriptor.
6. Press each key on the keyfob to confirm it performs its assigned function.
7. When testing is complete, select End Test and follow the prompts.
8. Select the small icon to return to the home screen.
Shutting Down the System
To avoid corrupting the control’s memory, before removing power from the system:
1. Disarm the system.
2. Wait 30 seconds.
4. Unplug the power supply.
5. Disconnect the battery.
Features and Capacities
Feature
Details
PROA7PLUS
PROA7
Partitions 4
••
Maximum
Devices
•250 Intrusion/Fire Zones
- 127 SiX Series devices
(sensors, keyfobs, keypads)
- 250 5800 series devices
(requires PROTAKEOV
module)*
••
•32 SiX Series Keyfobs
••
•8 SiX Series Keypads/
Touchscreens
••
•Built-in Camera
•---
Z-Wave Supports up to 78 Z-Wave devices
with the following maximums:
Light Modules .......................... 60
Garage Doors ............................ 6
Door Locks:............................... 6
Z-Wave Thermostats*:............... 6
Wi-Fi Thermostats*: ................... 4
* Combination Z-Wave & Wi-Fi
thermostats maximum
................
6
••
Bluetooth Smartphone disarming via Bluetooth
•---
Wiselink Wiselink compatibility with
PROINDMV and PROOUTMV
Motion Viewers
•---
Security
Codes
96 User Codes
(Includes Master User #1)
••
Event Log 4,000 events
••
* The PROTAKEOV module supports communication with certain previously installed wireless
sensors and modules. Refer to PROTAKEOV Compatibility chart (p/n R800-26221A or later) for
a list of tested and approved vendor wireless devices.
Specifications
Dimensions: 7.875” W x 5.75” H x 1.0” D
Voltage Input: P/N 300-10260 – 9VDC, 2.5A
P/N 300-10260-CAN (Canada) – 9VDC, 2.5A
24-Hour Backup Battery: P/N 300-10186: Rechargeable Backup Battery: Lithium-
ion battery pack rated at 3.6/4.2V, 7500 mAH
P/N 300-11186: Rechargeable Backup Battery: Lithium-
ion battery pack rated at 3.6/4.2V, 5200 mAH
Contacting Technical Support
PLEASE, before you call Technical Support, be sure you:
READ THE INSTRUCTIONS!
•Determine that the power supply and/or backup battery are supplying proper voltages.
•Verify your programming information where applicable.
•Note the proper model number of this product, and the version level (if known) along
with any documentation that came with the product.
•Note your Honeywell Home customer number and/or company name.
Keeping this information handy will make it easier for us to serve you quickly and
effectively. For technical support please call 1-800-645-7492
This system must be checked by a qualified technician at least once every
three (3) years.
The Limitations of this Alarm System
While this system is an advanced design security system, it does not offer guaranteed protection
against burglary or fire or other emergency. Any alarm system, whether commercial or
residential, is subject to compromise or failure to warn for a variety of reasons. For example:
•Intruders may gain access through unprotected openings or have the technical sophistication
to bypass an alarm sensor or disconnect an alarm warning device.
•Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other
sensing devices will not work without power. Battery-operated devices will not work without
batteries, with dead batteries, or if the batteries are not put in properly. Devices powered
solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
•Signals sent by wireless transmitters may be blocked or reflected by metal before they reach
the alarm receiver. Even if the signal path has been recently checked during a weekly test,
blockage can occur if a metal object is moved into the path.
•A user may not be able to reach a panic or emergency button quickly enough.
•While smoke detectors have played a key role in reducing residential fire deaths in the United
States, they may not activate or provide early warning for a variety of reasons in as many as
35% of all fires, according to data published by the Federal Emergency Management Agency.
Some of the reasons smoke detectors used in conjunction with this System may not work are
as follows. Smoke detectors may have been improperly installed and positioned. Smoke
detectors may not sense fires that start where smoke cannot reach the detectors, such as in
chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may
not sense a fire on another level of a residence or building. A second-floor detector, for
example, may not sense a first-floor or basement fire. Moreover, smoke detectors have
sensing limitations. No smoke detector can sense every kind of fire every time. In general,
detectors may not always warn about fires caused by carelessness and safety hazards like
smoking in bed, violent explosions, escaping gas, improper storage of flammable materials,
overloaded electrical circuits, children playing with matches, or arson. Depending upon the
nature of the fire and/or the locations of the smoke detectors, the detector, even if it operates
as anticipated, may not provide sufficient warning to allow all occupants to escape in time to
prevent injury or death
•Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as
diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric
area protection. They do create multiple beams of protection, and intrusion can only be
detected in unobstructed areas covered by those beams. They cannot detect motion or
intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass
doors, or windows. Mechanical tampering, masking, painting or spraying of any material on
the mirrors, windows or any part of the optical system can reduce their detection ability.
Passive Infrared Detectors sense changes in temperature; however, as the ambient
temperature of protected area approaches the temperature range of 90° to 105°F, the
detection performance can decrease.
•Alarm warning devices such as sirens, bells, or horns may not alert people or wake up
sleepers if they are located on the other side of closed or partly open doors. If warning
devices sound on a different level of the residence from the bedrooms, then they are less
likely to waken or alert people inside the bedrooms. Even persons who are awake may not
hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance,
or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-
impaired people or waken deep sleepers.
•Even if the system responds to the emergency as intended, however, occupants may have
insufficient time to protect themselves from the emergency situation. In the case of a
monitored alarm system, authorities may not respond appropriately.
•This equipment, like other electrical devices, is subject to component failure. Even though this
equipment is designed to last as long as 10 years, the electronic components could fail at any
time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is
inadequate maintenance. This alarm system should be tested weekly to make sure all sensors
and transmitters are working properly.
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system
is not a substitute for insurance. Homeowners, property owners, and renters should continue to
act prudently in protecting themselves and continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to
themselves and their loved ones to learn about these developments.
RF Exposure
Warning –
The antenna(s) used for this device must be installed to provide a separation
distance of at least 7.8 inches (20 cm) from all persons and must not be co-located or operating
in conjunction with any other antenna or transmitter except in accordance with FCC and ISED
multi-transmitter product procedures.
Mise en Garde
Exposition aux Frequences Radio:
La/les antenne(s) utilisée(s) pour cet émetteur
doit/doivent être installée(s) à une distance de séparation d'au moins 20 cm (7,8 pouces) de
toute personne et ne pas être située(s) ni fonctionner parallèlement à tout autre transmetteur ou
antenne, excepté en conformité avec les procédures de produit multi transmetteur FCC et
ISEDs.
This equipment should be installed in accordance with National Electrical Code, NFPA 70,
Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540 and
Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72 (National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper
installation, operation, testing, maintenance, evacuation planning, and repair service is to
be provided with this equipment.
Warning: Owner’s instruction notice: ’Not to be removed by anyone except occupant
Avertissement : Avis du propriétaire : « Ne doit être retiré par personne, saut
l’occupant. »
Warning: this unit includes an alarm verification feature that will result in a delay of the
system alarm signal from the indicated circuits. The total delay (control unit plus smoke
detectors) shall not exceed 60 seconds. No other smoke detector shall be connected to
these circuits unless approved by the local authority having jurisdiction.
Avertissement: Cette unité peut être programmée pour utiliser une fonction de vérification
d’alarme d’incendie qui entraîne un délai dans la signalisation des alarmes provenant des
circuits dédiés à l’incendie. Le délai total (unité de commande et détecteurs de fumée) ne
doit pas dépasser 60 secondes. Aucun autre détecteur de fumée ne doit être raccordé à
ces circuits sans l’approbation des autorités compétentes locales.
Note Each protected circuit within this control is supervised
.
SUPPORT & WARRANTY
See Installation and Setup Guide P/N 800-25082 or higher.
For the latest documentation and online support information, please go to:
www.resideo.com
For the latest warranty information, please go to:
www.security.honeywellhome.com/warranty
Recommendations for Proper Protection
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help
Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72
noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all
rooms and areas of the household as follows: For minimum protection a smoke detector should
be installed outside of each separate sleeping area, and on each additional floor of a multi-floor
family living unit, including basements. The installation of smoke detectors in kitchens, attics
(finished or unfinished), or in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the
living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage
rooms, basements and attached garages.
In addition, we recommend the following:
•Install a smoke detector inside every bedroom where a smoker sleeps.
•Install a smoke detector inside every bedroom where someone sleeps with the door partly
or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the
hallway outside may not wake up the sleeper if the door is closed.
•Install a smoke detector inside bedrooms where electrical appliances (such as portable
heaters, air conditioners or humidifiers) are used.
•Install smoke detectors at both ends if the hallway is more than 40 feet (12 meters) long.
•Install smoke detectors in any room where an alarm control is located, or in any room
where alarm control connections to an AC source or phone lines are made. If detectors are
not so located, a fire within the room could prevent the control from reporting a fire or an
intrusion.
This Control Complies with NFPA Requirements for Temporal Pulse
Sounding of Fire Notification Appliances
Recommendations for Proper Intrusion Protection
•For proper intrusion coverage, sensors should be located at every possible point of entry to
a home or premises. This would include any skylights that may be present, and the upper
windows in a multi-level building.
•In addition, we recommend that radio backup be used in a security system. This will ensure
that alarm signals can be sent to the alarm monitoring station in the event that the
communications are out of order (if connected to an alarm monitoring station).
DINING
KITCHEN BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM BEDROOM
BDRM
DINING
LIVING ROOM
TV ROOM KITCHEN
BEDROOM BEDROOM
TO
BR
LVNG RM
BASEMENT
KTCHN
.
CLOSED
DOOR
GARAGE
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BDRM
floor_plan-001-V1
Federal Communications Commission & ISED Statements
The user shall not make any changes or modifications to the equipment unless authorized by
the Installation Instructions or User's Manual. Unauthorized changes or modifications could
void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use.
The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used
properly, that is, in strict accordance with the manufacturer's instructions, may cause
interference to radio and television reception. It has been type tested and found to comply with
the limits for a Class B computing device in accordance with the specifications in Part 15 of
FCC Rules, which are designed to provide reasonable protection against such interference in a
residential installation. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• If using an indoor antenna, replace it with a quality outdoor antenna.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver
are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
ISED CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / ISED STATEMENT
This device complies with Part 15 of the FCC Rules, and ISED’s license-exempt RSSs.
Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC et exempt de licence RSS ISED.
Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer
d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les
interférences causant une réception indésirable.
Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary of
Resideo Technologies, Inc., 2 Corporate Center Dr., Melville, NY 11747, Ph: 516-577-2000
The product should not be disposed of with other household waste. Check for the nearest
authorized collection centers or authorized recyclers. The correct disposal of end-of-life
equipment will help prevent potential negative consequences for the environment and human
health.
The Honeywell Home Trademark is used under license from Honeywell International
Inc. This product manufactured by Resideo Technologies, Inc. and its affiliates.
www.resideo.com
Resideo Technologies, Inc
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2020 Resideo Technologies, Inc. All rights reserved.
Ê800
Ê800Ê800
Ê800-
--
-25079fŠ
25079fŠ25079fŠ
25079fŠ
800-25079B 3/19 Rev. B

Other manuals for PROA7PLUS Series

1

This manual suits for next models

1

Other Honeywell Home Security System manuals

Honeywell Home Ademco Vista Series Operating instructions

Honeywell Home

Honeywell Home Ademco Vista Series Operating instructions

Honeywell Home Ademco Vista Series User manual

Honeywell Home

Honeywell Home Ademco Vista Series User manual

Honeywell Home Lynx 5210 User manual

Honeywell Home

Honeywell Home Lynx 5210 User manual

Honeywell Home VISTA-21iP User manual

Honeywell Home

Honeywell Home VISTA-21iP User manual

Honeywell Home SMART HOME SECURITY User manual

Honeywell Home

Honeywell Home SMART HOME SECURITY User manual

Honeywell Home Touchscreen 6290W User manual

Honeywell Home

Honeywell Home Touchscreen 6290W User manual

Honeywell Home HS351X User manual

Honeywell Home

Honeywell Home HS351X User manual

Honeywell Home PROSiXFOB Assembly instructions

Honeywell Home

Honeywell Home PROSiXFOB Assembly instructions

Honeywell Home PROA7PLUS Series Instruction manual

Honeywell Home

Honeywell Home PROA7PLUS Series Instruction manual

Honeywell Home TUXEDOW User manual

Honeywell Home

Honeywell Home TUXEDOW User manual

Honeywell Home HS3SS Series User manual

Honeywell Home

Honeywell Home HS3SS Series User manual

Honeywell Home TUXEDOW User manual

Honeywell Home

Honeywell Home TUXEDOW User manual

Honeywell Home TUXEDOW User manual

Honeywell Home

Honeywell Home TUXEDOW User manual

Honeywell Home Touchscreen 6290W Owner's manual

Honeywell Home

Honeywell Home Touchscreen 6290W Owner's manual

Honeywell Home PROSiXSIREN User manual

Honeywell Home

Honeywell Home PROSiXSIREN User manual

Honeywell Home HS342X User manual

Honeywell Home

Honeywell Home HS342X User manual

Honeywell Home Ademco Vista-V21SIALTE Assembly instructions

Honeywell Home

Honeywell Home Ademco Vista-V21SIALTE Assembly instructions

Honeywell Home Touchscreen 6290W User manual

Honeywell Home

Honeywell Home Touchscreen 6290W User manual

Honeywell Home HS331 Series User manual

Honeywell Home

Honeywell Home HS331 Series User manual

Honeywell Home Ademco Vista-21iPLTE User manual

Honeywell Home

Honeywell Home Ademco Vista-21iPLTE User manual

Honeywell Home ADEMCO VISTA-15P User manual

Honeywell Home

Honeywell Home ADEMCO VISTA-15P User manual

Honeywell Home Touchscreen 6290W User manual

Honeywell Home

Honeywell Home Touchscreen 6290W User manual

Honeywell Home Water Defense RWD41 User manual

Honeywell Home

Honeywell Home Water Defense RWD41 User manual

Honeywell Home Touchscreen 6290W User manual

Honeywell Home

Honeywell Home Touchscreen 6290W User manual

Popular Security System manuals by other brands

Ness Guardpost installation manual

Ness

Ness Guardpost installation manual

Interlogix RF-7220-07-1 Installation sheet

Interlogix

Interlogix RF-7220-07-1 Installation sheet

Tecnoalarm TP8-64 user manual

Tecnoalarm

Tecnoalarm TP8-64 user manual

Wheelock TB-591 installation instructions

Wheelock

Wheelock TB-591 installation instructions

Control Products WA-1000 user manual

Control Products

Control Products WA-1000 user manual

ADEMCO LYNX installation instructions

ADEMCO

ADEMCO LYNX installation instructions

Night Owl THD301 Series Quick setup guide

Night Owl

Night Owl THD301 Series Quick setup guide

Defender PHOENIX1 instruction manual

Defender

Defender PHOENIX1 instruction manual

FältCom ECII SE Manual and installation instructions

FältCom

FältCom ECII SE Manual and installation instructions

rodger Amigo manual

rodger

rodger Amigo manual

DSC PC2550 instruction manual

DSC

DSC PC2550 instruction manual

FRC TH6 Installation and setup guide

FRC

FRC TH6 Installation and setup guide

AINA PTT Smart Button quick guide

AINA

AINA PTT Smart Button quick guide

Feelsafe OMNI 3000 Programming instructions

Feelsafe

Feelsafe OMNI 3000 Programming instructions

Chaney Instrument AcuRite 08510 instruction manual

Chaney Instrument

Chaney Instrument AcuRite 08510 instruction manual

Call Aid UK 1142RX Operation & maintenance manual

Call Aid UK

Call Aid UK 1142RX Operation & maintenance manual

Bosch IRIS-Net user manual

Bosch

Bosch IRIS-Net user manual

Conrad ZM 02 owner's manual

Conrad

Conrad ZM 02 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.